Telechargé par 321_ Wahyu Andrinoveza

IWCF Equipment

publicité
IWCF
Well Control
Lesson 7
Equipment
Part One
Contents
 API RP 53
Diverters
 Accumulator Unit
API Recommended Practice 53
• Goal of document
– Promoting personnel safety
– Public safety
– Integrity of the drilling equipment
• Purpose
– A guide for installation and testing of blowout
prevention equipment systems such as:
BOP’s, choke and kill lines, choke manifold, hydraulic
control system, etc.
3
API RP 53 discussed
• Diverters
• BOP’s
– Annular BOP
– Ram BOP
• Choke Manifold
• Kill and choke lines
• Hydraulic System
4
Diverter
• It is a low pressure annular preventer which can
divert or re-route flow rather than shut in the
well fluids. It is used during top-hole drilling.
• It can pack-off around:
–
–
–
–
Kelly
Drill string
Casing
Some on open hole (if having packing units)
• But it can not:
– Shut in the well
5
Diverter system components
• The diverter system consists of:
– Low pressure annular preventer
– Vent line connected to outlets below the packing
element.
– Full opening valves
– Control system to put valve on open position
before the diverter packer closes.
6
KFDJ Diverter
7
KFDJ Diverter
8
Hydril MSP Diverter
9
Diverter
•
•
•
•
•
•
•
•
1. closing port
2. outer packer (outer active seal)
3. flow line
4. flow line seals
5. insert packer
6. lockdown dogs
7. closed face
8. insert packer lockdown
dogs
10
Definition
• Rated Working Pressure:
– The maximum internal pressure that equipment design to contain or
control. (Correct)
– The maximum test pressure that equipment design to contain or
control. (Wrong)
• Test Pressure:
– Shell proof or hydrostatic testing pressure for all equipment must be
1.5 times RWP of the equipment.
• Anticipated surface pressure:
– ASP is the expected surface pressure or anticipated bottom hole
pressure minus anticipated hydrostatic pressure.
11
BOP
• At least once a week function test.
• Low pressure test 200 to 300 psi. and kept for at least 5 minutes.
• Initial High pressure test: RWP of BOP’s or wellhead stack whichever is
lower.
• Subsequent high pressure test: ASP but not greater than RWP of ram
BOP’s.
• Annular should be tested at ram BOP test pressure or 70% of RWP of
annular BOP.
• Pressure test should perform :
– Prior to spud
– After repair or reassemble of pressure containment seals on any part.
– Not exceed 21 days.
• The weakest part of BOP part is the rated working pressure of stack.
Example:
If we connect 5000 psi RWP flange on a 10K psi stack all stack will be down
graded to 5,000 psi stack.
12
Connection Types
• Studded
• Clamp Hub
• Flanged
(API)
13
Flange and ring gaskets
• Flange 6B
– Require Re-tightening
– R and Rx Ring gasket
– No face to face make up
• Flange 6BX
– Only BX ring gasket
• RX and BX gaskets are
pressure energized.
– Not interchangable.
– Must installed on clean
ring groove.
14
Groove and ring gaskets
15
Choke Manifold
• Must have:
– One hydraulic or Remote operated choke
– One Manual Choke
– A bypass line with the same diameter of manifold
and at least two valve in this bleeding line.
– Upstream valves, chokes and lines must meet
RWP.
– One valve should be installed downstream of each
choke.
16
Choke Manifold
• Must meet:
– Should have working pressure equal or greater
than RWP of BOP.
– Installed in safe place, accessible location outside
of the rig substructure.
– All valves should be full bore.
– Two valves which one is remotely operated must
be installed between BOP and Choke manifold.
– Must have backup air system.
– Bleed line should be at least equal in diameter
with choke line.
17
Choke manifold 2K, 3 K
18
Choke manifold 5K
19
Choke manifold 10K 15K
20
BOP Control system
• Precharge pressure:
– 1000 psi for 3000 psi system
– 1500 psi for 4500 and 5000 psi system
• Stored Hydraulic Pressure:
– Volume of fluid recoverable between MOP and precharge pressure.
• Usable Fluid:
– Volume of fluid between MOP and 200 psi above precharge pressure.
• Minimum calculated operating pressure:
– Is equal to MRWP of BOP divided by closing ratio.
21
BOP Control system
• Response time:
– Ram, 30 seconds or less
– Annular,
• Smaller than 18 ¾ , not more than 30 seconds
• Grater or equal 18 ¾ , 45 seconds
– HCR valves, not more than monitored closing time of Ram.
•
•
•
•
Only Nitrogen should be used.
Two independent pump
Air pump should work with minimum 75 psi air pressure.
Each pump has to provide a discharge pressure at least equal to
BOP control system working pressure.
22
BOP Control system
•
•
•
With pumps inoperative, accumulators should be capable of :
– Close one annular preventer (against zero wellbore pressure)
– Close all ram type
– Open one HCR valve
and Maintain 200 psi or more above precharge pressure
The pumps on accumulator system must be able to pressurized system from precharge pressure to maximum rated working pressure of system within 15 minutes.
With accumulators inoperative or shut off Each pump should be capable of:
– Close annular preventer on minimum pipe size
– Open HCR valve
And maintain pressure recommended by Manufacturer for seal off of pipe within
two minutes.
23
24
25
Separator or bladder type
Float or piston type
Accumulator Bottle Types
26
Safety Valves
• Float valve
– Flapper-type
– Spring loaded
• Kelly guards
– Upper kelly cock
– Lower kelly cock
• Inside BOP or NRV
• Dart or drop down
• All of which has to be tested at least
to ASP but limited to BOP RWP in use.
27
Float Valve
• Flapper-type
• Spring loaded
28
Kelly Guards
• Upper kelly
cock
• Lower kelly
cock
– Full opening
safety valve
(FOSV)
– Both Manually
operated
29
Gray Valve
• IBOP or Gray
Valve
• None return valve
(NRV)
• Non-return Safety
Valve
• Stab-in nonereturn
safety Valve
30
Gray Valve (NRSV)
• It will not allow wireline
to pass through.
• Needs pumping to read
SIDPP.
• Kept open by a Thandle.
• Has release rod to keep
in open position and can
not run into the well
while is open.
31
Drop Down check-guard valve
• It need landing
Sub. It must be
pumped down
• It can be retrieved
– By tripping out
– By wire line
• Also known as
drop or dart valve
32
Testers
• Plug Tester
• Cup Tester
– To test entire
casing head, side
outlets and casing
to wellhead seals.
33
Annular Preventer
• Closed on open hole or any object.
• Variable hydraulic pressure closing allow
tool joint to pass.
• Allow rotation or reciprocating on request.
• Packing Elements:
– Packing elements are selected based on
temperature and mud type.
– Has some metal segments to prevent rubber
extrusion and help support of string weight
during hang-up.
34
Packing elements:
35
Hydril GL
• It has secondary
chamber:
– Reduce closing
pressure
– Reduce closing
volume
• It can be used
both in land and
marine but
designed for
deepwater.
36
Hydril GL
37
Hydril GK
38
Hydril GK closing
39
Hydril DL
• Use special
packing unit with
steel segments
40
Shaffer
1- Head latched
2-Packing unit
3- opening port
4- Piston
5- closing port
41
Cameron D
1- Ring Groove
2- Head latched
3- Packing
4- Packing unit donut
5- Opening chamber
6- Piston
7- Closing chamber
42
43
Rams
•
Ram types:
– Pipe Ram
– Variable bore
– Shear/ Blind
•
•
•
•
Closing ratio : well bore pressure divided by pressure require to close the ram.
Weep hole: is a hole to monitor hydraulic and/ or mud leakage if primary seal
failed.
Secondary seal: an emergency sealing plastic which can be activated when leakage
monitored in weep hole.
Action to take if leakage monitored through the weep hole:
– While drilling or regular test:
•
Halt operation and repair equipment immediately.
– While well control operation:
•
Activate secondary seal and finish the job. Repair ram as soon as well is safe.
44
Ram secondary seal
45
Ram Packer extrusion
Ram packers are equipped
with heavy metals to
prevent extrusion and
helping pipe weight
handling.
46
Pipe Ram
47
Variable Ram
Shaffer multi ram
48
Shear Ram
49
Ram
50
Téléchargement