Telechargé par saha_baya

Basler Open Delta

publicité
APPLICATION
s
e
t
o
N
Published for the Basler Electric Power Systems Group
#PC-59N01 • August, 2004
The 59N and Broken Delta Applications
On an impedance grounded system, phase to ground
faults are detected by monitoring the zero sequence
component, V0, of the line voltages and tripping with
a 59N function (high V 0). Two ways relays determine
V0 are:
1) Numerically calculated V0 from phase-gnd
voltages. A relay monitors all phase-gnd voltages
from a set of 3 VTs connected Wye-gnd/Wyegnd. The relay calculates V 0 using the equation
V0 = (1/3)( VAG + VBG + VCG).
2) Measured 3V0 from Wye-Gnd/Broken Delta
VTs. A relay with a single voltage input monitors
the voltage across the
th e break in a set of 3 VTs
connected Wye-gnd/broken Delta. The voltage
across the broken delta is simply the
t he sum of system
phase-gnd voltages, or 3V 0. The Wye side of the
Wye-Gnd/Broken
Wye-Gnd/Broken delta VT can either be directly
connected to the high voltage terminals or to the
secondary of a main stepdown VT.
Method 1 is used by numeric multifunction relays,
such as the BE1-951, -1051, -IPS, and -GPS relays.
Most applications of such relays need (or work best
with) line-gnd voltage anyway, so the inclusion of the
V0 calculation and 59N protection requires no
additional inputs to the relay and, hence, is easily
included. Method 2 is a more historic method that
evolved before the era of numeric relays, but it still
sees substantial use, likely due to users being
comfortable with past practices, its ability to add a
small zero sequence load to help stabilize the system
neutral, and because it allows a simple relay to be
used. The BE1-59N was designed for this
application and is an easy relay to use and set.
Figure1:59NBrokenDeltaSchematic
Besides the BE1-59N, Basler’s BE1-951, -1051, -IPS,
and -GPS numeric relays can also monitor a broken delta
voltage via their VX input. Using numeric relays gives all the
advantages thereof, such as detailed event reports and
programmable logic. The BE1-951, -1051, and -IPS relays
also have the ability to perform the 67N function and have
the user selectable option of determining direction to a fault
by a number of means, including comparing the phase
relationship of V0 from the broken delta to I 0 or IG, so that
the BE1-951, -1051, and -IPS relays can effectively act as a
more modern way to do the work of the classic solid state
BE1-67N.
In method 2, it is common to place a resistor in the
broken delta as shown in Figures 1 and 2. One rationale for
the resistance is that the resistance stabilizes the measured
voltage. It does this by a) reducing the risk of
ferroresonance, and b) allowing the VT to act as a very
small ground bank. The ground bank effect will help hold
the system neutral voltage closer to ground, helping to
prevent small leakage impedance to ground from causing
high neutral shifts. The ground bank effect also provides a
means for bleeding off the capacitive voltage buildup
associated with arcing ground faults on high impedance
grounded systems. The ability of the VT and resistor to act
as a ground bank and hence stabilize the neutral is fairly
limited and will be covered further below.
The issue of whether an unloaded VT is at risk of
entering into ferroresonance is difficult to answer. One
circuit for ferroresonance can be seen if the delta presents
a path for a phase to ground voltage on one phase to
energize another phase via the delta, which in turn has a
capacitance to ground, creating an LC network where the L
is saturable. If the circuit is lossy due to the resistance in the
circuit, then resonance of the LC network is less likely, but
on the other hand, leaving the delta completely open
removes the resonant path, so an argument could be made
to leave the resistance out entirely if this is the circuit of
concern. Past practice by several generations of engineers
seems to indicate that including the resistance is advisable.
This application note will not try to analyze the matter any
further than indicated below.
Voltages During a Ground Fault
Refer to the phasor diagrams in Figure 2, Page 3.
During ideal normal operation with no ground fault or line
to ground current:
During a ground fault, virtually all of the faulted
phase's voltage is impressed upon the neutral impedance.
For a phase A to ground fault, Van=0, and the voltage
across the neutral resistor is essentially the negative of the
Phase A to neutral voltage. Mathematically:
which means:
which therefore means:
Since a broken delta sums the 3 phase voltages,
From this line of reasoning, one should be able to see
that the worst case steady state fundamental frequency
voltage seen at the broke n delta will be:
The VTR in the above equation is best thought of in
terms of the winding turns ratio, rather than voltage ratios.
This is highlighted because the question of whether one
should use VLL or VLN to calculate VTR is avoided if one
thinks in terms of winding turns ratio.
For an example, if normal system voltage was 13.8kV LL
and 7.97kVLG, and a VTR of 115 were used, for a phase A
fault, the worst case broken delta voltage would be:
With a VTR of 115, the normal secondary voltage
during unfaulted conditions on each leg of the delta will be:
During a fault, secondary voltage on the two unfaulted
phases rises to 120V (=13800/115). Note that 69.3 * 3 =
207.9V, which agrees with the earlier calculations for the
maximum broken delta voltage during the fault.
If the ground fault impedance is high or the source
ground impedance is low, the voltage that will arise during a
ground fault will be something less than 3 per unit. The
calculation of what will occur can be analyzed using a set of
simultaneous equations. The circuit in Figure 2 is analyzed
in a Mathcad™ (Revision 7) document, "59N_R#.MCD"
found in the "Downloads" section of the Basler Electric
web site, www.basler.com.
VT Voltage Rating
It is important to note that, during a ground fault, two
of the VTs must withstand and reproduce full line-line
voltage. It would b e an error to use a VT rated only for
line-ground voltage. For instance, in the wye-broken delta
system described above, the normal system voltage is
13.8kV LL and 7.97kVLG, and secondary voltage is 69.3
under normal operating conditions but rising to 120V
during a fault. The VT in this case needs to be rated for
13.8kV/120V.
Figure2:Phasordiagrams duringline-to-groundfault
Resistance Selection
To obtain the maximum capability of the resistor to
dampen system transients and dampen ferroresonant
circuits, a typical approach to sizing the resistor is to put in
one that can handle all the power that the VTs can supply
during a full neutral offset. Fully loading the VT will cause
some level of voltage drop and error in the secondary, but
if the VT is dedicated to the broken delta configuration, the
voltage drop that will re sult will not cause any i ll effects.
However, if the "aux VT" approach in Figure 1 is used,
then one might need to investigate if the fully loaded aux
VT will pull down the main VT secondary voltage and
affect other relaying in the system. Ignoring the voltage
drop issue, sizing of the resistor to bring the VTs to a high
loading level results in two approaches to sizing the
resistor:
a) size the resistor so that the amps drawn are equal to
the continuous current rating of the transformer bank, or
b) if the fault will be cleared quickly, size the resistor so
that power in the resistor is equal to the full 3 phase VA of
the transformer bank, which, as seen below, will
overcurrent the bank by a factor of sqrt(3).
a) Base resistance on VT continuous current rating
This approach needs to be used if the fault might be in
place for an extended period. Assume the previous
example where VSEC is 69.3 normally but rises to 120V
during a fault. Assume a VT rated at 500 VA per phase and
13.8kV/120V.
During a ground fault, ignoring voltage drop in the VT
when fully loaded, the resistor will see 207.9V per the
previous example. To limit current to 4.167A,
The power in the resistor will be:
Since it is anticipated that the fault might be held for an
extended period, the resistor must be sized to handle this
heat dissipation continuously.
b) Base resistance on VT 3 phase VA rating
This approach will overload the VTs and is appropriate only if the fault will be cleared before the overload can
affect the VTs. Assume, again, a VT rated at 500VA per
phase, for a total of 1500VA for all three phases. Also
ignore the voltage drop in the fully loaded VT and assume
that the full 207.9V from the previous calculations is seen
across the resistor. The resistance required to load the VT
bank to 1500VA will be:
where ts = time in seconds. Solving for the required
continuous rating:
In the above equation, if t is less than 1s, use t=1, and
if t>25s, then it may be best to consider using a fully rated
resistor. If a 28.8Ω resistor is to be used as in the above
example, but all faults will be cleared in 5 seconds, then by
the above equation and using a x2 safety margin, a 300W
resistor might be used (1500*(5/50)* (2) = 300).
Ground Bank Effect of a VT
The current drawn during the fault will be:
This current is sqrt(3) times the continuous current
rating of the VT, calculated previously. The power in the
resistor will be:
In this case, since the VT is overloaded, it is likely that
the intent is to clear the fault relatively quickly. Since the
fault will be cleared quickly, the short time rating of the
resistor might be considered, allowing a smaller resistor to
be used.
Resistor Short Time Power Rating
The power calculated in the above examples is rather
large. However, if the fault will be cleared quickly, then the
short time rating of the resistor can be used to allow a
smaller resistor watt rating. A "rule of thumb" is that a wirewound power resistor can handle a short time overload of:
P.A.E. Les Pins, 67319 Wasselonne Cedex FRANCE
Tel +33 3.88.87.1010 Fax +33 3.88.87.0808
e-mail: [email protected]
The ability of a VT to act as a small grounding bank,
and therefore limit neutral voltage shift, is fairly weak, but it
might be seen in cases where ground impedances are very
high. As a point of comparison, the 28.8 Ω resistor in the
previous example reflected to the primary by VTR2 (1152) is
381kΩ. This might help stabilize a substation bus or a short
transmission line with only minor phase to ground capacitance or leakage resistance. Directly related to this concept,
the current flowing in the delta will flow through the faulted
phase VT, which will tend to push some current from the
VT back into the ground fault. If the ground fault impedance is large, there can be some tendency for the VT to
sustain voltage on the faulted phase. The previously
mentioned Mathcad document that analyzes Figure 2 may
help you to determine if the ground bank effect might be
noticable in a ground fault in your system.
For More Information
For further information, visit the download section of
our website at www.basler.com to access product documentation on the BE1-59N, -951, -1051, -IPS, and -GPS,
the Mathcad file referenced on Page 2 of this Application
Note, and Application Notes on other topics.
To discuss your specific application, consult Basler at
the factory at (618) 654-2341.
Route 143, Box 269, Highland, Illinois U.S.A. 62249 328 North Zhongshan Road, Wujiang Economic Development Zone
Tel +1 618.654.2341 Fax +1 618.654.2351
Suzhou, Jiangsu Province, PRC 215200
e-mail: [email protected]
http://www.basler.com
PC-59N01 (08/04)
Tel +86(0)512 6346 1730 Fax +86(0)512 6346 1760
e-mail: [email protected]
Téléchargement