BEAMA Guide to Surge Protection Devices (SPDs): selection, application and theory 5
FIGURES
Figure 1: Principle of protection system in parallel 10
Figure 2: Transient overvoltages (surges) 12
Figure 3: Normal Mains Supply Waveform 12
Figure 4: Outage 13
Figure 5: Undervoltages 13
Figure 6: Overvoltages 13
Figure 7: ‘Sags’ 14
Figure 8: ‘Swells’ 14
Figure 9: Radio Frequency Interference 14
Figure 10: Harmonics 15
Figure 11: NEMP/EMP 15
Figure 12: Potential current path in buildings connected
through data communication lines 17
Figure 13: Inductive coupling 18
Figure 14: Damage 20
Figure 15: Different areas of lightning strike 21
Figure 16: Current waveform 24
Figure 17: Voltage waveform 24
Figure 18: Direct Strike to Structure 25
Figure 19: Direct Strike to nearby service 25
Figure 20: Indirect Strike near Structure 26
Figure 21: Indirect Strike near Structure 26
Figure 22: Lightning Protection Zones concept 28
Figure 23: Lightning protection zones split by category 28
Figure 24: Basic concept of SPD operation 30
Figure 25: Simplified current division concept 33
Figure 26: Current division concept for multiple services 33
Figure 27: Principle of coordinated SPDs 35
Figure 28: Concept of Location Categories
(IEEE C62.41.10) 37
Figure 29: Additive effect of the inductive voltage
drop to the SPD’s protection level 39
Figure 30: Influence of SPD connecting lead lengths 40
Figure 31: Electromagnetic field formation 41
Figure 32: Parallel or shunt installed SPD with
closely bound connecting leads to cancel magnetic
fields around the leads. 41
Figure 33: Effect of cable length on protection level 42
Figure 34: Series connected SPD 42
Figure 35: Large distance between SPD and equipment 43
Figure 36: Voltage doubling due to equipment capacitance
and long inductive cable distance 43
Figure 37: Optimal positioning of parallel SPD with
dedicated OCPD 48
Figure 38: SPDs installed on load side of RCD 50
Figure 39: SPDs installed on supply side of RCD 51
Figure 40: Installation of Types 1, 2 & 3 SPDs, for
example in TN-C-S systems 52
Figure 41: Breaking the 50 centimetre rule 53
Figure 42: Installed adjacent to a consumer unit (retrofit) 54
Figure 43: Installed inside a consumer unit 54
Figure 44: Installed adjacent to a distribution board 55
Figure 45: Installed within to distribution board 55
Figure 46: Types of SPD 61
TABLES
Table 1: Types of loss 22
Table 2: Standardized test waveforms
with peak currents used to test SPDs at
each LPZ boundary 29
Table 3: Based on 3 phase TN-S or TN-C-S
system: 4 conductors (L1, L2, L3, N) plus
Earth - 4 modes to Earth 32
Table 4: Expected surge currents due to
lightning flashes (as per BS EN 62305-1) 34
Table 5: Required minimum impulse
withstand voltage for a 230/240V system 36
Figures and Tables