Phase Sequence / Failure Plus Time Delay Séquence de phases / défaillance plus délai de temps 45080 TIMING DIAGRAM GRAPHIQUE DE FONCTIONNEMENT CONNECTION DIAGRAM DIAGRAMME DE RACCORDEMENT Exemples: Baisse de tension ou perte de phases/séquence de phases ~ MOUNTING DETAILS INSTRUCTIONS DE MONTAGE R (L1) Y (L2) TYPICAL EXAMPLES 78 B (L3) Under voltage or phase loss Phase sequence R R Y B Y Y R Y B B B R A1 15 R Y 45080 Auxiliary Supply Monitored 3 Phase Supply B LOAD 99 16 18 A2 Insert screwdriver to release clip 74 t NOTE:- t t ~ INCORRECT PHASE SEQUENCE / ROTATION PHASE FAILURE / LOSS UNDER VOLTAGE DELAY FROM FAULT - ADJUSTABLE SÉQUENCE DE PHASES INCORRECTE / ROTATION DÉFAILLANCE DE PHASES / PERTE BAISSE DE TENSION DÉLAI DE RÉACTION RÉGLABLE INSTALLATION AND SETTING MONTAGE ET INSTALLATION - BEFORE INSTALLATION, ISOLATE THE SUPPLY - Connect the unit as shown in the diagram above. - Set delay (from fault). - Apply power (green LED on, red LED on, contacts 15 and 18 closed). Troubleshooting Terminal conductor size: Approvals: WWW.Z-TRAUQ.COM AVANT MONTAGE, ISOLER L’ALIMENTATION - Raccorder comme indiqué dans le diagramme ci-dessus. - Régler le délai de réaction. - Appliquer l’alimentation (DEL verte allumée, DEL rouge allumée, contacts 15 et 18 fermés). - Vérifier les connexions et la tension présente. - Si séquence incorrecte, inverser 2 phases. TECHNICAL SPECIFICATION Electrical life: Housing: Weight: Mounting option: - Dépannage (pour régler un problème) - Check wiring and voltage present. - If incorrect sequence, reverse any 2 phases. Supply voltage Un: (AC: 48 - 63Hz) Supply variation: Isolation: Power consumption: Monitoring input / range: Trip level: Time delay (t): Reset time: Ambient temperature: Relative humidity: Contact rating: Width / largeur 45 mm = Voltage above required level. t = time delay (user adjustable) FICHES TECHNIQUES 24V, 110V, 230V, 400V AC (Galvanic isolated by transformer) 0.85 - 1.15 x Un Overvoltage cat. III (IEC 664) < 3VA 400V phase to phase 0.6 x 400V 0.1 - 10S (±20%) (from fault) ≈ 100mS -20 to +60°C +95% SPDT AC1 250V AC 10A (2500VA) AC15 250V AC 6A DC1 25V DC 10A (250W) ≥ 150,000 (AC1) to UL94 VO ≈ 234g to BS5584:1978 (EN50 002, DIN 46277-3) ≤ 2 x 1.5mm2 stranded ≤ 2 x 2.5mm2 solid UL, CUL, CSA, IEC, CE Alimentation: (48 - 63Hz) Variation d’alimentation: Isolation: Consommation: Échelle de contrôle: Seuil de déclenchement: Délai de temps (t): Réarmement: Température ambiante: Humidité relative: Capacité de la sortie: Durée de vie électrique: Boîtier: Poids: Option de montage: Calibre du conducteur: Homologations: 877-798-7287 24V, 110V, 230V, 400V CA (Protection galvanisée côté transformateur) 0.85 - 1.15 x Un Surtension cat. III (IEC 664) < 3VA 400V phase à phase 0.6 x 400V 0.1 - 10S (±20%) (défaillance) ≈ 100mS -20 à +60°C +95% 1 inverseur AC1 250V CA 10A (2500VA) AC15 250V CA 6A DC1 25V CC10A (250W) ≥ 150,000 (AC1) UL94 VO ≈ 234g BS5584:1978 (EN50 002, DIN 46277-3) ≤ 2 x 1.5mm2 toronné ≤ 2 x 2.5mm2 solide UL, CUL, CSA, IEC, CE [email protected]