Telechargé par Fayssal Fayssal

AN SWT 3000 C37.94

publicité
Table of Contents
SWT 3000 Stand-Alone Device with C37.94
Communication Solutions
Teleprotection Signalling
SWT 3000
V1.00
Application Notes
C53000-X6076-C237-1
1
Note
Please observe safety notes and warnings for your own safety.
Disclaimer of Liability
Copyright
This document has been subjected to rigorous technical review before being
published. It is revised at regular intervals, and any modifications and
amendments are included in the subsequent issues. The content of this document has been compiled for information purposes only. Although Siemens
AG has made best efforts to keep the document as precise and up-to-date
as possible, Siemens AG shall not assume any liability for defects and
damage which result through use of the information contained herein.
Copyright © Siemens AG 2012. All rights reserved.
This content does not form part of a contract or of business relations; nor
does it change these. All obligations of Siemens AG are stated in the relevant
contractual agreements.
SWT 3000 is a product of Siemens AG. Any unauthorized use is illegal. All
other designations in this document can be trademarks whose use by third
parties for their own purposes can infringe the rights of the owner.
Siemens AG reserves the right to revise this document from time to time.
Document version: 01
Date of issue: 03.2012
Product version: V1.00
The disclosure, duplication, distribution and editing of this document, or utilization and communication of the content are not permitted, unless authorized in writing. All rights, including rights created by patent grant or registration of a utility model or a design, are reserved.
Registered Trademarks
Table of Contents
1
SWT 3000 Stand-Alone Device with C37.94 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
1.1
Implementation of the New Feature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.2
Short Description of the New Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
1.3
Configuration of the Digital Line with C37.94. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.3.1
Configuring the Digital Line 1 or 2 with Type C37.94 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
1.3.2
FOM Type Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
3
Table of Contents
4
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
1
SWT 3000 Stand-Alone Device with C37.94
1.1
Implementation of the New Feature
6
1.2
Short Description of the New Feature
6
1.3
Configuration of the Digital Line with C37.94
8
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
5
SWT 3000 Stand-Alone Device with C37.94
1.1 Implementation of the New Feature
1.1
Implementation of the New Feature
.
The new functionality of C37.94 for SWT 3000 supports only the standalone device. The feature is
implemented in PowerSys versions ≥ P3.4.120, except for P3.5.100.
1.2
Short Description of the New Feature
.
The SWT 3000 is operating via optical fiber with multiplexer or data converter that supports IEEE C37.94. For
each transmission direction, a separate fiber is necessary.
Figure 1-1
SWT 3000 Configuration with C37.94
Table 1-1
Specification of the Fiber-Optic-Module FOS-3
Fiber type
Multi-mode with modules using 850 nm-wavelength
Wavelength
830 nm
Optical connector
LC connector
Range
Approx. 2 km at 850 nm (depending on the fiber used)
2 x LED
TX and RX-Alarm
Clock
FOM_C37.94 is DTE (for test purpose, a switchover to DCE is possible)
Note
For more information, refer to the Equipment Manual, Chapter Technical Data.
Note
1. Both SWT 3000 have the same FOM C37.94 module and the same configuration (that means the same data
rate).
2. FOM C37.94 can be used as primary or secondary path and in any combination with other digital or analog
interfaces on another path.
6
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
SWT 3000 Stand-Alone Device with C37.94
1.2 Short Description of the New Feature
CAUTION
Exercise caution with laser beams of the optical plug-in modules.
The laser beams can damage your eyes. If you do not comply with the safety notes, this will result in
medium severe or slight injuries.
✧
Do not look directly into the optical fiber terminals of the active optical plug-in modules, not even with
optical devices.
Note
Laser class 1 is adhered to in compliance with EN 60825-1 and EN 60825-2, in the case of ≤ 62.5 μm/125 μm
optical fibers.
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
7
SWT 3000 Stand-Alone Device with C37.94
1.3 Configuration of the Digital Line with C37.94
1.3
Configuration of the Digital Line with C37.94
1.3.1
Configuring the Digital Line 1 or 2 with Type C37.94
Configuration of C37.94
Figure 1-2
SWT 3000 - Configuration ---> System
Note
2 SWT 3000 which are equipped with FOM_C37.94 can be connected directly either with the DCE setting
(clock source) or the DTE setting. This connection is used only for testing the connection and functionality of
the FOM_C37.94.
In normal operation, the mode C37.94-DTE is used and the clock source is the external multiplexer or data
converter.
8
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
SWT 3000 Stand-Alone Device with C37.94
1.3 Configuration of the Digital Line with C37.94
Configuration of the Data Rate
If C37.94 has been selected in both digital interfaces boxes, the data rate 1 corresponds to the digital interface
1 and the data rate 2 corresponds to the digital interface 2 (refer to the following figure).
Figure 1-3
Configuring Both Digital Interfaces
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
9
SWT 3000 Stand-Alone Device with C37.94
1.3 Configuration of the Digital Line with C37.94
If only one interface has been selected, only the corresponding data-rate field is enabled. The other one is
disabled (refer to the following figure).
According to IEEE C37.94, the data rate must be 1 to 12 x 64 kbps. It can be selected via the list box of data
rate 1 or data rate 2 in tab System of the SWT 3000 – Configuration.
Figure 1-4
10
Configuring the Data Rate
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
SWT 3000 Stand-Alone Device with C37.94
1.3 Configuration of the Digital Line with C37.94
For the standard configuration C37.94 DTE, it is also possible to detect automatically the data rate of the DCE
device by selecting Auto in the data-rate field.
Figure 1-5
Configuring the Data Rate by Selecting the Option Auto
Note
For the setting of the Tx and Rx address, Siemens recommends using a pair of 2 different address numbers
as stated in the following table.
Table 1-2
Example of TX and RX Addresses
Device A
Device B
TX-add. = 1
RX-add. = 1
RX-add. = 2
TX-add. = 2
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
11
SWT 3000 Stand-Alone Device with C37.94
1.3 Configuration of the Digital Line with C37.94
1.3.2
FOM Type Information
.
The FOM type that was plugged into the slot can be read in the field Firmware-overview. The type must be
C37.94 (refer to the following figure).
Figure 1-6
12
Firmware-overview with C37.94 Type
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
SWT 3000 Stand-Alone Device with C37.94
1.3 Configuration of the Digital Line with C37.94
If a FOM board type other than FOS-3 is plugged into the slot and the FOM board is configured with the C37.94,
the hardware alarm and configuration alarm are issued. The type of FOM board appearing in the field must be
FOM (refer to the following figure).
Figure 1-7
Firmware-overview with FOM Type
Note
For more information, refer to the Equipment Manual, Chapter Technical Data.
■
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
13
SWT 3000 Stand-Alone Device with C37.94
1.3 Configuration of the Digital Line with C37.94
14
Communication Solutions Teleprotection Signalling, Application Notes
C53000-X6076-C237-1, Edition 03.2012
Téléchargement