Battery Voltage Alarm Relay Relais d’alarme pour la tension de la batterie M1BVR TIMING DIAGRAM GRAPHIQUE DE FONCTIONNEMENT Supply/Monitoring Input CONNECTION DIAGRAM DIAGRAMME DE RACCORDEMENT MOUNTING DETAILS INSTRUCTIONS DE MONTAGE Supply/Monitoring -ve HYST 89 (excl. clips) +ve 45 Insert screwdriver to release clips A1 15 LEVEL 49 59 Withdraw clips fully when surface mounting 16 18 93 (+/- 1mm) A2 t Width / largeur 17.5 mm (DIN 43880) UNDER VOLTAGE - ADJUSTABLE TRIP LEVEL DELAY FROM FAULT – ADJUSTABLE DIN RAIL OR DIRECT MOUNTING SOUS-TENSION – SEUIL DE DÉCLENCHEMENT RÉGLABLE DÉLAI DE RÉACTION RÉGLABLE MONTAGE SUR RAIL DIN OU PLATINE INSTALLATION AND SETTING MONTAGE ET INSTALLATION - BEFORE INSTALLATION, ISOLATE THE SUPPLY - Connect the unit as shown in the diagram above. - Set trip level and delay. - Apply power (green LED on, red LED on, contacts 15 and 18 closed). - AVANT MONTAGE, ISOLER L'ALIMENTATION - Raccorder comme indiqué dans le diagramme ci-dessus. - Régler le seuil de déclenchement et le délai. - Appliquer l’alimentation (DEL verte allumée, DEL rouge allumée, contacts 15 et 18 fermés). Troubleshooting Dépannage (pour régler un problème) - Check wiring and voltage present. - Check polarity. - Vérifier les connexions et la tension présente. - Vérifier la polarité. FICHES TECHNIQUES TECHNICAL SPECIFICATION Supply/monitored voltage: Supply variation: Power consumption: Trip level: Hysteresis: Time delay (t): Accuracy: Trip level: Time delay Ambient temperature: Relative humidity: Contact rating: Electrical life: Housing: Weight: Mounting option: Terminal conductor size: Approvals: WWW.Z-TRAUQ.COM 12 - 24V DC 0.75 - 1.25 x Un < 1.8W 9 - 28V 5% 1 - 30S (from fault) ± 10% ± 20% -20 to +60°C +95% SPDT AC1 250V AC 8A (2000VA) AC15 250V AC 5A (no), 3A (nc) DC1 25V DC 8A (200W) ≥ 150,000 (AC1) to UL94 VO ≈ 60g to BS5584:1978 (EN50 002, DIN 46277-3) ≤ 2 x 2.5mm2 solid / stranded UL, CUL, CSA, IEC, CE Alimentation/Échelle contrôlée : Variation d'alimentation: Consommation: Seuil de déclenchement: Hystérésis: Délai de temps (t): Précision : Seuil de déclenchement Délai de temps Température ambiante: Humidité relative: Capacité de la sortie: Durée de vie électrique: Boîtier: Poids: Option de montage: Calibre du conducteur: Homologations: 877-798-7287 12 - 24V CC 0.75 - 1.25 x Un < 1.8W 9 - 28V 5% 1 - 30S (défaillance) ± 10 % ± 20 % -20 à + 60°C +95% 1 inverseur AC1 250V CA 8A (2000VA) AC15 250V CA 5A (travail), 3A (repos) DC1 25V CC 8A (200W) ≥ 150,000 (AC1) UL94 VO ≈ 60g BS5584:1978 (EN50 002, DIN 46277-3) ≤ 2 x 2.5mm2 solide/toronné UL, CUL, CSA, IEC, CE [email protected]