Application of Shunt Trip DC Switch on
String Inverter
Remote shutdown functions based on shut trip DC switch
The software developed for the shunt trip switch in GW250KN-HT will:
1. Accumulate the trip times when the trip current is greater than 20A. Until the accumulated times exceed 10
times, a trip switch fault warning will be issued without affecting the normal grid connection of the inverter.
2. Record the trip time and be monitored by SolarGo App, and be reset to zero when being replaced.
Based on the above software logics, there are two major functions to protect the inverter:
Operation guide of shunt DC switch
1. The inverter happened with PV Reverse Polarity or PV Short Circuit, the DSP of inverter will trip the DC switch,
and trigger the following alarms accordingly, which will be showed in the LCD, SEMS and SolarGo:
1) PV Reverse Fault:
2) PV Short Failure
2. The O&M team heads to the project site to check the inverter with the fault alarm, clear the alarm and reset
the DC trip switch.
3. Reset the trip time on SolarGo when replacing the DC trip switch.