1
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE
APPLICATIONS
Terence Hazel
Senior Member IEEE
Schneider Electric
38050 Grenoble
France
Abstract – The power requirements for large industrial sites
is increasing. Often there is also a requirement to reduce the
installation volume of electrical equipment in off-shore
facilities where every square meter is very expensive. One
means of reducing the amount of electrical equipment is to
use the generation voltage as the distribution voltage of the
site. This often however, results in very high values of short-
circuit current exceeding both the peak rating and breaking
capacity of switchgear. Fast-acting current limiting devices
can be installed in the electrical distribution system in order to
reduce the short-circuit current to acceptable values.
Index Terms – electrical substations, short-circuit current,
current limiters.
I. INTRODUCTION
In the past, when power requirements increased, the only
solution was to increase the voltage in order to meet the
limitations of nominal current and short-circuit current. This
meant using transformers to step-up the generated voltage to
33kV or higher, and then to step the voltage back down with
substation transformers in order to supply the loads. These
step-up and step-down transformers together with the
additional switchgear for their protection greatly increased the
amount of space required for the installation of the electrical
distribution equipment.
For grass-roots on-shore sites this design philosophy is still
used since it allows the use of standard electrical equipment.
For existing sites and for off-shore facilities there is often
insufficient room for the transformers. Should step-up and
step-down transformers not be used, it is necessary that the
switchgear be able to handle the very high values of short-
circuit current resulting from the use of a lower distribution
voltage. Since the short-circuit current will exceed both the
peak and the interrupting current ratings of standard
switchgear, the only choice is to limit the value of short-circuit
current that can occur.
Current limiting devices that can limit the peak current and
the interrupting current are available. How these devices
operate and where they can be used is the subject that will be
presented in this paper. In addition to the higher values of
short-circuit current, the nominal current will increase.
Solutions using circuit-breakers in parallel and alternating
load and source circuits in switchboards are techniques that
can be used to handle this problem which is important, but
not the subject of this paper.
In this paper, the term medium-voltage will be used for all
voltages above 1 kV up to 36 kV. The term high-voltage will
be used for voltages exceeding 36 kV.
II. POWER DISTRIBUTION IN INDUSTRIAL SITES
The type of electrical distribution system depends on many
factors, one of the most important being the amount of power
required. Other factors such as the availability of the power
supply are equally important but not directly related to the
maximum available short-circuit current. For the purpose of
this paper, a radial distribution will be used since it will
illustrate all the required concepts and makes the discussions
easier to understand. The extrapolation of the use of current
limiting devices to redundant distribution systems such as
commonly used in petro-chemical facilities is easily made.
A. Distribution systems for small sites
For sites where the installed power is less than
approximately 40 MW, the voltage at which the power is
generated can be used directly by the loads as shown in
Fig. 1. A typical voltage is 6.6 kV which is one of the most
commonly used for medium-voltage motors. The only
transformers required in this system are the distribution
transformers for supplying low-voltage loads. This is the
optimal design requiring the minimum number of transformers
and distribution system circuit-breakers.
B. Distribution systems for medium-sized sites
When the installed power increases, it is necessary to also
increase the voltage. Generator and large motors can
operate at 13.8 kV which is typically the highest utilization
voltage used for systems as shown in Fig. 2. The 13.8 kV is
also used as the distribution voltage for supplying the unit
substations located throughout the site.
Normally few motors will be supplied at 13.8 kV due to the
expense of using higher voltages. Typically most medium-
voltage motors will be supplied at 6.6 kV which requires