Check that the cameras setting and programmed as per project
requirements and manufacturer recommendations.
Installation of Wires:
Install cables in raceways and cable trays except within consoles,
back boxes, desks, and counters. Conceal raceway and cables
except in unfinished spaces.
Using CAT-6A type cable the maximum length of the cable not
exceeds more than 90 mtrs. Of manufacturer recommendation,
which will provided from structural cabling system supplier.
Comply with requirements for raceways and boxes specified in
Division 26 Section "Raceways, Boxes, Cable Tray, Cable
Ladder and Trunking".
Conceal conductors and cables in accessible ceilings, walls, and
floors where possible.
Wiring within Enclosures:
Bundle, lace, and train cables within enclosures.
Connect to terminal points with no excess and without exceeding
manufacturer's limitations on bending radius.
Grounding
Comply with requirements in Division 26 Section "Grounding and
Bonding for Electrical Systems." for grounding conductors and
connectors.
Comply with ADDC Electricity Wiring Regulations, Sections.
Bond metallic equipment to the system grounding bus bar, using
not smaller than the specified equipment grounding conductor by
ADDC Electricity Wiring Regulations, Sections.
Identification
Identify system components, wiring, and cabling complying with
ADDC Electricity Wiring Regulations. Comply with requirements
for identification specified in Division 26 Section "Identification for
Electrical Systems."
Programming
After making sure all the system installed in correct way
from Subcontractor and supplier, programming of the
system must take place before final testing and
commissioning accourding to Consultant requirement and
senario of the system.