Phase Sequence / Failure Plus Time Delay
Séquence de phases / défaillance plus délai de temps
45080
TIMING DIAGRAM
GRAPHIQUE DE FONCTIONNEMENT
CONNECTION DIAGRAM
DIAGRAMME DE RACCORDEMENT
Exemples: Baisse de tension ou perte de phases/séquence de
phases
~
MOUNTING DETAILS
INSTRUCTIONS DE MONTAGE
R (L1)
Y (L2)
TYPICAL EXAMPLES
78
B (L3)
Under voltage or phase loss
Phase sequence
R
R
Y
B
Y
Y
R
Y
B
B
B
R
A1 15
R
Y
45080
Auxiliary
Supply
Monitored
3 Phase Supply
B
LOAD
99
16 18
A2
Insert screwdriver
to release clip
74
t
NOTE:-
t
t
~
INCORRECT PHASE SEQUENCE / ROTATION
PHASE FAILURE / LOSS
UNDER VOLTAGE
DELAY FROM FAULT - ADJUSTABLE
SÉQUENCE DE PHASES INCORRECTE / ROTATION
DÉFAILLANCE DE PHASES / PERTE
BAISSE DE TENSION
DÉLAI DE RÉACTION RÉGLABLE
INSTALLATION AND SETTING
MONTAGE ET INSTALLATION
-
BEFORE INSTALLATION, ISOLATE THE SUPPLY
- Connect the unit as shown in the diagram above.
- Set delay (from fault).
- Apply power (green LED on, red LED on, contacts 15 and 18 closed).
Troubleshooting
Terminal conductor size:
Approvals:
WWW.Z-TRAUQ.COM
AVANT MONTAGE, ISOLER L’ALIMENTATION
- Raccorder comme indiqué dans le diagramme ci-dessus.
- Régler le délai de réaction.
- Appliquer l’alimentation (DEL verte allumée, DEL rouge allumée, contacts 15 et 18
fermés).
- Vérifier les connexions et la tension présente.
- Si séquence incorrecte, inverser 2 phases.
TECHNICAL SPECIFICATION
Electrical life:
Housing:
Weight:
Mounting option:
-
Dépannage (pour régler un problème)
- Check wiring and voltage present.
- If incorrect sequence, reverse any 2 phases.
Supply voltage Un:
(AC: 48 - 63Hz)
Supply variation:
Isolation:
Power consumption:
Monitoring input / range:
Trip level:
Time delay (t):
Reset time:
Ambient temperature:
Relative humidity:
Contact rating:
Width / largeur 45 mm
= Voltage above required level. t = time delay (user adjustable)
FICHES TECHNIQUES
24V, 110V, 230V, 400V AC
(Galvanic isolated by transformer)
0.85 - 1.15 x Un
Overvoltage cat. III (IEC 664)
< 3VA
400V phase to phase
0.6 x 400V
0.1 - 10S (±20%) (from fault)
≈ 100mS
-20 to +60°C
+95%
SPDT
AC1 250V AC 10A (2500VA)
AC15 250V AC 6A
DC1 25V DC 10A (250W)
≥ 150,000 (AC1)
to UL94 VO
≈ 234g
to BS5584:1978
(EN50 002, DIN 46277-3)
≤ 2 x 1.5mm2 stranded
≤ 2 x 2.5mm2 solid
UL, CUL, CSA, IEC, CE
Alimentation:
(48 - 63Hz)
Variation d’alimentation:
Isolation:
Consommation:
Échelle de contrôle:
Seuil de déclenchement:
Délai de temps (t):
Réarmement:
Température ambiante:
Humidité relative:
Capacité de la sortie:
Durée de vie électrique:
Boîtier:
Poids:
Option de montage:
Calibre du conducteur:
Homologations:
877-798-7287
24V, 110V, 230V, 400V CA
(Protection galvanisée côté transformateur)
0.85 - 1.15 x Un
Surtension cat. III (IEC 664)
< 3VA
400V phase à phase
0.6 x 400V
0.1 - 10S (±20%) (défaillance)
≈ 100mS
-20 à +60°C
+95%
1 inverseur
AC1 250V CA 10A (2500VA)
AC15 250V CA 6A
DC1 25V CC10A (250W)
≥ 150,000 (AC1)
UL94 VO
≈ 234g
BS5584:1978
(EN50 002, DIN 46277-3)
≤ 2 x 1.5mm2 toronné
≤ 2 x 2.5mm2 solide
UL, CUL, CSA, IEC, CE