A
93 42 5
ABCDEF
The technical information contained in this document is the exclusive property of Schneider Electric and can not be used or disclosed to third parties of any kind without its written consent. Only those drawings and diagrams remitted after order booking are binding for execution. All devices shown in this diagrams are in open position, drawn out with operating mechanisms discharged and all power sources off.
MV CHARACTERISTICS
6
CUSTOMER NAME
PROJECT DESCRIPTION
PROJECT
PAGE
bFO OPP #
SINGLE LINE DIAGRAM
DRAWING DESCRIPTION
SCHNEIDER ELECTRIC
=
+++
REVISIONS :
1
PAGE DESCRIPTION
0 7 8
==
4
SETSEINT07
DRAWING NUMBER
ELECTRICAL CHARACTERISTICS :
RATED SERVICE VOLTAGE
RATED VOLTAGE 36kV
33kV
L1-R/L2-Y/L3-B
(UR / KV)
(US / KV)
RATED INSULATION LEVEL
POWER FREQUENCY WITHSTAND VOLTAGE 50Hz - 1MIN 70kVrms-1mn(Ud / RMS kV)
LIGHTNING IMPULSE WITHSTAND VOLTAGE 1.2/50 μs 170kV Peak
(Up / KV peak)
RATED NORMAL CURRENT AND MAXIMUM SHORT TIME WITHSTAND CURRENT
SHORT TIME WITHSTAND CURRENT ( Ik / kA - tk / s) 16kAeff 1s
SHORT CIRCUIT MAKING CURRENT AT 50Hz ( Ip / peak value KA) 40kA peak
MAIN BUSBAR RATED CURRENT 630A
RATED FREQUENCY 50Hz
INTERNAL ARC CLASSIFICATION
INTERNAL ARC CURRENT ( IA / KA ) 16kA
INTERNAL ARC CLASSIFICATION (IAC) AND TIME AFL (3 SIDES)- 1SEC
(tA / s)
NEUTRAL SYSTEM NETWORK UNKNOWN
BUSBAR COLOUR CODING
GENERAL CHARACTERISTICS :
SWITCHBOARD COLOR RAL9003
NOMV CABLE BOX
PACKING TYPE OVERSEAS
MV CB MECHANICAL CLOSING CANCELLATION NO
LV PROJECT CONTAINS SCHEMATIC IN THE MECHANISM OF LBS NO
ENGLISHLABELING LANGUAGE
CB ASSEMBLY (OPEN+CLOSE COIL)+MOTOR
O-0.3SEC-CO-3MIN-COCB OPERATING SEQUENCE
CB CABLING REVISION NO
INTERCUBICLE CABLE CONNECTION
CUBICLE DESTINATION
AVERAGE RELATIVE HUMIDITY ≤95% ON 24 H / ≤90% ON 1 MONTH
AMBIENT TEMPERATURE <40°
ALTITUDE <1000m
AMBIENT
DEGREE OF PROTECTION (IP) IP3X UNITS IP2XC BETWEEN
COMPARTMENTS
NOMV COMPARTMENT LIGHTING
NOPRESSURE SWITCH ON LBS
ABROAD
CUBICLE HEATING YES (BY THERMOSTAT)
L.V. HEATER NO
ENLARGED LV COMPARTMENT NO
LV COMPARTMENT LIGHTING NO
NO