Installation Operation Maintenance Cooling only: CGAN 209-210-211-212-213-214 CG-SVX07A-E4 General information Foreword Warnings and cautions These instructions are given as a guide to good practice in the installation, start-up, operation, and maintenance by the user, of Trane CGAN 209-214 chillers. They do not contain full service procedures necessary for the continued successful operation of this equipment. The services of a qualified technician should be employed through the medium of a maintenance contract with a reputable service company. Read this manual thoroughly before unit start-up. Warnings and Cautions appear at appropriate sections throughout this manual. Your personal safety and the proper operation of this machine require that you follow them carefully. The constructor assumes no liability for installations or servicing performed by unqualified personnel. Units are assembled, pressure tested, dehydrated, charged and run tested before shipment. For information about the unit controller, refer to the controller's user guide. WARNING! : Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION! : Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices or for equipment or property-damage-only accidents. Safety recommendations To avoid death, injury, equipment or property damage, the following recommendations should be observed during maintenance and service visits: 1. The maximum allowable pressures for system leak testing on low and high pressure side are given in this manual. Always provide a pressure regulator. 2. Disconnect the main power supply before any servicing on the unit. 3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel. 2 CG-SVX07A-E4 General information Reception Warranty On arrival, inspect the unit before signing the delivery note. Warranty is based on the general terms and conditions of the manufacturer. The warranty is void if the equipment is repaired or modified without the written approval of the manufacturer, if the operating limits are exceeded or if the control system or the electrical wiring is modified. Damage due to misuse, lack of maintenance or failure to comply with the manufacturer's instructions or recommendations is not covered by the warranty obligation. If the user does not conform to the rules of this manual, it may entail cancellation of warranty and liabilities by the manufacturer. Reception in France only: In case of visible damage: The consignee (or the site representative) must specify any damage on the delivery note, legibly sign and date the delivery note, and the truck driver must countersign it. The consignee (or the site representative) must notify Trane Epinal Operations - Claims team and send a copy of the delivery note. The customer (or the site representative) should send a registered letter to the last carrier within 3 days of delivery. Note: for deliveries in France, even concealed damage must be looked for at delivery and immediately treated as visible damage. Reception in all countries except France: In case of concealed damage: The consignee (or the site representative) must send a registered letter to the last carrier within 7 days of delivery, claiming for the described damage. A copy of this letter must be sent to Trane Epinal Operations - Claims team. CG-SVX07A-E4 Refrigerant The refrigerant provided by the manufacturer meets all the requirements of our units. When using recycled or reprocessed refrigerant, it is advisable to ensure its quality is equivalent to that of a new refrigerant. For this, it is necessary to have a precise analysis made by a specialized laboratory. If this condition is not respected, the manufacturer warranty could be cancelled. 3 General information 4 Maintenance contract Training It is strongly recommended that you sign a maintenance contract with your local Service office. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty. To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown. CG-SVX07A-E4 Contents General information 2 General data 6 Installation 11 Unit nameplate Foundations Isolation and Sound Emission Isolating rubber pads Neoprene Isolator Installation (option) Clearance Lifting and Moving Instructions Drainage Water treatment Water connections Minimal installation water content Winter freeze protection Expansion valves settings Electrical connections General start-up 11 11 11 12 12 12 14 15 15 16 19 21 22 23 24 Start-up preparation 24 Start-up 25 Operation 30 Control system Unit operation Weekly start-up Weekend shutdown Seasonal shutdown Seasonal start-up Maintenance 30 30 30 30 31 31 32 Troubleshooting guide CG-SVX07A-E4 35 5 General Data Table 1 - General data CGAN Standard R407C CGAN 209 Standard R407C Eurovent Performances (1) Net Cooling Capacity (kW) 287.7 Total Power input in cooling (kW) 107.4 COP 2.68 Evaporator water pressure drop (kPa) 33 Available head pressure (5) Low head pressure /standard head pressure (kPa) 104 / 161 Main Power supply 400/3/50 Sound Power Level (5) (dBA) 95 System Data Number of refrigerant circuits 2 Number of capacity steps 4 Minimum capacity (%) 23 Units Amps Nominal (4) (A) 247 Start-up Amps Standard unit (A) 509 With soft starter option (A) 381 Short circuit unit capacity (kA) 15 Max supply cable size (mm²) 150 Min supply cable size (mm²) 240 Compressor Number 4 Type Model 2 X (25T+30T) Rated Amps (compA/CompB) (A) 52/62.5 Locked rotor Amps (compA/CompB) (A) 272/310 Motor RPM (rpm) 2900 Power factor (compA/CompB) 0.87/0.87 Sump Heater (W) 150 Evaporator Number 1 Type Water volume (total) (l) 26.8 Antifreeze Heater (W) 200 Unit water connection Chilled water (Inch/mm) 4" (100) Type Fan Type Number 6 Diameter (mm) 760 Drive type Number of speeds 1 Air flow (m3/h) 117300 Motor HP (2) (kW) 9.4 Rated Amps (2) (A) 19.6 Motor RPM (rpm) 915 Dimensions Height (mm) 2323 Length (mm) 5135 Width (mm) 2230 Operating Weight (kg) 2680 Shipping Weight (kg) 2650 Refrigerant Charge (3) Circuit 1/Circuit 2 (kg) 41/41 Oil Charge per circuit Circuit 1/Circuit 2 (l) 12.6/12.6 (1) (2) (3) (4) (5) 6 CGAN 210 Standard R407C CGAN 211 Standard R407C CGAN 212 Standard R407C CGAN 213 Standard R407C CGAN 214 Standard R407C 315.6 120.4 2.62 35 350.2 130.2 2.69 34 389.2 139.4 2.79 42 428.1 155.8 2.75 43 462.1 171.6 2.69 50 93 / 155 400/3/50 95 105 / 149 400/3/50 95 84 / 133 400/3/50 96 69 / 120 400/3/50 96 62 / 119 400/3/50 96 2 4 25 2 5 19 2 6 17 2 6 15 2 6 17 269 282 326 359 392 531 403 15 150 240 544 416 15 185 240 551 443 15 185 240 621 493 15 240 240 654 526 15 240 240 4 5 6 6 2 X (30T+30T) 62.5/62.5 310/310 2900 0.87/0.87 150 6 Scroll 3 x 25T+2 x 30T 2 x (25T+25T+25T) 52/62.5 52/52 272/310 272/272 2900 2900 0.87/0.87 0.87/0.87 150 150 1 1 29.2 200 35.6 200 4" (100) 4" (100) 1 Brazed plate 35.6 200 3 x 25T+3 x 30T 2 x (30T+30T+30T) 52/62.5 62.5/62.5 272/310 310/310 2900 2900 0.87/0.87 0.87/0.87 150 150 1 1 42.0 200 42.0 200 4" (100) 4" (100) 4" (100) 8 760 8 760 8 760 Victaulic Propeller 6 760 7 760 1 117300 9.4 19.6 915 1 131000 11.0 22.8 915 1 144700 12.6 26.1 915 1 141900 12.6 26.1 915 1 139100 12.6 26.1 915 2323 5135 2230 2710 2680 2323 5135 2230 3070 3030 2323 5135 2230 3370 3330 2323 5135 2230 3490 3450 2323 5135 2230 3590 3550 41/41 56/41 56/56 60/56 60/60 12.6/12.6 18.9/12.6 18.9/18.9 18.9/18.9 18.9/18.9 Direct drive at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) total per circuit Max rated conditions. Dual Pump Option CG-SVX07A-E4 General Data Table 2 - General data CGAN Super Quiet R407C CGAN 209 Super Quiet R407C Eurovent Performances (1) Net Cooling Capacity 287.5 Total Power input in cooling 104.8 COP 2.74 Evaporator water pressure drop (kPa) 33 Available head pressure (5) Low head pressure / standard head pressure (kPa) 104 / 161 Main Power supply 400/3/50 Sound Power Level (5) (dBA) 90 System Data Number of refrigerant circuits 2 Number of capacity steps 4 Minimum capacity (%) 23 Units Amps Nominal (4) (A) 247 Start-up Amps Standard unit (A) 509 With soft starter option (A) 381 Short circuit unit capacity (kA) 15 Max supply cable size (mm²) 150 Min supply cable size (mm²) 240 Compressor Number 4 Type Model 2 X (25T+30T) Rated Amps (compA/CompB) (A) 52/62.5 Locked rotor Amps (compA/CompB) (A) 272/310 Motor RPM (rpm) 2900 Power factor (compA/CompB) 0.87/0.87 Sump Heater (compA/CompB) (W) 150 Evaporator Number 1 Type Water volume (total) (l) 26.8 Antifreeze Heater (W) 200 Unit water connection Chilled water (Inch/mm) 4" (100) Type Fan Type Number 8 Diameter (mm) 760 Drive type Number of speeds 1 Air flow (m3/h) 115400 Motor HP (2) (kW) 4.5 Rated Amps (2) (A) 10.9 Motor RPM (rpm) 690 Dimensions Height (mm) 2323 Length (mm) 5135 Width (mm) 2230 Operating Weight (kg) 2850 Shipping Weight (kg) 2820 Refrigerant Charge (3) Circuit 1/Circuit 2 (kg) 41/41 Oil Charge per circuit Circuit 1/Circuit 2 (l) 12.6/12.6 (1) (2) (3) (4) (5) CGAN 210 Super Quiet R407C CGAN 211 Super Quiet R407C CGAN 212 Super Quiet R407C CGAN 213 Super Quiet R407C CGAN 214 Super Quiet R407C 315.3 117.8 2.68 35 344.6 130.5 2.64 33 377.5 142.7 2.65 40 412.3 162.7 2.53 40 442.3 181.8 2.43 44 93 / 155 400/3/50 90 106 / 150 400/3/50 90 87 / 136 400/3/50 90 74 / 125 400/3/50 90 69 / 124 400/3/50 91 2 4 25 2 5 19 2 6 17 2 6 15 2 6 17 269 282 326 359 392 531 403 15 150 240 544 416 15 185 240 551 443 15 185 240 621 493 15 240 240 654 526 15 240 240 4 5 6 6 2 X (30T+30T) 62.5/62.5 310/310 2900 0.87/0.87 150 6 Scroll 3 x 25T+2 x 30T 2 x (25T+25T+25T) 52/62.5 52/52 272/310 272/272 2900 2900 0.87/0.87 0.87/0.87 150 150 1 1 29.2 200 35.6 200 4" (100) 4" (100) 8 760 8 760 1 115400 4.5 10.9 690 1 Brazed plate 35.6 200 3 x 25T+3 x 30T 2 x (30T+30T+30T) 52/62.5 62.5/62.5 272/310 310/310 2900 2900 0.87/0.87 0.87/0.87 150 150 1 1 42 200 42 200 4" (100) 4" (100) 8 760 8 760 8 760 1 112600 4.5 10.9 690 1 109700 4.5 10.9 690 1 107100 4.5 10.9 690 1 104500 4.5 10.9 690 2323 5135 2230 2880 2850 2323 5135 2230 3220 3180 2323 5135 2230 3490 3450 2323 5135 2230 3620 3580 2323 5135 2230 3720 3680 41/41 56/41 56/56 60/56 60/60 12.6/12.6 18.9/12.6 18.9/18.9 18.9/18.9 18.9/18.9 4" (100) Victaulic Propeller Direct drive at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) total per circuit Max rated conditions. Dual Pump Option CG-SVX07A-E4 7 General Data Table 3 - General data CGAN Standard R22 Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling COP Evaporator water pressure drop (kPa) Available head pressure (5) Low head pressure / standard head pressure (kPa) Main Power supply Sound Power Level (5) (dBA) System Data Number of refrigerant circuits Number of capacity steps Minimum capacity (%) Units Amps Nominal (4) (A) Start-up Amps Standard unit (A) With soft starter option (A) Short circuit unit capacity (kA) Max supply cable size (mm²) Min supply cable size (mm²) Compressor Number Type Model Rated Amps (compA/CompB) (A) Locked rotor Amps (compA/CompB) (A) Motor RPM (rpm) Power factor (compA/CompB) Sump Heater (W) Evaporator Number Type Water volume (total) (l) Antifreeze Heater (W) Unit water connection Chilled water (Inch/mm) Type Fan Type Number Diameter (mm) Drive type Number of speeds Air flow (m3/h) Motor HP (2) (kW) Rated Amps (2) (A) Motor RPM (rpm) Dimensions Height (mm) Length (mm) Width (mm) Operating Weight (kg) Shipping Weight (kg) Refrigerant Charge (3) Circuit 1/Circuit 2 (kg) Oil Charge per circuit Circuit 1/Circuit 2 (l) (1) (2) (3) (4) (5) 8 CGAN 209 Standard R22 CGAN 210 Standard R22 CGAN 211 Standard R22 CGAN 212 Standard R22 CGAN 213 Standard R22 CGAN 214 Standard R22 282.1 101.3 2.78 31 311.6 117.2 2.66 34 343.6 123.6 2.78 33 376.1 130.1 2.89 39 415.5 148.9 2.79 41 453.6 167.3 2.71 49 102 / 159 400/3/50 95 91 / 153 400/3/50 95 103 / 147 400/3/50 95 81 / 130 400/3/50 96 65 / 115 400/3/50 96 58 / 115 400/3/50 96 2 4 23 2 4 25 2 5 19 2 6 17 2 6 15 2 6 17 247 269 282 326 359 392 509 381 15 150 240 531 403 15 150 240 544 416 15 185 240 551 443 15 185 240 621 493 15 240 240 654 526 15 240 240 4 4 5 6 6 2 X (25T+30T) 52/62.5 272/310 2900 0.87/0.87 150 2 X (30T+30T) 62.5/62.5 310/310 2900 0.87/0.87 150 3 x 25T+3 x 30T 52/62.5 272/310 2900 0.87/0.87 150 2 x (30T+30T+30T) 62.5/62.5 310/310 2900 0.87/0.87 150 1 1 1 1 1 35.6 200 42 200 42 200 4" (100) 4" (100) 4" (100) 8 760 8 760 8 760 6 Scroll 3 x 25T+2 x 30T 2 x (25T+25T+25T) 52/62.5 52/52 272/310 272/272 2900 2900 0.87/0.87 0.87/0.87 150 150 1 Brazed plate 26.8 200 29.2 200 35.6 200 4" (100) 4" (100) 4" (100) Victaulic Propeller 6 760 6 760 7 760 1 117300 9.4 19.6 915 1 117300 9.4 19.6 915 1 131000 11.0 22.8 915 1 144700 12.6 26.1 915 1 141900 12.6 26.1 915 1 139100 12.6 26.1 915 2323 5135 2230 2680 2650 2323 5135 2230 2710 2680 2323 5135 2230 3070 3030 2323 5135 2230 3370 3330 2323 5135 2230 3490 3450 2323 5135 2230 3590 3550 41/41 41/41 56/41 56/56 60/56 60/60 12.6/12.6 12.6/12.6 18.9/12.6 18.9/18.9 18.9/18.9 18.9/18.9 Direct drive at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) total per circuit Max rated conditions. Dual Pump Option CG-SVX07A-E4 General Data Table 4 - General data CGAN Super Quiet R22 Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling COP Evaporator water pressure drop (kPa) Available head pressure (5) Low head pressure (kPa) Main Power supply Sound Power Level (5) (dBA) System Data Number of refrigerant circuits Number of capacity steps Minimum capacity (%) Units Amps Nominal (4) (A) Start-up Amps Standard unit (A) With soft starter option (A) Short circuit unit capacity (kA) Max supply cable size (mm²) Min supply cable size (mm²) Compressor Number Type Model Rated Amps (compA/CompB) (A) Locked rotor Amps (compA/CompB) (A) Motor RPM (rpm) Power factor (compA/CompB) Sump Heater ( (W) Evaporator Number Type Water volume (total) (l) Antifreeze Heater (W) Unit water connection Chilled water (Inch/mm) Type Fan Type Number Diameter (mm) Drive type Number of speeds Air flow (m3/h) Motor HP (2) (kW) Rated Amps (2) (A) Motor RPM (rpm) Dimensions Height (mm) Length (mm) Width (mm) Operating Weight (kg) Shipping Weight (kg) Refrigerant Charge (3) Circuit 1/Circuit 2 (kg) Oil Charge per circuit Circuit 1/Circuit 2 (l) (1) (2) (3) (4) (5) CGAN 209 Super Quiet R22 CGAN 210 Super Quiet R22 CGAN 211 Super Quiet R22 CGAN 212 Super Quiet R22 CGAN 213 Super Quiet R22 CGAN 214 Super Quiet R22 282.0 98.6 2.86 30 311.4 114.6 2.72 33 339.1 123.6 2.74 33 366.7 133.0 2.76 36 405.0 155.2 2.61 36 441.9 177.5 2.49 44 108 / 165 400/3/50 90 96 / 158 400/3/50 90 111 / 155 400/3/50 90 91 / 138 400/3/50 90 74 / 126 400/3/50 90 69 / 124 400/3/50 91 2 4 23 2 4 25 2 5 19 2 6 17 2 6 15 2 6 17 247 269 282 326 359 392 509 381 15 150 240 531 403 15 150 240 544 416 15 185 240 551 443 15 185 240 621 493 15 240 240 654 526 15 240 240 4 4 5 6 6 2 X (25T+30T) 52/62.5 272/310 2900 0.87/0.87 150 2 X (30T+30T) 62.5/62.5 310/310 2900 0.87/0.87 150 3 x 25T+3 x 30T 52/62.5 272/310 2900 0.87/0.87 150 2 x (30T+30T+30T) 62.5/62.5 310/310 2900 0.87/0.87 150 1 1 1 1 1 35.6 200 42 200 42 200 4" (100) 4" (100) 4" (100) 8 760 8 760 8 760 6 Scroll 3 x 25T+2 x 30T 2 x (25T+25T+25T) 52/62.5 52/52 272/310 272/272 2900 2900 0.87/0.87 0.87/0.87 150 150 1 Brazed plate 26.8 200 29.2 200 35.6 200 4" (100) 4" (100) 4" (100) Victaulic Propeller 8 760 8 760 8 760 1 115400 4.5 10.9 690 1 115400 4.5 10.9 690 1 112600 4.5 10.9 690 1 109700 4.5 10.9 690 1 107100 4.5 10.9 690 1 104500 4.5 10.9 690 2323 5135 2230 2850 2820 2323 5135 2230 2880 2850 2323 5135 2230 3220 3180 2323 5135 2230 3490 3450 2323 5135 2230 3620 3580 2323 5135 2230 3720 3680 41/41 41/41 56/41 56/56 60/56 60/60 12.6/12.6 12.6/12.6 18.9/12.6 18.9/18.9 18.9/18.9 18.9/18.9 Direct drive at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) total per circuit Max rated conditions. Dual Pump Option CG-SVX07A-E4 9 General Data Table 5 - General data - Hydraulic module (option) Rated Amps (1) (A) Motor RPM (rpm) 14,7 2900 Water strainer diameter (inches) 4 Expansion tank volume (l) 50 User volume expansion capacity (2) (l) 3000 Max. water-side operating pressure without hydraulic module (kPa) 1000 with hydraulic module (kPa) 400 Hydraulic module additional weight (1) (kg) 300 Water tank volume (option) (l) 600 Water tank additional shipping weight (kg) 240 (1) For dual pump standard head pressure (2) Hydrostatic pressure 3 bar at 45°C with -12°C mini 10 CG-SVX07A-E4 Installation Unit nameplate Foundations The unit nameplate gives the complete model reference numbers. The unit power rating is shown, and power supplies should not deviate by more than 5 % from the rated power. Compressor motor amperage is shown in box I.MAX. The customer's electrical installation must be able to withstand this current. Provide rigid, non-warping mounting pads or a concrete foundation of sufficient strength and mass to support the unit operating weight (that is, including completed piping, and full operating charges of refrigerant, oil, and water). Refer to General Data section for operating weights. After it is in place, the unit must be level within 6 mm over its length and width. Trane is not responsible for equipment problems resulting from an improperly designed or constructed foundation. Isolation and Sound Emission The most effective form of isolation is to locate the unit away from any sound-sensitive area. Structurally transmitted sound can be reduced by elastomeric vibration eliminators. Spring isolators are not recommended. Consult an acoustical engineer in critical sound applications. For maximum isolation effect, isolate water lines and electrical conduit. Wall sleeves and rubber isolated piping hangers can be used to reduce the sound transmitted through water piping. To reduce the sound transmitted through electrical conduit, use flexible electrical conduit. National and local codes on sound emissions should always be considered. Because the environment in which a sound source is located affects sound pressure, unit placement must be carefully evaluated. Sound-power levels for Trane air-cooled chillers are available on request. Figure 1 - Unit isolation recommendations 4 1 3 4 3 1 2 1 2 3 4 = = = = Flex conduit control power Concrete base Neoprene isolators Elastomeric vibration eliminators CG-SVX07A-E4 11 Installation Isolating rubber pads Clearance 8 pads are supplied as standard with the unit and should be placed between the supporting floor and the unit to isolate from the ground. Respect recommended clearance around the unit to allow maintenance operation to take place without obstruction and recommended clearance around condenser. Also as on option pads might be replaced by neoprene isolators which are to be mounted on site as it is indicated on the submittals. Trane does not recommend installing spring isolators. Neoprene Isolator Installation (option) Secure the isolators to the mounting surface using the mounting slots in the isolator base plate. DO NOT fully tighten the isolator mounting bolts at this time. See unit submittals for isolator placement, maximum weights, and isolator diagrams. Align the mounting holes in the base of the unit with the threaded positioning pins on the top of the isolators. Lower the unit onto the isolators and secure the isolator to the unit with a nut. The maximum isolator deflection should be 6 mm. Level the unit carefully. Fully tighten the isolator mounting bolts. 12 Vertical clearance Vertical condenser air discharge must be unobstructed. While it is difficult to predict the degree of warm air recirculation, a unit installed as shown in Figure 2 would have its capacity and efficiency significantly reduced and could possibly encounter nuisance high head pressure tripouts. Performance data is based on free air discharge. Figure 2 - Vertical air discharge CG-SVX07A-E4 Installation Lateral clearance Walled enclosure installations The condenser coil inlet must not be obstructed. Thanks to its W-shaped condenser coil design, AquaStream2® lateral clearance is one of the best of the market - it can be as low as 1.2 m. A unit installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, resulting in unit capacity and efficiency reductions and possible excessive head pressures. When the unit is placed in an enclosure or small depression, the top of the fans should be no lower than the top of the enclosure or depression. If they are, consideration should be given to ducting the top of the unit. Ducting individual fans, however, is not recommended. Such applications should always be reviewed with the local Trane sales engineer. The recommended lateral clearances are given in the certified drawings for multiple chiller installation up to 3 units. For applications with more than 3 chillers, check with the local Trane sales engineer. CAUTION! Unit operation is function of the air temperature. Any recycling of the air fed out by the fans will increase the air intake temperature over the condenser fins and can result in high pressure cut-out. In this case the standard operating conditions and performance are modified. Operation of the unit may be affected by an increase in air temperature on the condenser. When the units are positioned in a windy area, avoid all the risks of aircooled recycling. Refer to certified drawings. Figure 3 - Lateral clearance recommendations 1.2 m CG-SVX07A-E4 13 Installation Lifting and Moving Instructions A specific lifting method is recommended as follows: 1. 4 lifting points are built into the unit. 2. Slings and spreader bar to be provided by rigger and attached to the lifting points. 3. Minimum rated lifting capacity (vertical) of each sling and spreader bar shall be no less than the tabulated unit shipping weight. CAUTION! 4. This unit must be lifted with the utmost care. Avoid shock load by lifting slowly and evenly. CAUTION! Refer to lifting and moving instructions for unit weight and additional installation instructions contained inside the control panel. Other lifting arrangements may cause equipment damage or serious personal injury. Figure 4 - Rigging and handling 2400 4000 A C B Pull-out hook Table 6 - Unit dimensions (maximum, mm) A B C Unit without hydraulic module Can be identified by the absence of any water pump 2423 2280 4849 Unit with hydraulic module Can be identified by the presence of a single or dual pump and the absence of the 600 litre water tank on the water side 2423 2250 4849 Unit with hydraulic module and buffer tank Can be identified by the presence of the 600 litre water tank on the water side. 2423 2250 4849 14 CG-SVX07A-E4 Installation Drainage Provide a large-capacity drain for water vessel drain-down during shutdown or repair. All local and national codes apply. Trane will not accept any ability in regards of damage due to the use of untreated or improperly treated water or from the use of saline or brackish water. If required, contact your local Trane sales office. The vent on the top of the water tube is provided to prevent a vacuum, by allowing air into the evaporator for complete drainage. Thoroughly flush all water piping to the unit before making the final piping connections to the unit. Water treatment If using an acidic commercial flushing solution, construct a temporary bypass around the unit to prevent damage to internal components of the evaporator. Untreated or insufficiently treated water, if used in this unit, may cause scale, slime or algae to accumulate or cause erosion and corrosion. As Trane does not know the components used in the hydraulic network and the quality of the water used, we recommend the services of a qualified water treatment specialist. The following materials are used in Trane chillers heat exchangers: • Stainless steel plates AISI 316, 1.4401 with copper brazing. • Water piping: steel • Water connections: brass CAUTION! To avoid possible equipment damage, do not use untreated or improperly treated system water. CAUTION! Trane assumes no responsibility for equipment failures which results from untreated or improperly treated water or saline or brackish water. Water connections Before making any water connection, make sure the labeling for entering and leaving water corresponds to the submittals. Figure 5 - Victaulic connections CG-SVX07A-E4 15 Installation CAUTION! CAUTION! The chilled-water connections to the evaporator are to be Victaulic type connections. Do not attempt to weld these connections, because the heat generated from welding can cause microscopic and macroscopic fractures on the unit piping. An optional Victaulic pipe stub and coupling is available for welding on flanges. A pipe strainer must be installed in the entering water line. Failure to do so can allow waterborne debris to enter the brazed plate evaporator. The strainer must be cleanable without dismounting and designed to filter particles bigger than 1.6 mm. Units with hydraulic module are already fitted with this type of strainer. To prevent damage to chilled-water components, do not allow evaporator pressure (maximum working pressure) to exceed 10.0 bar on units without hydraulic module and 4 bar on units with hydraulic module. CGAN units are available in 3 versions: • Without hydraulic module (with or without contactors) • With hydraulic module (single or dual pump) • With hydraulic module and buffer tank. Use rubber vibration eliminators to prevent vibration transmission through the water lines. If desired, install thermometers in the lines to monitor entering and leaving water temperatures. On all installation the following components will always be necessary to be mounted on the piping: Install a balancing valve in the leaving-water line to control water flow balance. Install shutoff valves on both the entering and leaving-water lines so that the evaporator or hydraulic module can be isolated for service. 16 CG-SVX07A-E4 Installation WARNING! Units with hydraulic module and buffer tank content all safety and operation devices and only require the supply and return piping to be connected using expansion compensators. Units without hydraulic module have to be connected according to Figure 6. Figure 6 - Hydraulic module schematics A = Circuit with hydraulic module B = Circuit without hydraulic module CW = Chilled water loop FT = Water flow switch TT = Temperature sensor Pi = Gauge 1 = Single or double water pump 2 = Water strainer 3 = Relief valve 4 = Expansion tank 6 = Manual air vent 7 = Manual water vent 8 = Automatic air vent 9 = Stop butterfly valve 10 = Insulated evaporator 12 = Optional buffer tank 13 = Antifreeze protection 14 = Schraeder ¼ SAE male CG-SVX07A-E4 17 Installation Figure 7 - Unit without hydraulic module and buffer tank - typical water circuit 10 Figure 8 - Unit with hydraulic module and buffer tank - typical water circuit 2 1 = Pressure gauges: show entering and leaving water pressure (2 pressure ports are available inside of the unit - see item 1 in Figure 7) 2 = Balancing valve: adjusts water flow. 3 = Air purge allows to remove the air from the water circuit during fill up. 4 = Stop valves: isolate chillers and water circuiting pump during maintenance operations. 5 = Thermometers: indicate chilled water entering and leaving temperatures (not mandatory). 6 = Expansion compensators: avoid mechanical stress between chiller and piping installation. 7 = Stop valve located on the outlet connection: used to measure the water pressure inlet or outlet of evaporator. 8 = Strainer: avoid to get heat exchangers dirty. All installation must be equipped with efficient strainer in order that only clean water enters into exchanger. If there is no strainer, reserve will be formulated by the Trane technician at the start-up of the unit. The strainer used must be able to stop all particles with a diameter greater than 1.6 mm. 9 = Draining and charging: used to drain and charge the plate heat exchanger. 10 = Charging valve To protect the environment, it is compulsory to recover and process glycol brines. 18 CG-SVX07A-E4 Installation Minimal installation water content The minimum volume can be determined by using the following formula: The water volume is an important parameter because it allows a stable chilled water temperature and avoids short cycle operation of the compressors. Volume = Cooling capacity x Time x highest capacity step (%) / Specific heat / Dead band Parameters which influence the water temperature stability • Water loop volume. • Load fluctuation. • Number of capacity steps. • Compressors rotation. • Dead band (adjusted by control CH530). • Minimum time between 2 starts of a compressor. Specific heat = 4.18 kJ / kg Minimum water volume for a comfort application Minimum operating time = 120 seconds Average Dead band = 3°C (or 2°C) Note: To estimate the biggest step, it is usually more reliable to make a selection at lower ambient temperature where efficiency is higher and compressors steps bigger. It is also essential to take into account the brine specific heat, in case of the use of glycol. For comfort application we can allow water temperature fluctuation at part load. The parameter to take into account is the minimum operating time of the compressor. In order to avoid lubrication problem on a scroll compressor it must run at least 2 minutes (120 seconds) before it stops. Table 7 - Minimum water loop for comfort applications This table is estimated with: Ambient 35°C, Water 12°/7°C, Water (0% glycol), deadband of 3°C Unit size Chiller data Minimum water loop CG-SVX07A-E4 CGAN 209 210 211 212 213 214 Capacity (kW) 288 316 350 389 428 462 Biggest step (%) 27 25 22 17 18 17 Comfort (l) 751 755 745 621 745 737 19 Installation Minimum water volume for a process application For process application we have to minimize the water temperature fluctuation at part load. In order to avoid problem on a scroll compressor it must run at least 2 minutes (120 seconds) before it stops and the minimum time between two starts is 5 minutes (300 seconds). The water volume has to be able to provide the cooling capacity while the unit is shut down. The minimum volume can be determined by using the following formula: Volume = Cooling capacity x Time x highest capacity step (%) / Specific heat / Dead band For the CGAN running in following conditions: Air temperature 35°C, water 12/7°C, this gives the following volumes. If the total water volume of the installation is below the above mentioned values it is necessary to use a buffer tank. Minimum time = 180 seconds (300120) Specific heat =4.18 kJ / kg Dead band = 2°C (request) With these values the formula becomes: Volume = Cooling capacity x 43 x highest capacity step (%) / Dead band Increasing the dead band is like adding water volume to the loop. With these values the formula becomes for water: Volume = Cooling capacity X 43 x highest capacity step (%)/ dead band 20 CG-SVX07A-E4 Installation Winter freeze protection During negative ambient air temperature chilled water piping must be fully insulated. Ensure that all safeties are taken to prevent frost damage during negative ambient air temperature. CAUTION! Table 8 - Freeze protection recommendations Freeze protection heater Type of pump control Without electrical heater digit 36=X With electrical heater digit 36=1 Following systems can be used: • Electrical heater mounted on all water piping exposed to negative temperatures. • Start chilled water pump during negative ambient air temperature. • Add ethylene glycol in the chilled water. • Drain water-circuit, however be aware of corrosion process when drained. Advice No pump controled digit 35=X No winter freeze protection. Electric heat function. For areas where ambient temperature might go below freezing temperatures use glycol or freeze protection devices. Remote pump control digit 35=A, B Pump winter freeze protection (not recommended). Electric heat function with pump winter freeze protection. It is recommended to deactivate the pump protection and use only heater protection. Pump installed in the unit digit 35=C to F Pump winter freeze protection. Electric heat function with pump winter freeze protection. It is recommended to use pump protection or even both modes together. When using the freeze protection by pump activation during the cold season, water must be able to circulate freely. Check that no closure valve or other device might block waterflow. °C Figure 9 - Freezing point versus ethylene glycol percentage % % = % ethylene glycol °C = Brine temperature 1 = Liquid 2 = Freezing without burst effect 3 = Freezing with burst effect CG-SVX07A-E4 21 Installation Expansion valves settings Electrical connections In order to keep the compressor in the operating envelope, it is mandatory to control the superheat suction at commissioning. It shall reduce the compressor discharge gas temp and increase the saturated suction temperature, increasing by the way the unit capacity. The rule to reduce the suction superheat is to loosen the expansion valve adjustment screw. One turn counterclockwise equals to -1°C to - 2°C superheat decrease. It is recommended to lower the superheat by increasing the suction pressure by making adjustments to the expansion valve setting prior to attempting to lower the LP setting parameter to avoid unit tripping on low pressure. Always make sure there is enough subcooling. This can be especially convenient for units with Ethylene Glycol and Propylene Glycol. CAUTION! 1. The greatest care should be taken when cutting through passages and installing electric wiring. Under no circumstances should chips of metal or cuttings of copper or isolating material fall into the starter panel or electric components. Relays, contactors, terminals and control wiring should be covered and protected before power supplies are connected. 2. Install power supply cabling as shown in wiring diagram. Adequate cable gland should be chosen, ensuring no foreign bodies enter the electrical housing or components. See "General start-up" section for recommended settings. CAUTION! 1. Cabling must comply with local standards. The type and location of fuses must also comply with standards. 2. Only copper wiring should be used. Using aluminium wires can produce galvanic corrosion and possibly lead to superheat and failure of connection points. Soft starter recommended setting Acceleration time: 0.5 seconds full speed Start-up torque: 50% Deceleration time: 0 seconds Use adjustment setting button. 22 CG-SVX07A-E4 Installation CG-SVX07A-E4 155mm L1 L2 L3 PE 65 65 Figure 10 - Main power supply connection 23 General start-up Start-up preparation Carry out all operations on check list so that the unit is correctly installed and ready to operate. The installer must check all the following points before calling in the Trane Servicing Department to put the equipment into service: • Check position of unit • Check unit is level • Check type and position of rubber pads • Check clearance required for maintenance access (Refer to certified drawings) • Check clearance around condenser (Refer to certified drawings) • Chilled water circuit ready to operate, filled with water, pressure test carried out and air purged. • Chilled water circuit must be rinsed • Check the presence of water strainer ahead of evaporator • The strainers must be cleaned after 2 hours of pumps operation • Check the thermometers and manometers position • Check chilled water pumps interconnection to control panel • Ensure that the isolation resistance of all power supply terminals to ground complies with standards and regulations in force. • Check that unit voltage and frequency supplied match rated input voltage and frequency • Check that all electrical connections are clean and sound • Check that main power supply switch is sound. • Check Ethylene glycol or Propylene glycol % in the chilled water circuit. • Water flow control checking: decrease the water flow and check the electrical contact in the control panel. • Check chilled water pressure drop through evaporator (unit without hydraulic module) or unit available pressure (unit with hydraulic module) are in accordance with the Trane order write-up (Figure 12). • On start-up of each motor in the system, check the direction of rotation and operation of all the components they drive. • Check that there is sufficient demand for cooling on the day of start-up (around 50% of nominal load) WARNING! For leak test, maximum pressure on HP and LP side is 21 bar. 24 CG-SVX07A-E4 General start-up Start-up Follow the instructions below to correctly start-up the unit. Installation and chiller inspection: • Ensure that all the operations above (start-up preparation), are followed. Follow the instruction stuck inside the electrical cabinet: • Ensure all water and refrigerant valves are in service positions, • Ensure that the unit is not damaged, • Ensure that sensors are properly installed in their bulb-wells and submerged in heat conducting product, • Check fixing of capillary tubes (protection from vibration and from wear) and ensure that they are not damaged, • Reset all manually set control devices, • Check refrigerating circuits tightness Checking and setting: Compressors: • Check oil level at rest. The level should reach at least halfway up indicator located on housing. See Figure 11 for correct level. Figure 11 - Compressor oil level • Check fixing of capillary tubes (protection from vibration and from wear) and ensure that they are not damaged, • Reset all manually set control devices, • Check refrigerating circuits tightness • Check electrical terminals tightening of the motors and in the control panel, • Check the isolation of the motors using a 500V DC megohmeter which meets manufacturer's specifications (alert value 2 megohms) • Check the direction of the rotation using phasemeter. Electrical power wiring: • Check all the electrical terminals tightening, • Set-up compressors overload relays, • Set-up fan-motors overload relays, Electrical control wiring: • Check all the electrical terminals tightening, • Check all the pressostats, • Check and set-up the TRACER CH530 control module • Test and start-up without the electrical power. Condenser: • Check direction of the rotation of fans, 1 = Maximum oil level 2 = Minimum oil level CG-SVX07A-E4 25 General start-up Operating parameters statement: • Check that the unit is clean and clear of any debris, tools, etc… • All valves are in operating position, • Switch on main power supply switch, • Start the water pump(s) and check there is no cavitation. • Start-up the unit following procedure described in the controller user guide The unit and the chilled water pumps contactor must be connected together, • After unit start up, leave in operation for at least 15 minutes, to ensure pressures are stabilized. 26 Then check: • voltage, • compressors and fan-motors currents, • leaving and return chilled water temperature, • suction temperature and pressure, • ambient air temperature, • blowing air temperature, • discharge pressure and temperature, • liquid refrigerant temperature and pressure, • operating parameters: • chilled water pressure drop through evaporator (if no hydraulic module is installed) or unit available pressure. It must be in accordance with Trane order write-up, • superheat: difference between suction temperature and dew point temperature. Normal superheat should be within 4 and 7 °C with R407C in cooling mode, • sub-cooling: difference between liquid temperature and bubble point temperature. Normal subcooling should be within 2 and 10°C with R407C in cooling mode, • difference between dew point temperature in high pressure and condenser air inlet temperature. Normal value on standard unit with R407C, should be 15 to 23°C. • difference between outlet water temperature and dew point temperature in low pressure. Normal value on standard unit, without Ethylene glycol in chilled water, should be about 3°C + superheat with R407C. Final check: When the unit is operating correctly • Close control and starter panel doors and check panels fixation. CAUTION! • For the warranty to apply, any start-up carried out directly by the customer must be recorded in a detailed report, which must be sent as soon as possible to the nearest Trane sales office. • Do not start-up a motor whose insulation resistance is less than 0.5 megohms • Phase imbalance should not be greater than 2%. • The voltage supplied to motors should be within 5% of the rated voltage on the compressor nameplate. • Excessive emulsion of the oil in the compressor shows that refrigerant is present in the oil and the result will be that compressor is not lubricated enough. Shut down compressor and wait for 60 minutes for the sump heaters to heat oil and start again. Should this not work, consult Trane technician. • Excess oil in compressor can damage the compressor. Before adding oil, consult Trane technician. Use only Trane products recommended. • The compressors must operate in a single direction of rotation. If refrigerant high pressure remains stable in the 30 seconds after compressor start-up, immediately shut down unit and check the direction of rotation using phasemeter. CG-SVX07A-E4 General start-up WARNING! • The chilled water circuit may be under pressure. Bring down this pressure before opening up the system to rise out or fill up the water circuit. Failure to comply with this instruction may cause accidental injury to maintenance personnel. • If a cleaning solution is used in the chilled water circuit, the chiller must be isolated from the water circuit to avoid all the damage risks of the chiller and evaporator water pipes. Figure 12 - Pressure drop without hydraulic module 50 20 5 CG-SVX07A-E4 10 20 50 27 General start-up Figure 13 - Chiller Available pressure (Hydraulic module standard head pump) 250 200 kPa 150 100 209 210 211 50 213 214 212 0 5 10 15 20 25 30 35 l/s Figure 14 - Chiller Available pressure (Hydraulic module low head pump) 180 211 160 140 120 kPa 100 80 60 40 210 20 209 0 5 10 15 20 212 25 213 214 30 l/s 28 CG-SVX07A-E4 General start-up The correction factor found in Table 9 and Table 10 may be used to calculate the actual general data of the unit. You may apply both of those factors (first Table 9 then Table 10) In case of application with negative temperature at the evaporator or usage of another type of fluid: please contact your local Trane sales engineer. A relief valve is located at pump suction limiting water circuit pressure at 4 bar. Nitrogen pressure inside of the expansion tank must be equal to the geometric height of the installation + 0.5 bar. In order to avoid air entering in the water circuit, expansion tank must be inflated with nitrogen. Pressure must be checked yearly. For a good pump operation, pump suction pressure must be between 0.5 and 3.5 bar when pump runs. This table is valid for evaporator leaving water temperature between +5°C and +15°C. Table 9 - Performance data adjustment altitude and delta T factors (1) Elevation Chilled Water Temp. Delta T Sea Level Cooling Power capacity input factor factor Flow rate factor Cooling capacity factor 600 m Power input factor Flow rate factor Cooling capacity factor 1200 m Power input factor Flow rate factor Cooling capacity factor 1800 m Power input factor Flow rate factor 4 °C 0.997 0.999 1.246 0.987 1.012 1.233 0.975 1.027 1.217 0.960 1.045 1.200 5 °C 1.000 1.000 1.000 0.989 1.013 0.989 0.977 1.028 0.977 0.963 1.047 0.963 6 °C 1.003 1.001 0.835 0.992 1.014 0.826 0.979 1.030 0.816 0.965 1.048 0.804 7 °C 1.004 1.002 0.717 0.993 1.016 0.710 0.981 1.031 0.701 0.966 1.049 0.690 8 °C 1.006 1.003 0.629 0.995 1.016 0.622 0.982 1.032 0.614 0.968 1.050 0.605 (1) with fouling factor of 0.044 m²/°C/kW Table 10 - Performance data adjustment with glycol Correction factors to apply in case of the use of Glycol in the water loops Glycol Concentration Fluid Type Water in Evaporator Ethylene Glycol Mono-Propylene Glycol (1) (2) Performance Evaporator Evaporator Cooling Capacity Factor Power input Factor Flow rate Factor (1) Pressure drop Factor (2) 0% 10% 20% 30% 10% 20% 30% 1.00 0.99 0.98 0.97 0.99 0.97 0.96 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.02 1.05 1.10 1.01 1.03 1.05 1.00 1.02 1.06 1.10 1.05 1.10 1.17 Flow rate with capacity modification Pressure drop to be used after flow rate factor rate CG-SVX07A-E4 29 Operation Control system The control is through the TRACER CH530 control module. Unit operation • Check the chilled water pump(s) operates • Start up the unit following procedure described in the controller user guide. The unit will operate correctly when there is sufficient water flow. The compressors will start up if the evaporator water leaving temperature is above the control module setpoint. 30 Weekly start-up • Check the chilled water pump(s) operates • Start up the unit following procedure described in the controller user guide. Weekend shutdown • If the unit needs to be shut down for a short period of time, stop the unit following procedure described in the controller user guide (See "Clock" menu) • If the unit is shut down for a longer period, see "Seasonal shutdown". • Ensure that all safeties are taken to prevent frost damages during negative ambient temperature. • Do not put the general disconnect switches to off, except if the unit is drained. Trane does not recommend draining the unit, due to the fact that it increases tube corrosion. CG-SVX07A-E4 Operation CG-SVX07A-E4 Seasonal shutdown Seasonal start-up • Check water flows and interlocks. • Check glycol % in the chilled water circuit if glycol presence is required • Carry out leak test. • Carry out oil analysis • Record operating pressures, temperatures, amperages and voltage. • Check operation of machines and compare conditions of operation against original commissioning data. • Stop the unit following procedure described in the controller user guide. • Ensure that all safeties are taken to prevent frost damages during negative ambient temperature. • Fill out the visit log sheet and review with the operator • Do not put the general disconnect switch to off, except if the unit is drained. Trane does not recommend draining the unit, due to the fact that it increases tube corrosion. • Check water flows and interlocks. • Check Ethylene glycol % in the chilled water circuit if glycol presence is required • Check operational set points and performance. • Check operation of all safety devices. • Inspect contacts and tighten terminals. • Megger the motor compressor windings. • Record operating pressures, temperatures, amperages and voltage. • Carry out leak test. • Check configuration of unit control module. • Change the oil as required based upon results of the oil analysis made during seasonal shutdown Get the 8 condition measurements at the same time, on each circuit. • HP • LP • Suction temperature • Discharge temperature • Liquid temperature • Water entering temperature • Water leaving temperature • Outdoor ambient temperature Then calculate the sub-cooling and superheat. No diagnosis can be accurate with one of these records missing. • Check operation of machines/compare conditions of operation against original commissioning data. • Fill out the visit log sheet and review with the operator 31 Maintenance The following maintenance instructions are part of maintenance operations required for this equipment. A qualified technician is needed for regular maintenance as part of a regular maintenance contract. Carry out all operations as required by schedule. This will ensure long unit service life and reduce the possibility of serious and costly breakdown. Keep service records up to date, showing monthly information on unit operations. These records can be of great help to maintenance personnel diagnostics. Similarly, if machine operator keeps a log of changes in unit operating conditions, problems can be identified and solutions found before more serious problems arise. 32 Inspection visit after the first 500 hours of operation from unit start up • Carry out oil analysis • Carry out leak test. • Inspect contacts and tighten terminals. • Record operating pressures, temperatures, amperages and voltage. • Check operation of machines/compare conditions of operation against original commissioning data. • Fill out inspection visit log sheet and review with the operator • Check and clean the strainer For medium to highly critical applications, a monthly preventive visit is recommended. Monthly preventive visit • Carry out leak test. • Oil test of acidity • Check Ethylene glycol % in the chilled water circuit if glycol presence is required • Inspect contacts and tighten terminals. • Record operating pressures, temperatures, amperages and voltage. • Check operation of machines/compare conditions of operation against original commissioning data. • Fill out visit log sheet and review with the operator. • Check and clean the strainer. CG-SVX07A-E4 Maintenance Annual preventive visit • Check and clean the strainer. • Check water flows and interlocks. • Check expansion tank pressure. • Check glycol % in the chilled water circuit if glycol presence is required • Check operational set points and performance. • Calibrate controls and pressure transducer. • Check operation of all safety devices. • Inspect contacts and tighten terminals. • Megger the motor compressor windings. • Record operating pressures, temperatures, amperages and voltage. • Carry out leak test. • Check configuration of unit control module. • Carry out oil analysis • Change the oil as required based upon results of the oil analysis • Check operation of machines and compare conditions of operation against original commissioning data. • Fill out the annual start up visit log sheet and review with the operator. CG-SVX07A-E4 CAUTION! • Please refer to specific Trane documentation on oil, available from your nearest Trane sales office. Oils recommended by Trane have been exhaustively tested in Trane laboratories to the specific requirement of Trane chiller and hence the user's requirements. Any use of oils not meeting specifications recommended by Trane is the responsibility of the user only, who thereby is liable to warranty loss. • Oil analysis and oil test acidity must be carried out by a qualified technician. Poor interpretation of results may cause unit operating problems. Also, oil analysis must follow the correct procedures, to avoid accidental injury to maintenance personnel. • If the condensers are dirty, clean them with a soft brush and water. If the coils are too dirty, consult a cleaning professional. Never use high pressure water to clean condenser coils. • Contact Trane Service for information on maintenance contracts. WARNING! • Switch off unit main power supply before any intervention. Failure to follow this safety instruction can lead to death or may also damage equipment. • Never use steam or hot water above 60°C to clean condenser coils. The resulting increasing pressure could cause refrigerant loss through the safety valve. Pump maintenance Pumps motor bearings and mechanical seals have a designed life expectancy of 20000-25000 hours of operation. For critical applications it might be necessary to change the components as a preventive measure. 33 Maintenance This list must be checked off by the installer to ensure correct installation before the unit start up. UNIT POSITION ! Check clearance around condenser ! Check clearance required for maintenance access ! Check type and position of rubbers pads ! Check unit is level CHILLED WATER CIRCUIT ! Check manometers presence and position ! Check water flow rate balancing valve presence and position ! Check presence of strainer ahead of evaporator ! Check presence of air-purge valve ! Check rinsing and filling of chilled water pipes ! Check water pump(s) contactor interconnected to control panel ! Check water flow ! Check chilled water pressure drop or unit available pressure (units with hydraulic module) ! Check for leaks in chilled water pipes ELECTRICAL EQUIPMENT ! Check installation and rating of mains power switch/fuses ! Check electrical connections complied with specification ! Check that electrical connections are in accordance with information on manufacturer's identification plate ! Check direction of rotation using phasemeter Comments .................................................................................................................................. .................................................................................................................................. .................................................................................................................................. .................................................................................................................................. .................................................................................................................................. Signature: ................................Name: .................................................................... Order N°:.................................................................................................................. Work site: ................................................................................................................. Please return to your local Trane Service Office 34 CG-SVX07A-E4 Maintenance Troubleshooting guide These are simple diagnostic hints. This is not a comprehensive analysis of the Scroll compressor refrigeration system. The aim is to give operators simple instructions on basic unit processes so that they have the technical knowledge to identify and bring defective operations to the notice of qualified technicians. If there is a breakdown, the Trane Service office should be contacted for confirmation and assistance. Problems symptoms Problem causes Action recommended Motor burned out. Replace compressor A) The compressor does not start up Compressor terminals are live but motor does not start Contactor motor not operational. Coil burned out or broken contacts. Repair or replace. No current ahead of motor contactor. a) Power cut. Check fuses and connection. b) Main power supply switched off. See why system tripped. If system is operational, switch on main power supply. Current ahead of fuse, but not on contactor side. Fuse blown. Check motor insulation. Replace fuse. Low voltage reading on voltameter. Voltage too low. Contact power Supply Utility. Starter coil not excited. Regulation circuit open. Locate regulation device which has tripped out and see why. See instructions concerning this device. Compressor does not run. Compressor sticking (damaged or sticking components). Replace compressor. Discharge pressure too high See instructions for "discharge pressure high". Compressor motor "groans". High pressure switch tripped to contacts open on high pressure. Discharge pressure too high. B) Compressor stops High pressure switch tripped. Discharge pressure too high. See instructions for "discharge pressure high". Over current thermal relay tripped. a) Voltage too low. a) Contact Power Supply Utility. b) Cooling demand too high, or condensing temperature too high. b) See instruction "discharge pressure too high". Motor temperature thermostat tripped. Not enough cooling fluid. Repair leak. Add refrigerant. Anti-freeze security tripped. Water flow to evaporator too low. Check water flow rate, and flow switch contact in water Filter drier clogged. Replace filter drier. Temperature too high in areas requiring airconditioning. Excess load on cooling system. Check thermal insulation and air-tightness of areas requiring air-conditioning. Chilled water temperature output too high. Excess cooling demand on system. Check thermal insulation and air-tightness of areas requiring air-conditioning. C) Compressor stops just after its start Suction pressure too low. Filter drier iced up. D) The compressor keeps running without stopping E) Loss of oil in compressor Oil level too low in indicator. Not enough oil. Contact Trane before ordering oil Gradual fall in oil level. Filter drier clogged. Replace filter drier. Suction line too cold. Liquid flows back to compressor. Adjust superheat and check bulb fixing of the expansion valve. CG-SVX07A-E4 35 Maintenance F) Compressor noisy Compressor knocks. Components broken in compressor. Change compressor. Suction duct abnormally cold. a) Uneven liquid flow. a) Check superheat setting and fixing of expansion valve bulb. b) Expansion valve locked in open position. b) Repair or replace. Not enough refrigerant. Check refrigerant circuit tightness and add refrigerant. G) Insufficient cooling capacity Thermostatic expansion valve "whistles". Excess pressure drops through filter drier Drier filter clogged. Replace. Excessive superheat. Superheat not properly adjusted. Check adjustment of superheat and adjust thermostatic expansion valve. Insufficient water flow. Chilled water pipes obstructed. Clean pipes and strainer. Condenser abnormally hot. Presence of uncondensable liquids in system, or excess refrigerant. Purge uncondensable fluids and drain off excess refrigerant. Chilled water leaving temperature too high. Overload on cooling system. H) Discharge pressure too high Reduce load on system. Reduce water flow if necessary. Condenser air output too hot. Reduced air flow. Air intake temperature higher than specified for unit Clean or replace air filters. Clean coil. Check operation of motor fans. Compressor operates continuously. Excess cooling demand on evaporator Check system. Suction duct abnormally cold. a) Expansion valve too far open. a) Check for superheat and check that expansion valve bulb is secure. Refrigerant flows back to compressor. b) Expansion valve locked in open position. b) Replace. Excessive pressure drop through filter drier. Filter drier clogged. Replace the filter drier. Refrigerant does not flow through thermostatic expansion valve. Expansion valve bulb has lost its refrigerant. Replace the bulb. Loss of power. Expansion valve obstructed. Replace. Superheat too low. Excessive pressure drops through evaporator. Check adjustment of superheat and adjust thermostatic expansion valve. Low water flow rate. Check water flow rate. Check state of strainer, check for obstruction in chilled water pipes. I) Suction pressure too high J) Suction pressure too low K) Insufficient cooling capacity Low pressure drops through evaporator 36 CG-SVX07A-E4 Notes CG-SVX07A-E4 37 Notes 38 CG-SVX07A-E4 Notes CG-SVX07A-E4 39 Literature Order Number CG-SVX07A-E4 Date 1005 New Literature Stocking Location Europe www.trane.com Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. Only qualified technicians should perform the installation and servicing of equipment referred to in this publication. For more information, contact your local sales office or e-mail us at [email protected] American Standard Europe BVBA Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium