48049-101-61 CLL Circuit Breakers
08/01 Instruction Bulletin
5
© 1996–2001 Schneider Electric All Rights Reserved
English
CIRCUIT BREAKER WITH PADLOCK
ACCESSORY
TROUBLESHOOTING
Condition Possible Causes Solution
Circuit breaker fails to stay closed. 1. Magnetic trip adjustment too low.
2. Undervoltage trip not energized.
3. Shunt trip energized.
4. Short circuit or overload on system.
1. Adjust magnetic trip adjustment.
2. Energize undervoltage trip.
3. De-energize shunt trip.
4. Check system for short circuit or overload.
Circuit breaker trips, but no short circuit or overload is
evident. 1. Magnetic trip adjustment too low.
2. Voltage below undervoltage trip setting. 1. Adjust magnetic trip adjustment.
2. Check system for low voltage.
Push-to-trip button will not trip circuit breaker. Circuit breaker already tripped or OFF. Move circuit breaker handle to reset then to ON
position. Press push-to-trip button.
HAZARD OF PERSONAL INJURY OR
EQUIPMENT DAMAGE
Circuit breaker with padlock accessory installed
does not comply with IEC 947 isolation
requirements. Before locking handle off, make
sure circuit breaker is open by placing handle in
off position and checking that voltage is not
present on circuit breaker being protected.
Failure to follow this instruction can result in
death, serious injury or equipment damage.
WARNING
HAZARD OF ELECTRIC SHOCK, BURN, OR
EXPLOSION
Disconnect all power to electrical equipment
before working on circuit breaker. Turn off
circuit breaker.
Failure to follow these instructions will
result in death or serious injury.
DANGER