BEFORE YOU BEGIN
Read these instructions completely and carefully.
WARNING/AVERTISSEMENT
RISK OF ELECTRIC SHOCK
• Turn power off before inspection, installation or removal.
• Properly ground electrical enclosure.
RISK OF FIRE
• Follow all NEC and local codes.
• Use only UL approved wire for input/output connections.
Minimum size 18 AWG or 14 AWG for continuous runs.
• When using multi-branch wire circuits with a shared
neutral, do not operate any circuit with the neutral open.
Also ensure all neutral connections are secure before
energizing the circuit. An open neutral can cause an
overvoltage condition at the luminaire power supply.
RISQUES DE DÉCHARGES ÉLECTRIQUES
• Coupez l’alimentation avant d’inspecter, installer ou déplacer le luminaire.
• Assurez-vous de correctement mettre à la terre le boîtier d’alimentation électrique.
RISQUES D’INCENDIE
• Respectez tous les codes NEC et codes locaux.
• N’utilisezquedeslsapprouvésparULpourlesentrées/sortiesdeconnexion.
Taille minimum 18 AWG ou 14 AWG pour les rangées continues.
• Lorsque vous utilisez des circuits câblés à branches multiples avec un neutre
commun, ne mettez aucun circuit en service avec le neutre ouvert. Assurez-
vous également que tous les raccords neutres soit sécurisés avant de mettre le
circuit sous tension. Un neutre ouvert peut causer une condition de surtension
à l’alimentation du luminaire.
Prepare Electrical Wiring
Grounding Instructions
The grounding and bonding of the overall system
shall be done in accordance with National Electric
Code (NEC) Article 600 and local codes.
Electrical Requirements
TheLEDxturemustbesuppliedwith120-277VAC,
50/60Hzor347V,50/60Hzandprotectedbyamax.
20amperecircuitbreaker.Usemin.75°Csupply
conductor.347Vpowershouldonlybesuppliedto
luminaires with voltage code “D”.
IMPORTANT NOTE: LUS series luminaires come in two versions: continuous units (ISC series) and independent units (IS1 series). A
continuouselectricalrunwillconsistofanumberofcontinuousunitsuptoamaximumcurrentspeciedabove.Wheninstalling
luminairesusecleanglovesinordertoavoidfoulingthereectivesurface.Toinsureacleanxture,installthexturewiththeplastic
bagaroundthexture,andthenremoveplasticbaguponcompletionofanyandallconstructionrelatedactivity.
IMPORTANT - Maximum Length of Electrical Run
Voltage
Lumen Code
[42] [84] [52] [A0]
[62] [65] [85]
[A3] [A7]
[A1] [A2]
[B1] [B4]
120V 192’ 160’ 80’ 60’
277Vor347V 400’ 320’ 188’ 132’
• Maximumdrivercurrentthroughconnectedxtures
shallnotexceed15Aforlumencodes[42],[52],[62],
[84],or[A0].
• Maximumdrivercurrentthroughconnectedxtures
shallnotexceed12Aforlumencodes[65],[85],[A3],
[A7],[A1],[A2],[B1]or[B4].
1
Special Instruction for [TQ] and [TS] SKUs - Node Identication Label
Installation of an Independent Luminaire
Nodeidenticationlabelfortheluminaire.
Nodeidenticationlabelforthecustomer’soorplan.
Removetheknockoutplate.
Removeasmanyknockoutholesasrequired.
3knockoutholesareprovidedperluminaire.
Attachastrainrelieforconduittotheknockoutwiththe
wires passing through.
Connect the wires as follows:
a.Black=Line
b.White=Neutral
c.Green=Ground
d.Purple=‘+’0-10V
e.Grey=‘-‘0-10V
Choosethesuspensionmethodandinstallthebracketssuppliedwiththeluminaire.
6
5
4
3
2
2
1
2
1
Ensurethatthebracketisclippedintheheatsinkrails.
Installation of a Continuous Luminaire
NOTE:Forcontinuousluminaires,astarterkitmustbepurchasedseparately.
Follow the steps from the previous section.
ForbranchcircuitSKUs,thepowersupply(blackandwhite)inputwireswillnotbeconnected.Youmustchoose
what line to install the power supply on.
a.Thelinesareidentiedasthefollowing:
i.Black=Line#1
ii.White=Neutral#1
iii.Green=CommonGround
iv.Brown=Line#2
v.BrownwithWhitestripes=Neutral#2
OptionalbranchcircuitcanbeusedforA/BswitchingbymovingblackandwhitePSUwiresof“B”xturesonto
brown and brown/white lines.
On an additional circuit that requires its own neutral. Note that the brown/white is a neutral for the brown line.
For “EL” option code wiring see Emergency Light Supplement wiring diagram.
ForadditionalguidancepleaserefertoNEC2014Section410.64PartC-WiringSupplyingLuminaires
connected together.
For the dimming leads (grey and purple):
a. Use the harness provided in the Starter Kit to connect to the dimming leads.
b. Connect it to the grey and purple wire connectors at the end of the power supply.
c. Now you are ready to connect your wires to the dimming leads of the luminaire.
3
2
1
7
Oncetherstxtureiswiredcorrectly,attachthenextluminaire.
Removethepowersupplycoveroftherstluminairebypressingonthecircleandpushingbackward.
Slide the bridge lever at the end of the luminaire, it should be completely left or right.
Now you are ready to insert one luminaire in the other.
7
6
5
4
Locktheluminaireinplacebeforemovingtheleververtical.
Once2luminairesareattachandlockedinplace,youcancoveritwiththecontinuouscapprovidedwith
the luminaire.
Connectthewirestogetherwiththequickconnectors.
10
Youcannowre-attachthepowersupplycoverbypushingituntilitclipsin.