Air-Cooled Liquid Chiller with integrated hydraulic module Cooling only: CGAN 200 - 250 - 300 400 - 450 - 490 - 500 - 600 - 700 - 800 900 - 925 Reversible: CXAN 200 - 250 - 300 400 - 450 - 490 - 500 - 600 - 700 800 - 900 - 925 CG-PRC010-E4 ©American Standard Inc. 2004 CG-PRC010-E4 Contents Features 4 General data 6 Application considerations 15 Cooling performance - Standard version 17 Cooling performance - Super Quiet version 29 Heating performance - Standard version and CG-PRC010-E4 Super Quiet version 41 Water side performance 44 3 Features • Available in several configurations: - Standard or Super quiet - With or without hydraulic module - Hydraulic module with or without buffer tank • 1 refrigerant circuit (sizes 200 to 490), 2 circuits (sizes 500 to 900) • R407C operating charge • Scroll compressors • Stainless steel brazed plate heat exchanger • Aluminium fin coil with copper tubes • Filter drier • Thermostatic expansion valves • High and low pressure cut-outs • 4-way valve (CXAN) • Liquid receiver (CXAN) • Low noise fans • Disconnect switch • Water flow switch • Winter-freeze protection through pump activation if pump is controlled by unit • Draining valve • Frame in galvanized steel coated with powder polyester resin paint (RAL 9002) • Threaded ISO R7 connection Control • Microprocessor control module with Control of leaving water temperature. • Control steps: - 2 steps for single circuit - 4 steps for double circuits • Liquid crystal display indicating: - leaving water temperature. - main operating parameters - codes of any faults - unit status • Control of operating parameters. • Cold or hot water reset • On/off Programming • Anti-freeze protection of evaporator. • Control of defrosting (CXAN). • Dry contacts for remote signal of on/off and general fault. • Inputs for external water setpoint reset, auxiliary setpoint, remote On/Off and Cooling/heating switch 4 Options Hydraulic 5 versions available • No hydraulic control • With single pump contactors to control a remote pump • With double pump contactors to control 2 remote double pumps • With single pump integrated hydraulic module • With double pump hydraulic module Hydraulic module • Single or double pump • Balancing valve • Expansion vessel • Pressure relief valve set to 3.5 bar • Water strainer • Shut-off valve • Drainage valve • Pressure ports for gauge connection • Water pressure gauge • Thermally insulated evaporator and liquid line to reduce water condensing or freezing • Condensate collection and drainage (below pump) • Pump winter freeze protection down to -18°C (the pump is activated under an ambient temperature setting) Buffer tank (only available with hydraulic module) As a unique design the water tank is located below the chiller which allow to keep the same footprint and increase the height of the unit of only 400 mm. The tank is fully insulated and is engineered for a continuous flow. Sizes 200 and 250 370 l. Sizes 300 to 490 410 l. Sizes 500 to 925 570 l. The purpose of such device is to increase the circuit inertia when necessary, for example with short water loops. A high circuit inertia reduces the compressors cycling to increase the compressors life span and also smoothes the water temperature for comfort or demanding processes. CG-PRC010-E4 Features Condenser Fan control for low ambient operation in cooling mode: 1 speed fan (+10°C) 2 speeds fans (-10°C) Inverter fans (-18°C) Super quiet version, Unit with compressor sound insulated casing (-5dB(A) average) High External Static Pressure fans (not available in super quiet) 80 Pa for sizes 200, 250, 300, 500, 600, 700 60 Pa for sizes 400, 450, 490, 800, 900, 925 Condenser fins • Aluminum fins and copper tubes (standard) • Copper fins • Aluminum fins with black epoxy fin protection • Coil protection grille (not suitable for container shipment) Electrical • Phase reversal protection • Soft starter to reduce starting current (sizes 200 250 300 only not available with inverter fans) • Antifreeze protection to protect the evaporator, hydraulic module and buffer tank down to -10°C For futher detail, refer to the official documentation LonWorks® FTT-10A free topology transeiver user’s guide and to the official LonWorks® guidelines LonMark® layer 1-6 interoperability guidelines version 3.0. These documents and additional information are available on the internet site www.lonmark.org The serial link uses the chiller controller profile reference 8040. The following orders can be sent to the chiller(s) : • Modify the chilled or hot water temperature setpoint • Start or stop the unit • Switch from cooling to heating mode on heat pump The following information can be read : • Leaving chilled or hot water temperature setpoint • Water temperature at the inlet and outlet of the evaporator • Ambient air temperature • Chiller in operation • Alarm description: Manual or auto reset fault Ckt1 or ckt2 fan fault Pump1 or pump 2 fault Compressor A1 or B1 or A2 or B2 fault Other HP and LP pressure gauges, pressure measurement can also be done through the controller (pressure transducers) Any other request please contact your local Trane Sales office LonTalk® option Description The Lon interface uses an Echelon FTT-10 transceiver, which is approved to be used on the TP/FT-10 channel. This channel is characterized by the following main features: • It consists of up to 64 nodes on a single network segment • Data rate: 78 125 kbps • Maximum distance: 1400 meters CG-PRC010-E4 5 General data Table 1 - CGAN cooling only - Standard version - R407C Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop Pressure available (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per foot Fan Type Number Diameter Drive type Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) 6 (kW) (kW) (kPa) (kPa) CGAN 200 CGAN 250 CGAN 300 CGAN 400 CGAN 450 CGAN 490 50.7 19.1 29 195 62.5 24.4 33 180 76.2 28.8 38 173 102.8 38.7 46 139 121.8 43.6 43 195 132.3 50.5 44 181 89 236 10 95 50 102 327 10 95 50 111 336 10 95 50 2 2 (20T+25T) 38+47 272 2900 0.87 150 (25T+25T) 47+47 272 2900 0.87 150 1 1 11.3 115 12.6 115 2½” 2½” 2896 1626 4.71 3 180 2896 1626 4.71 4 168 2896 1626 4.71 4 168 3 800 3 800 3 800 400/3/50 (A) (A) (kA) (mm2) (mm2) 47 148 10 16 10 57 203 10 35 16 69 215 10 35 16 2 2 2 (10T+10T) 19+19 120 2900 0.84 100 (10T+15T) 19+28.5 175 2900 0.85 160 1 1 5.3 115 6.8 115 2” 2” (fpf) 2489 1422 3.54 2 204 2489 1422 3.54 3 180 2896 1422 4.12 3 180 (mm) 2 710 2 710 3 710 (kW) (A) (rpm) 20200 2 0.6 1.5 700 19100 2 0.6 1.5 700 26300 3 0.6 1.5 700 Direct drive 37300 3 1.05 2.4 680 37100 3 1.05 2.4 680 37100 3 1.05 2.4 680 (mm) (mm) (mm) (kg) (kg) 1897 2800 1100 748 743 1897 2800 1100 842 834 1897 3200 1100 968 954 2074 3200 1100 1143 1124 2074 3200 1100 1267 1260 2074 3200 1100 1292 1284 (%) 1 2 50 1 2 40/60 1 2 50 1 2 37/63 1 2 37/63 1 2 37/63 (kg) (kg) 13 - 18 - 21 - 24 - 28 - 28 - (A) (A) (rpm) (W) (L) (W) 3 Scroll (15T+15T) (15T+15T+10T) 28.5+28.5 28.5+28.5+19 175 175 2900 2900 0.85 0.85 160 160 1 1 Brazed plate 8.2 10.5 115 115 Male ISO R7 2½” 2½” Slit Fin (mm) (mm) (m2) Propeller (m3/h) at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 General data Table 1 cont Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop Pressure available (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per foot Fan Type Number Diameter Drive type Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) (kW) (kW) (kPa) (kPa) CGAN 500 CGAN 600 CGAN 700 CGAN 800 CGAN 900 CGAN 925 128.9 49.1 30 206 157.1 57.9 36 185 182.8 68.4 30 196 214.2 77.9 35 174 241.3 88.3 35 137 267.0 102.4 41 124 188 334 10 150 95 208 354 10 150 95 225 450 10 150 95 400/3/50 (A) (A) (kA) (mm2) (mm2) 113 259 10 95 50 136 282 10 95 50 153 300 10 150 95 4 4 6 (10T+15T) 2x(19+28.5) 175 2900 0.85 160 (15T+15T) 2x(28.5+28.5) 175 2900 0.85 160 1 1 17.2 180 19.8 180 2 ½” 2 ½” 1 Brazed plate 25.6 29.0 180 180 Male ISO R7 3” 3” (fpf) 2489 1422 3.54 3 180 2896 1422 4.12 3 180 2896 1626 4.71 3 180 (mm) 4 710 6 710 6 710 (kW) (A) (rpm) 38300 4 0.57 1.5 700 52700 6 0.57 1.5 700 55400 6 0.57 1.5 700 (mm) (mm) (mm) (kg) (kg) 1897 3400 2300 1623 1588 1897 3400 2300 1818 1778 (%) 2 4 20/30 (kg) (kg) 19 19 (A) (A) (rpm) (W) (L) (W) 6 6 Scroll (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 175 175 175 2900 2900 2900 0.85 0.85 0.85 160 160 160 1 4 (25T+25T) 2x(47+47) 272 2900 0.87 150 1 1 35.7 180 35.7 180 3” 3” 2896 1626 4.71 3 180 2896 1626 4.71 4 180 2896 1626 4.71 4 168 6 800 6 800 6 800 Direct drive 86300 6 1.4 4 680 83000 6 1.4 4 680 79300 6 1.4 4 680 2100 3400 2300 2087 2030 2100 3400 2300 2245 2181 2100 3400 2300 2423 2344 2100 3400 2300 2456 2377 2 4 25 2 4 22/29 2 4 19/32 2 4 17/33 2 4 17/33 22 22 27 27 27 27 34 34 31 31 Slit Fin (mm) (mm) (m2) Propeller (m3/h) at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 7 General data Table 2 CGAN cooling only - Super Quiet version - R407C Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop Pressure available (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (2)(4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per foot Fan Type Number Diameter Drive type Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) 8 (kW) (kW) (kPa) (kPa) CGAN 200 CGAN 250 CGAN 300 CGAN 400 CGAN 450 CGAN 490 50.5 18.8 29 195 62.2 24.2 32 180 75.7 28.4 37 174 101.9 36.4 45 141 121.8 43.6 43 195 132.3 50.5 44 181 90 236 10 95 50 102 327 10 95 50 111 336 10 95 50 2 2 (20T+25T) 38+47 272 2900 0.87 150 (25T+25T) 47+47 272 2900 0.87 150 1 1 11.3 115 12.6 115 2 ½” 2 ½” 2896 1626 4.71 3 180 2896 1626 4.71 4 168 2896 1626 4.71 4 168 3 800 3 800 3 800 400/3/50 (A) (A) (kA) (mm2) (mm2) 46 147 10 16 10 55 202 10 35 16 66 213 10 35 16 2 2 2 (10T+10T) 19+19 120 2900 0.84 100 (10T+15T) 19+28.5 175 2900 0.85 160 1 1 5.3 115 6.8 115 2” 2” (fpf) 2489 1422 3.54 2 204 2489 1422 3.54 3 180 2896 1422 4.12 3 180 (mm) 2 710 2 710 3 710 (kW) (A) (rpm) 20200 2 0.57 1.5 700 19100 2 0.57 1.5 700 26300 3 0.57 1.5 700 Direct drive 37300 3 1.05 2.4 680 37100 3 1.05 2.4 680 37100 3 1.05 2.4 680 (mm) (mm) (mm) (kg) (kg) 1897 2800 1100 778 773 1897 2800 1100 872 864 1897 3200 1100 1010 996 2048 3200 1100 1155 1136 2048 3200 1100 1279 1272 2048 3200 1100 1304 1296 (%) 1 2 50 1 2 40/60 1 2 50 1 2 37/63 1 2 37/63 1 2 37/63 (kg) (kg) 13 - 18 - 21 - 24 - 28 - 28 - (A) (A) (rpm) (W) (L) (W) 3 Scroll (15T+15T) (15T+15T+10T) 28.5+28.5 28.5+28.5+19 175 175 2900 2900 0.85 0.85 160 160 1 1 Brazed plate 8.2 10.5 115 115 Male ISO R7 2 ½” 2 ½” Slit Fin (mm) (mm) (m2) Propeller (m3/h) at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 General data Table 2 cont Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop Pressure available (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (2)(4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per foot Fan Type Number Diameter Drive type Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) (kW) (kW) (kPa) (kPa) CGAN 500 CGAN 600 CGAN 700 CGAN 800 CGAN 900 CGAN 925 128.1 48.8 29 207 156.1 57.2 36 186 181.5 68.0 29 197 212.1 73.4 34 176 238.0 85.0 34 139 264.9 102.1 40 126 178 324 10 150 95 200 344 10 150 95 216 441 10 150 95 400/3/50 (A) (A) (kA) (mm2) (mm2) 110 256 10 95 50 131 278 10 95 50 150 295 10 150 95 4 4 6 (10T+15T) 2x(19+28.5) 175 2900 0.85 160 (15T+15T) 2x(28.5+28.5) 175 2900 0.85 160 1 1 17.2 180 19.8 180 2 ½” 2 ½” 1 Brazed plate 25.6 29.0 180 180 Male ISO R7 3” 3” (fpf) 2489 1422 3.54 3 180 2896 1422 4.12 3 180 2896 1626 4.71 3 180 (mm) 4 710 6 710 6 710 (kW) (A) (rpm) 38300 4 0.57 1.5 700 52700 6 0.57 1.5 700 55400 6 0.57 1.5 700 (mm) (mm) (mm) (kg) (kg) 1897 3400 2300 1685 1650 1897 3400 2300 1900 1860 (%) 2 4 20/30 (kg) (kg) 19 19 (A) (A) (rpm) (W) (L) (W) 6 6 Scroll (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 175 175 175 2900 2900 2900 0.85 0.85 0.85 160 160 160 1 4 (25T+25T) 2x(47+47) 272 2900 0.87 150 1 1 35.7 180 35.7 180 3” 3” 2896 1626 4.71 3 180 2896 1626 4.71 4 180 2896 1626 4.71 4 168 6 800 6 800 6 800 Direct drive 74700 6 1.05 2.4 680 71400 6 1.05 2.4 680 74300 6 1.05 2.4 680 2100 3400 2300 2171 2114 2074 3400 2300 2335 2271 2074 3400 2300 2513 2434 2074 3400 2300 2546 2467 2 4 25 2 4 22/29 2 4 19/32 2 4 17/33 2 4 17/33 22 22 27 27 27 27 34 34 31 31 Slit Fin (mm) (mm) (m2) Propeller (m3/h) at Eurovent Conditions (Evap 12°C/7°C - Air. 35°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 9 General data Table 3 - CXAN reversible - Standard version - R407C Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop in cooling Pressure available in cooling (5) Net Heating Capacity Power input in heating Pressure drop in heating Pressure available in heating (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (2)(4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per inch Fan Type Number Diameter Drive type Number of speeds Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) 10 (kW) (kW) (kPa) (kPa) (kW) (kW) (kPa) (kPa) CXAN 200 CXAN 250 CXAN 300 CXAN 400 CXAN 450 CXAN 490 49.2 20.3 28 198 48.1 20.3 26 200 60.8 25.4 31 183 59.6 24.9 30 185 73.6 30.1 35 177 72.7 30.4 35 179 94.5 40.0 39 156 99.2 43.0 43 146 116.4 42.8 40 201 112.3 45.7 37 205 124.8 49.7 39 190 120.3 48.7 36 195 89 236 10 95 50 89 236 10 95 50 89 236 10 95 50 3 3 (15T+15T+10T) 28.5+28.5+18.6 176 2900 0.87 50 (15T+15T+10T) 28.5+28.5+18.7 177 2900 0.87 50 1 1 10.5 115 10.5 115 2 ½” 2 ½” 2896 1626 4.71 3 204 2896 1626 4.71 4 168 2896 1626 4.71 4 168 3 800 3 800 3 800 37100 3 1.05 2.4 680 37300 3 1.05 2.4 680 400/3/50 (A) (A) (kA) (mm2) (mm2) 47 148 10 16 10 57 203 10 35 16 69 215 10 35 16 2 2 2 (10T+10T) 19+19 120 2900 0.84 100 (10T+15T) 19+28.5 175 2900 0.85 160 1 1 5.3 115 6.8 115 2” 2” (fpf) 2489 1422 3.54 2 204 2489 1422 3.54 3 204 2896 1422 4.12 3 204 (mm) 2 710 2 710 3 710 (A) (A) (rpm) (W) (L) (W) 3 Scroll (15T+15T) (15T+15T+10T) 28.5+28.5 28.5+28.5+18.5 175 175 2900 2900 0.85 0.85 160 50 1 1 Brazed plate 8.2 10.5 115 115 Male ISO R7 2 ½” 2 ½” Plate Fin (mm) (mm) (m2) Propeller (kW) (A) (rpm) 20200 2 0.57 1.5 700 19100 2 0.57 1.5 700 Direct drive 1 26300 37300 3 3 0.57 1.05 1.5 2.4 700 680 (mm) (mm) (mm) (kg) (kg) 1897 2800 1100 776 771 1897 2800 1100 870 862 1897 3200 1100 996 982 2048 3200 1100 1182 1163 2048 3200 1100 1302 1295 2048 3200 1100 1331 1323 (%) 1 2 50 1 2 40/60 1 2 50 1 2 37/63 1 2 37/64 1 2 37/65 (kg) (kg) 13 - 18 - 21 - 24 - 40 - 40 - (m3/h) at Eurovent Conditions (Cooling :Water 12°C/7°C - Air. 35°C // Heating :Water 40°C/45°C - Air. DB7°C / WB6°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 General data Table 3 cont Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop in cooling Pressure available in cooling (5) Net Heating Capacity Power input in heating Pressure drop in heating Pressure available in heating (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (2)(4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per inch Fan Type Number Diameter Drive type Number of speeds Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) (kW) (kW) (kPa) (kPa) (kW) (kW) (kPa) (kPa) CXAN 500 CXAN 600 CXAN 700 CXAN 800 CXAN 900 CXAN 925 125.9 51.1 28 209 119.2 49.5 25 214 153.1 60.7 35 189 145.3 60.4 31 197 167.4 69.8 25 208 171.8 69.6 26 205 195.1 78.2 29 191 198.4 84.5 30 188 220.7 90.1 29 148 220.0 92.6 29 149 251.9 102.0 36 134 251.6 101.1 36 134 188 334 10 150 95 208 354 10 150 95 225 450 10 150 95 400/3/50 (A) (A) (kA) (mm2) (mm2) 113 259 10 95 50 136 282 10 95 50 153 300 10 150 95 4 4 6 (10T+15T) 2x(19+28.5) 175 2900 0.85 160 (15T+15T) 2x(28.5+28.5) 175 2900 0.85 160 1 1 17.2 180 19.8 180 2½” 2½” 1 Brazed plate 25.6 29.0 180 180 Male ISO R7 3" 3" (fpf) 2489 1422 3.54 3 204 2896 1422 4.12 3 204 2896 1626 4.71 3 204 (mm) 4 710 6 710 6 710 (A) (A) (rpm) (W) (L) (W) 6 6 Scroll (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 175 175 175 2900 2900 2900 0.85 0.85 0.85 160 160 160 1 4 (25T+25T) 2x(47+47) 272 2900 0.87 150 1 1 35.7 180 35.7 180 3" 3" 2896 1626 4.71 3 204 2896 1626 4.71 4 180 2896 1626 4.71 4 168 6 800 6 800 6 800 83000 6 1.4 4 680 79300 6 1.4 4 680 Plate Fin (mm) (mm) (m2) Propeller (kW) (A) (rpm) 38300 4 0.57 1.5 700 52700 6 0.57 1.5 700 Direct drive 1 55400 86300 6 6 0.57 1.4 1.5 4 700 680 (mm) (mm) (mm) (kg) (kg) 1897 3400 2300 1677 1642 1897 3400 2300 1872 1832 2100 3400 2300 2166 2109 2100 3400 2300 2324 2260 2100 3400 2300 2502 2423 2100 3400 2300 2535 2456 (%) 2 4 20/30 2 4 25 2 4 22/29 2 4 19/32 2 4 17/33 2 4 17/33 (kg) (kg) 21 21 24 24 29 29 30 30 37 37 41 41 (m3/h) at Eurovent Conditions (Cooling :Water 12°C/7°C - Air. 35°C // Heating :Water 40°C/45°C - Air. DB7°C / WB6°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 11 General data Table 4 - CXAN reversible - Super Quiet version - R407C Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop in cooling Pressure available in cooling (5) Net Heating Capacity Power input in heating Pressure drop in heating Pressure available in heating (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (2)(4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per inch Fan Type Number Diameter Drive type Number of speeds Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) 12 (kW) (kW) (kPa) (kPa) (kW) (kW) (kPa) (kPa) CXAN 200 CXAN 250 CXAN 300 CXAN 400 CXAN 450 CXAN 490 49.1 19.9 27 198 48.1 19.6 26 200 60.4 25.2 31 183 59.6 24.2 30 185 73.1 29.8 35 178 72.7 29.3 35 179 93.6 37.6 38 158 99.2 39.8 43 146 116.4 42.8 40 201 112.3 45.7 37 205 124.8 49.7 39 190 120.3 48.7 36 195 90 236 10 95 50 102 327 10 95 50 111 336 10 95 50 2 2 (20T+25T) 38+47 272 2900 0.87 150 (25T+25T) 47+47 272 2900 0.87 150 1 1 11.3 115 12.6 115 2 ½” 2 ½”" 2896 1626 4.71 3 204 2896 1626 4.71 4 168 2896 1626 4.71 4 168 3 800 3 800 3 800 37100 3 1.05 2.4 680 37100 3 1.05 2.4 680 400/3/50 (A) (A) (kA) (mm2) (mm2) 46 147 10 16 10 55 202 10 35 16 66 213 10 35 16 2 2 2 (10T+10T) 19+19 120 2900 0.84 100 (10T+15T) 19+28.5 175 2900 0.85 160 1 1 5.3 115 6.8 115 2” 2” (fpf) 2489 1422 3.54 2 204 2489 1422 3.54 3 204 2896 1422 4.12 3 204 (mm) 2 710 2 710 3 710 (A) (A) (rpm) (W) (L) (W) 3 Scroll (15T+15T) (15T+15T+10T) 28.5+28.5 28.5+28.5+19 175 175 2900 2900 0.85 0.85 160 160 1 1 Brazed plate 8.2 10.5 115 115 Male ISO R7 2 ½” 2 ½” Plate Fin (mm) (mm) (m2) Propeller (kW) (A) (rpm) 20200 2 0.57 1.5 700 19100 2 0.57 1.5 700 Direct drive 1 26300 37300 3 3 0.57 1.05 1.5 2.4 700 680 (mm) (mm) (mm) (kg) (kg) 1897 2800 1100 806 801 1897 2800 1100 900 892 1897 3200 1100 1038 1024 2048 3200 1100 1194 1175 2048 3200 1100 1314 1307 2048 3200 1100 1343 1335 (%) 1 2 50 1 2 40/60 1 2 50 1 2 37/63 1 2 37/63 1 2 37/63 (kg) (kg) 13 - 18 - 21 - 24 - 40 - 40 - (m3/h) at Eurovent Conditions (Cooling :Water 12°C/7°C - Air. 35°C // Heating :Water 40°C/45°C - Air. DB7°C / WB6°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 General data Table 4 cont Eurovent Performances (1) Net Cooling Capacity Total Power input in cooling Water pressure drop in cooling Pressure available in cooling (5) Net Heating Capacity Power input in heating Pressure drop in heating Pressure available in heating (5) Main Power supply Units Amps Nominal (4) Start-up Amps Short circuit unit capacity Max supply cable size Min supply cable size Compressor Number Type Model Rated Amps (2)(4) Locked rotor Amps (2) Motor RPM Power factor Sump Heater (2) Evaporator Number Type Water volume (total) Antifreeze Heater Unit Water Connections Water Connections Diameter Coil Type Length Height Face Area (3) Rows Fins per inch Fan Type Number Diameter Drive type Number of speeds Air flow Number of motors Motor HP (2) Rated Amps (2) Motor RPM Dimensions Height (6) Length Width Operating Weight Shipping Weight System Data Number of refrigerant circuits Capacity steps Minimum capacity Refrigerant Charge (3) Circuit A Circuit B (1) (2) (3) (4) (5) (6) (kW) (kW) (kPa) (kPa) (kW) (kW) (kPa) (kPa) CXAN 500 CXAN 600 CXAN 700 CXAN 800 CXAN 900 CXAN 925 125.5 50.9 28 209 119.2 48.5 25 214 152.5 60.3 34 190 145.3 59.0 31 197 166.8 69.6 25 209 171.8 68.2 26 205 194.1 75.9 29 192 198.4 79.5 30 188 219.2 88.3 29 149 220.0 87.6 29 149 250.0 101.5 36 135 251.6 97.4 36 134 178 324 10 150 95 200 344 10 150 95 216 441 10 150 95 400/3/50 (A) (A) (kA) (mm2) (mm2) 110 256 10 95 50 131 278 10 95 50 150 295 10 150 95 4 4 6 (10T+15T) 2x(19+28.5) 175 2900 0.85 160 (15T+15T) 2x(28.5+28.5) 175 2900 0.85 160 1 1 17.2 180 19.8 180 2 ½” 2 ½” 1 Brazed plate 25.6 29.0 180 180 Male ISO R7 3” 3” (fpf) 2489 1422 3.54 3 204 2896 1422 4.12 3 204 2896 1626 4.71 3 204 (mm) 4 710 6 710 6 710 (A) (A) (rpm) (W) (L) (W) 6 6 Scroll (10T+10T+15T) (15T+15T+10T) (15T+15T+15T) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 175 175 175 2900 2900 2900 0.85 0.85 0.85 160 160 160 1 4 (25T+25T) 2x(47+47) 272 2900 0.87 150 1 1 35.7 180 35.7 180 3” 3" 2896 1626 4.71 3 204 2896 1626 4.71 4 180 2896 1626 4.71 4 168 6 800 6 800 6 800 71400 6 1.05 2.4 680 74300 6 1.05 2.4 680 Plate Fin (mm) (mm) (m2) Propeller (kW) (A) (rpm) 38300 4 0.57 1.5 700 52700 6 0.57 1.5 700 Direct drive 1 55400 74700 6 6 0.57 1.05 1.5 2.4 700 680 (mm) (mm) (mm) (kg) (kg) 1897 3400 2300 1739 1704 1897 3400 2300 1954 1914 2100 3400 2300 2250 2193 2074 3400 2300 2414 2350 2074 3400 2300 2592 2513 2074 3400 2300 2625 2546 (%) 2 4 20/30 2 4 25 2 4 22/29 2 4 19/32 2 4 17/33 2 4 17/33 (kg) (kg) 21 21 24 24 29 29 30 30 37 37 41 41 (m3/h) at Eurovent Conditions (Cooling :Water 12°C/7°C - Air. 35°C // Heating :Water 40°C/45°C - Air. DB7°C / WB6°C) per motor per circuit Max rated conditions. Dual Pump Option For units with HESP option, contact your local sales office CG-PRC010-E4 13 General data Table 5 - Hydraulic module and buffer tank Motor (2) Rated Amps (2) Motor RPM Water strainer Ø Expansion tank volume User volume expansion capacity (1) Antifreeze heater Piping Hydraulic Module Weight Water tank volume (Option) Water tank additionnal shipping height Water tank additionnal shipping weight CGAN CXAN 200 2.2 4.9 CGAN CXAN 250 2.2 4.9 CGAN CXAN 300 2.2 4.9 CGAN CXAN 400 2.2 4.9 CGAN CXAN 450 4.0 7.5 2” 25 2” 25 2 ½” 25 2 ½” 25 2 ½” 25 (L) (W) 1000 1000 1000 1000 1000 (kg) (L) 103 370 103 370 108 410 108 410 108 410 (kW) (A) (rpm) (L) CGAN CGAN CXAN CXAN 490 500 2.2 4.0 7.5 7.5 2900 2 ½” 2 ½” 25 35 1000 1400 150 Steel 108 110 410 570 (mm) (kg) CGAN CXAN 600 4.0 7.5 CGAN CXAN 700 4.0 7.5 CGAN CXAN 800 4.0 7.5 CGAN CXAN 900 5.5 11.1 CGAN CXAN 925 5.5 11.1 2 ½” 35 3” 35 3” 35 3” 35 3” 35 1400 1400 1400 1400 1400 110 570 114 570 114 570 189 570 189 570 644 644 644 644 644 400 396 396 437 436 436 436 644 (1) Hydrostatic pressure 3 bar at 45°C with -12°C mini (2) Dual Pump Option 14 CG-PRC010-E4 Application considerations Optimum performance of CGAN and CXAN units will be achieved only if proper application guidelines are followed. Where the application varies from the guidelines presented, it should be reviewed with your local Trane sales engineer. Unit sizing Unit capacities are listed in the “Performance Data” section. Intentionally oversizing a unit to assure adequate capacity is not recommended. Erratic system operation and excessive compressor cycling are often a direct result of an oversized unit. In addition, an oversized unit is usually more expensive to purchase, install and operate. If oversizing is desired, consider using two units. Water drainage Insure there is adequate drainage to drain away water from the unit in the event of shutdown or repair. Vertical clearance Vertical condenser air discharge must be unobstructed. While it is difficult to predict the degree of warm air recirculation, a unit installed as shown in Figure 1 would have its capacity and efficiency significantly reduced possibly to the degree of nuisance high head pressure tripouts. Performance data is based on free air discharge. Figure 1 Unit placement Foundation A base or foundation is not required if the selected unit location is level and strong enough to support the unit operating weight. Isolation and sound emission Structurally transmitted sound is reduced by using rubber pads isolators provided as standard. They have to be installed between the unit and the ground. 4 or 6 rubber pads are provided to avoid contact between the unit and the ground. Sound emission or structural vibration can be reduced by using other rubber pad isolators between the unit and the ground. An acoustical engineer should always be consulted on critical applications. Table 6 - Standard Operating Limits CGAN - CXAN Cooling Low ambient operating Min. outdoor air temperature Max. outdoor air temperature Min. leaving water temperature Max. leaving water temperature CXAN Heating Standard +10°C +42°C 2 Speed Fan -10°C +42°C Speed inverter -18°C +42°C -10°C (1) +20°C -12°C +12°C -12°C +12°C -12°C +12°C +25°C +50°C (2) (1) For a maximum of 35°C leaving water (2) For a minimum of 0°C outdoor air temperature CG-PRC010-E4 15 Application considerations Lateral clearance The condenser coil inlet must not be obstructed. A unit installed closer than the minimum recommended distance to a wall or other vertical riser may experience a combination of coil starvation and warm air recirculation, resulting in unit capacity and efficiency reductions and possible excessive head pressures. The recommended lateral clearances are given in the certified drawings for multiple chiller installation up to 3 units. For more than 3 chillers applications, check with the local Trane sales engineer. Walled enclosure installations When the unit is placed in an enclosure or small depression, the top of the fans should be no lower than the top of the enclosure or depression. If they are, consideration should be given to ducting the top of the unit. Ducting individual fans, however, is not recommended. Such applications should always be reviewed with the local Trane sales engineer. Parameters which influence the water temperature stability - Number of capacity step. - Minimum time between two starts of a compressor. - Water loop volume. - Load fluctuations. Minimum water volume for a comfort application For comfort application we can allow water temperature fluctuation at part load. The parameter to take into account is the minimum operating time of the compressor. In order to avoid lubrication problem on a scroll compressor it must run at least 2 minutes (120 seconds) before it stops. It is important to check that the total water loop volume is at least equal to the value indicated in Table 7. For specific applications or for additional information, refer to the chiller IOM or contact your local sales office. Minimal installation water content The water volume is an important parameter because it allows a stable chilled water temperature and avoids short cycle operation of the compressors. Table 7 - Minimum water loop volume for comfort application CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CGAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN CXAN 200 250 300 400 450 490 500 600 700 800 900 925 Water volume (l) 250 360 360 610 640 620 370 370 500 650 760 630 At Eurovent conditions 16 CG-PRC010-E4 CG-PRC010-E4 Table 8 - Cooling capacities CGAN 200 Standard version Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 27.4 32.6 38.3 44.4 51.0 52.9 54.6 56.3 58.0 59.7 61.4 63.1 64.8 25 P.I. (kW) 11.9 12.2 12.6 13.0 13.5 13.6 13.7 13.8 14.0 14.1 14.2 14.3 14.5 °C HP (bar) 13.4 13.8 14.4 14.9 15.6 15.8 16.0 16.2 16.3 16.5 16.7 16.9 17.0 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.1 5.2 Cap (kW) 26.1 31.0 36.4 42.3 48.6 50.4 52.0 53.6 55.2 56.8 58.5 60.1 61.7 30 P.I. (kW) 13.3 13.7 14.1 14.6 15.1 15.2 15.3 15.5 15.6 15.7 15.9 16.0 16.2 °C HP (bar) 15.3 15.8 16.4 17.0 17.7 17.9 18.1 18.3 18.5 18.6 18.8 19.0 19.2 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 5.2 Cap (kW) 24.6 29.2 34.3 39.9 45.9 47.7 49.2 50.7 52.2 53.8 55.3 56.9 58.5 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 15.0 17.5 1.9 23.0 16.9 20.0 15.4 18.0 2.4 27.3 17.4 20.5 15.9 18.6 2.9 32.1 17.9 21.1 16.4 19.3 3.4 37.4 18.5 21.8 16.9 20.0 4.0 43.1 19.1 22.5 17.1 20.2 4.2 44.7 19.3 22.7 17.2 20.4 4.3 46.1 19.4 22.9 17.4 20.6 4.5 47.6 19.6 23.1 17.5 20.7 4.6 49.0 19.7 23.3 17.7 20.9 4.8 50.5 19.9 23.5 17.8 21.1 5.0 52.0 20.0 23.7 18.0 21.3 5.1 53.5 20.2 23.9 18.1 21.5 5.3 54.9 20.4 24.1 Cap (kW) 30.8 36.5 42.8 49.6 56.8 58.9 60.7 62.5 64.4 66.2 68.0 69.9 71.7 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 18.9 17.7 1.9 19.6 18.3 2.4 34.1 22.1 20.9 20.3 19.0 2.9 40.1 22.9 21.6 21.0 19.7 3.4 46.5 23.7 22.3 21.9 20.5 4.0 53.3 24.6 23.2 22.1 20.8 4.2 55.2 24.9 23.4 22.3 21.0 4.3 56.9 25.1 23.6 22.5 21.2 4.5 58.6 25.3 23.9 22.7 21.4 4.6 60.3 25.5 24.1 23.0 21.6 4.8 62.1 25.8 24.3 23.2 21.8 4.9 63.8 26.0 24.6 23.4 22.1 5.1 65.5 26.3 24.8 23.6 22.3 5.3 67.3 26.5 25.0 LP (bar) 2.0 2.4 2.9 3.5 4.0 4.2 4.4 4.5 4.7 4.8 5.0 5.2 5.3 Cap (kW) 45 °C P.I. HP (kW) (bar) 29.7 34.7 40.0 41.5 42.9 44.3 20.3 20.9 21.5 21.7 21.9 22.0 LP (bar) Cap (kW) 45 °C P.I. HP (kW) (bar) 37.2 43.1 25.8 26.7 23.8 24.5 25.3 25.5 25.7 25.9 LP (bar) 2.9 3.5 4.1 4.3 4.4 4.6 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 29.2 34.1 39.4 33.5 20.8 21.4 22.1 21.9 Table 9 - Cooling capacities CGAN 250 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 34.3 40.7 47.7 55.2 63.2 65.5 67.5 69.6 71.6 73.6 75.7 77.7 79.8 25 P.I. (kW) 15.1 15.6 16.1 16.7 17.4 17.6 17.7 17.9 18.1 18.3 18.5 18.6 18.8 °C HP (bar) 13.5 14.0 14.6 15.2 15.9 16.2 16.3 16.5 16.7 16.9 17.1 17.3 17.5 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 32.6 38.6 45.3 52.5 60.2 62.3 64.2 66.2 68.1 70.0 72.0 73.9 75.9 30 P.I. (kW) 16.8 17.4 18.0 18.7 19.5 19.7 19.9 20.1 20.3 20.5 20.7 20.9 21.1 °C HP (bar) 15.5 16.0 16.7 17.4 18.1 18.4 18.6 18.7 18.9 19.1 19.4 19.6 19.8 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.2 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° 2.4 2.9 3.4 4.0 4.2 4.4 4.5 4.7 4.8 5.0 5.1 5.3 24.4 25.2 LP (bar) 2.9 3.5 46 °C Cap P.I. (kW) (kW) 42.4 27.3 47 °C Cap P.I. (kW) (kW) Cooling performance - Standard version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% 17 18 Table 10 - Cooling capacities CGAN 300 Standard version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 41.4 49.1 57.6 66.7 76.6 79.4 81.8 84.3 86.8 89.3 91.8 94.3 96.8 25 P.I. (kW) 17.9 18.4 19.1 19.7 20.5 20.7 20.9 21.1 21.3 21.5 21.7 21.9 22.1 °C HP (bar) 13.2 13.7 14.2 14.8 15.4 15.6 15.8 16.0 16.2 16.3 16.5 16.7 16.9 LP (bar) 1.9 2.3 2.8 3.4 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.1 Cap (kW) 39.3 46.7 54.8 63.6 73.0 75.7 78.0 80.4 82.7 85.1 87.5 89.9 92.3 30 P.I. (kW) 19.9 20.5 21.2 22.0 22.8 23.1 23.3 23.5 23.7 23.9 24.2 24.4 24.6 °C HP (bar) 15.2 15.7 16.2 16.9 17.5 17.7 17.9 18.1 18.3 18.5 18.7 18.8 19.0 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 22.3 17.4 1.9 35.0 25.1 19.8 23.0 17.9 2.4 41.5 25.8 20.3 23.8 18.5 2.9 48.8 26.7 21.0 24.6 19.1 3.4 56.7 27.6 21.6 25.5 19.9 4.0 65.1 28.6 22.4 25.8 20.1 4.1 67.5 28.8 22.6 26.0 20.2 4.3 69.6 29.1 22.8 26.2 20.4 4.4 71.7 29.3 23.0 26.5 20.6 4.6 73.8 29.6 23.2 26.7 20.8 4.7 76.0 29.9 23.4 27.0 21.0 4.9 78.1 30.1 23.6 27.2 21.2 5.0 80.2 30.4 23.8 27.5 21.4 5.2 82.4 30.6 24.0 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 5.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 45.5 52.9 60.7 63.0 64.9 66.9 30.0 30.9 32.0 32.3 32.5 32.8 Outdoor Ambient Temperature 35 °C 40 °C LP Cap P.I. HP LP Cap P.I. HP (bar) (kW) (kW) (bar) (bar) (kW) (kW) (bar) 1.9 49.9 29.7 17.3 1.9 46.9 33.4 19.8 2.4 59.3 30.6 17.8 2.4 55.7 34.4 20.3 2.9 69.6 31.6 18.4 2.9 65.4 35.5 20.9 3.4 80.7 32.6 19.1 3.4 75.9 36.6 21.5 4.0 92.6 33.8 19.8 4.0 87.1 37.8 22.3 4.1 96.0 34.1 20.0 4.1 90.3 38.2 22.5 4.3 98.9 34.4 20.1 4.3 93.1 38.5 22.7 4.4 101.9 34.7 20.3 4.4 95.8 38.8 22.8 4.6 104.8 35.0 20.5 4.6 98.6 39.1 23.0 4.7 107.8 35.3 20.7 4.7 101.4 39.5 23.2 4.8 110.7 35.6 20.9 4.9 104.2 39.8 23.4 5.0 113.6 35.9 21.1 5.0 107.0 40.1 23.6 5.1 116.6 36.2 21.2 5.2 109.7 40.4 23.8 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 5.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 60.9 70.8 81.3 84.2 86.8 89.4 92.0 39.9 41.1 42.4 42.8 43.1 43.5 43.8 LP (bar) 1.9 2.4 2.8 3.4 3.9 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 37.2 44.2 51.9 60.2 69.2 71.7 73.9 76.2 78.4 80.7 83.0 85.2 87.5 23.7 24.4 25.2 25.4 25.6 25.8 LP (bar) 2.9 3.4 4.0 4.2 4.3 4.5 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 44.9 52.1 59.8 62.0 44.2 51.3 30.7 31.6 32.7 33.0 31.4 32.4 Table 11 - Cooling capacities CGAN 400 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 55.6 65.9 77.3 89.5 102.6 106.3 109.5 112.7 116.0 119.3 122.5 125.8 129.0 25 P.I. (kW) 23.8 24.5 25.3 26.2 27.2 27.4 27.7 27.9 28.2 28.4 28.7 28.9 29.2 °C HP (bar) 13.2 13.7 14.2 14.8 15.4 15.6 15.8 15.9 16.1 16.3 16.5 16.6 16.8 30 LP Cap P.I. (bar) (kW) (kW) 1.9 52.8 26.5 2.4 62.7 27.3 2.9 73.5 28.2 3.4 85.3 29.2 3.9 97.7 30.2 4.1 101.3 30.5 4.2 104.4 30.8 4.4 107.5 31.1 4.5 110.6 31.3 4.7 113.7 31.6 4.8 116.8 31.9 5.0 119.9 32.2 5.1 123.0 32.4 °C HP (bar) 15.2 15.7 16.2 16.8 17.5 17.7 17.8 18.0 18.2 18.4 18.6 18.7 18.9 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° 23.6 24.3 25.0 25.3 25.4 25.6 25.8 LP (bar) 2.9 3.5 4.0 4.2 4.3 4.5 4.6 46 °C Cap P.I. (kW) (kW) 60.0 69.7 80.0 82.9 40.8 42.1 43.4 43.8 47 °C Cap P.I. (kW) (kW) 68.6 43.1 CG-PRC010-E4 Cooling performance - Standard version R407C % Ethylen % Glycol CG-PRC010-E4 Table 12 - Cooling capacities CGAN 450 Standard version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 61.2 72.4 88.0 105.4 123.2 128.0 132.1 136.3 140.4 144.6 148.8 153.0 157.3 25 P.I. (kW) 26.1 26.9 28.0 29.4 30.8 31.3 31.6 32.0 32.4 32.8 33.2 33.7 34.1 °C HP (bar) 14.0 14.4 15.0 15.7 16.5 16.7 16.9 17.1 17.3 17.5 17.7 17.9 18.1 LP (bar) 2.9 3.3 3.9 4.6 5.4 5.6 5.7 5.9 6.1 6.3 6.5 6.7 6.8 Cap (kW) 58.1 68.4 82.9 99.6 116.7 121.3 125.2 129.2 133.2 137.2 141.3 145.3 149.4 30 P.I. (kW) 29.1 29.9 31.2 32.7 34.4 34.9 35.3 35.7 36.2 36.6 37.1 37.5 38.0 °C HP (bar) 15.9 16.4 17.0 17.8 18.6 18.8 19.0 19.2 19.4 19.6 19.9 20.1 20.3 LP (bar) 2.9 3.3 3.9 4.6 5.4 5.6 5.8 5.9 6.1 6.3 6.5 6.7 6.9 Cap (kW) 54.8 64.2 77.6 93.3 109.7 114.2 118.0 121.8 125.6 129.5 133.4 137.3 141.3 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 32.8 18.1 2.9 33.7 18.6 3.3 59.8 38.1 21.0 35.0 19.2 3.9 72.0 39.5 21.7 36.6 20.0 4.6 86.8 41.2 22.5 38.5 20.9 5.4 102.4 43.1 23.4 39.0 21.1 5.6 106.7 43.6 23.7 39.4 21.4 5.8 110.4 44.1 23.9 39.9 21.6 5.9 114.0 44.5 24.1 40.4 21.8 6.1 117.7 45.0 24.4 40.8 22.0 6.3 121.4 45.5 24.6 41.3 22.2 6.5 125.2 46.0 24.9 41.8 22.5 6.7 128.9 46.5 25.1 42.3 22.7 6.9 132.8 47.0 25.4 Cap (kW) 60.2 70.5 84.9 101.8 119.4 124.2 128.2 132.3 136.4 140.5 144.7 148.9 153.1 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 38.7 17.5 1.9 39.9 18.0 2.3 65.4 45.3 20.5 41.7 18.8 2.9 78.6 47.0 21.3 43.8 19.7 3.6 94.4 49.0 22.2 46.0 20.6 4.4 111.2 51.3 23.2 46.6 20.9 4.6 115.9 51.9 23.5 47.2 21.1 4.8 119.7 52.4 23.7 47.7 21.3 4.9 123.6 53.0 24.0 48.3 21.6 5.1 127.6 53.5 24.2 48.8 21.8 5.3 131.6 54.1 24.5 49.4 22.1 5.5 135.6 54.6 24.8 50.0 22.3 5.7 139.6 55.2 25.0 50.5 22.6 5.9 143.7 55.7 25.3 LP (bar) 3.3 3.9 4.6 5.4 5.6 5.8 6.0 6.1 6.3 6.5 6.7 6.9 Cap (kW) 45 °C P.I. HP (kW) (bar) 66.1 79.8 44.6 46.3 Cap (kW) 45 °C P.I. HP (kW) (bar) 86.5 54.9 24.4 25.3 LP (bar) 3.9 4.6 46 °C Cap P.I. (kW) (kW) 78.4 47 °C Cap P.I. (kW) (kW) 47.4 Table 13 - Cooling capacities CGAN 490 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 67.1 79.3 96.2 115.2 134.4 139.6 144.0 148.4 152.9 157.3 161.8 166.4 170.9 25 P.I. (kW) 30.7 31.8 33.4 35.2 37.1 37.7 38.1 38.6 39.1 39.6 40.2 40.7 41.2 °C HP (bar) 13.3 13.8 14.4 15.2 16.1 16.3 16.5 16.7 16.9 17.2 17.4 17.6 17.8 LP (bar) 1.9 2.3 2.9 3.6 4.4 4.6 4.7 4.9 5.1 5.3 5.5 5.7 5.8 Cap (kW) 63.9 75.1 90.8 108.7 127.1 132.1 136.3 140.6 144.8 149.1 153.5 157.8 162.2 30 P.I. (kW) 34.3 35.5 37.2 39.1 41.3 41.9 42.4 42.9 43.5 44.0 44.6 45.1 45.7 °C HP (bar) 15.3 15.8 16.5 17.3 18.3 18.5 18.7 18.9 19.2 19.4 19.6 19.9 20.1 LP (bar) 1.9 2.3 2.9 3.6 4.4 4.6 4.7 4.9 5.1 5.3 5.5 5.7 5.9 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.3 2.9 3.6 4.4 4.6 4.8 5.0 5.1 5.3 5.5 5.7 5.9 25.0 LP (bar) 3.6 46 °C Cap P.I. (kW) (kW) 84.9 56.2 47 °C Cap P.I. (kW) (kW) Cooling performance - Standard version R407C % Ethylen Glycol 19 20 Table 14 - Cooling capacities CGAN 500 Standard version Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 70.5 83.5 97.9 113.4 130.2 135.0 139.3 143.6 147.9 152.3 156.7 161.2 165.6 25 P.I. (kW) 30.2 31.3 32.4 33.7 35.1 35.5 35.8 36.2 36.6 37.0 37.4 37.8 38.2 °C HP (bar) 13.5 14.1 14.7 15.3 16.1 16.3 16.5 16.7 16.9 17.1 17.4 17.6 17.8 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.7 4.9 5.1 5.3 5.4 Cap (kW) 66.9 79.3 93.0 107.8 123.8 128.4 132.4 136.5 140.6 144.8 149.0 153.2 157.5 30 P.I. (kW) 33.8 35.0 36.3 37.7 39.3 39.7 40.1 40.5 41.0 41.4 41.9 42.3 42.8 °C HP (bar) 15.6 16.1 16.8 17.5 18.3 18.5 18.7 19.0 19.2 19.4 19.6 19.9 20.1 LP (bar) 2.0 2.4 3.0 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.3 5.5 Cap (kW) 63.0 74.8 87.7 101.8 116.9 121.3 125.1 128.9 132.8 136.8 140.7 144.7 148.8 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 38.0 17.8 2.0 39.3 18.4 2.5 70.0 44.4 21.0 40.8 19.1 3.0 82.1 46.0 21.7 42.3 19.9 3.5 95.3 47.7 22.5 44.1 20.7 4.1 109.5 49.6 23.4 44.6 21.0 4.3 113.6 50.1 23.6 45.0 21.2 4.5 117.2 50.6 23.9 45.5 21.4 4.6 120.8 51.1 24.1 46.0 21.6 4.8 124.5 51.6 24.3 46.5 21.9 5.0 128.2 52.1 24.6 46.9 22.1 5.1 131.9 52.6 24.8 47.4 22.4 5.3 135.7 53.1 25.1 47.9 22.6 5.5 139.4 53.7 25.4 Cap (kW) 76.3 90.6 106.4 123.7 142.3 147.6 152.3 157.1 161.9 166.8 171.7 176.6 181.6 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 44.8 17.4 2.0 71.7 50.4 19.9 46.2 18.0 2.4 85.1 51.9 20.4 47.8 18.6 2.9 100.1 53.6 21.1 49.5 19.3 3.5 116.3 55.5 21.8 51.4 20.0 4.1 133.8 57.6 22.6 52.0 20.2 4.3 138.9 58.1 22.8 52.5 20.4 4.4 143.3 58.7 23.0 53.0 20.6 4.6 147.8 59.2 23.2 53.5 20.8 4.8 152.3 59.8 23.4 54.0 21.1 4.9 156.9 60.3 23.6 54.5 21.3 5.1 161.5 60.9 23.9 55.1 21.5 5.3 166.2 61.4 24.1 55.6 21.7 5.4 170.9 62.0 24.3 LP (bar) 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 Cap (kW) 45 °C P.I. HP (kW) (bar) 76.1 88.4 51.9 53.7 Cap (kW) 45 °C P.I. HP (kW) (bar) 79.4 93.3 108.4 124.8 129.5 133.6 58.4 60.2 62.2 64.4 65.0 65.6 24.5 25.4 LP (bar) 3.0 3.6 46 °C Cap P.I. (kW) (kW) 86.9 47 °C Cap P.I. (kW) (kW) 55.0 Table 15 - Cooling capacities CGAN 600 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 85.0 100.7 118.1 137.0 157.6 163.5 168.7 173.9 179.2 184.6 190.0 195.5 201.1 25 P.I. (kW) 35.9 37.1 38.3 39.8 41.3 41.8 42.2 42.6 43.1 43.5 44.0 44.4 44.9 °C HP (bar) 13.3 13.8 14.3 14.9 15.6 15.8 16.0 16.2 16.4 16.5 16.7 16.9 17.2 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 Cap (kW) 80.7 95.8 112.4 130.6 150.2 155.8 160.8 165.8 170.9 176.0 181.2 186.4 191.7 30 P.I. (kW) 40.0 41.3 42.7 44.3 46.0 46.5 47.0 47.5 47.9 48.4 48.9 49.4 49.9 °C HP (bar) 15.3 15.8 16.3 17.0 17.7 17.9 18.1 18.3 18.5 18.7 18.9 19.1 19.3 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.2 4.4 4.6 4.7 4.9 5.1 5.2 5.4 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.0 2.4 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 23.2 23.8 24.5 25.3 25.6 25.8 LP (bar) 2.5 3.0 3.5 4.1 4.3 4.5 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 91.9 106.8 122.9 90.5 105.1 61.6 63.6 65.8 63.1 65.1 CG-PRC010-E4 Cooling performance - Standard version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% CG-PRC010-E4 Table 16 - Cooling capacities CGAN 700 Standard version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 99.4 117.9 138.4 160.6 184.6 191.5 197.5 203.7 209.9 216.2 222.5 228.9 235.4 25 P.I. (kW) 42.3 43.7 45.2 47.0 48.9 49.5 50.0 50.5 51.0 51.6 52.1 52.7 53.3 °C HP (bar) 13.5 14.1 14.7 15.3 16.1 16.3 16.5 16.7 16.9 17.2 17.4 17.6 17.8 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 Cap (kW) 94.3 111.9 131.4 152.6 175.4 182.0 187.7 193.6 199.5 205.5 211.5 217.6 223.8 30 P.I. (kW) 47.2 48.8 50.6 52.5 54.7 55.3 55.9 56.5 57.1 57.7 58.3 58.9 59.6 °C HP (bar) 15.5 16.1 16.7 17.4 18.3 18.5 18.7 18.9 19.1 19.4 19.6 19.8 20.1 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 Cap (kW) 88.9 105.5 124.0 144.0 165.6 171.8 177.3 182.8 188.4 194.1 199.8 205.5 211.3 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 53.1 17.8 2.0 83.1 60.0 20.3 54.9 18.4 2.5 98.6 62.0 20.9 56.8 19.0 3.0 115.9 64.1 21.6 59.0 19.8 3.5 134.8 66.5 22.4 61.4 20.6 4.2 155.1 69.0 23.3 62.1 20.9 4.3 160.9 69.8 23.5 62.7 21.1 4.5 166.0 70.5 23.7 63.3 21.3 4.7 171.2 71.1 24.0 64.0 21.6 4.8 176.5 71.8 24.2 64.6 21.8 5.0 181.8 72.5 24.5 65.3 22.0 5.2 187.2 73.2 24.7 66.0 22.3 5.4 192.6 74.0 25.0 66.7 22.5 5.5 198.0 74.7 25.2 45 LP Cap P.I. (bar) (kW) (kW) 2.0 2.5 3.0 107.3 72.4 3.6 124.9 74.9 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 5.6 Cap (kW) 102.7 122.2 144.0 167.7 193.5 200.9 207.5 214.2 220.9 227.8 234.7 241.7 248.7 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 58.9 17.2 2.0 96.4 66.2 19.5 60.5 17.6 2.5 114.8 68.0 20.0 62.4 18.2 3.0 135.3 69.9 20.6 64.3 18.7 3.5 157.8 72.1 21.2 66.5 19.4 4.1 182.2 74.4 21.9 67.2 19.6 4.3 189.2 75.1 22.1 67.7 19.8 4.5 195.4 75.7 22.3 68.3 20.0 4.6 201.7 76.3 22.4 68.9 20.2 4.8 208.1 77.0 22.6 69.5 20.4 5.0 214.6 77.6 22.8 70.1 20.5 5.1 221.2 78.2 23.0 70.8 20.7 5.3 227.8 78.9 23.2 71.4 20.9 5.5 234.4 79.6 23.4 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.3 5.5 °C HP (bar) LP (bar) 24.4 25.2 3.0 3.6 46 °C Cap P.I. (kW) (kW) 105.5 122.8 47 °C Cap P.I. (kW) (kW) 74.1 76.7 Table 17 - Cooling capacities CGAN 800 Standard version % Ethylen Glycol Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 114.4 135.9 159.7 185.7 214.1 222.2 229.4 236.7 244.2 251.7 259.3 266.9 274.7 25 P.I. (kW) 47.3 48.7 50.2 51.9 53.7 54.2 54.7 55.2 55.7 56.2 56.8 57.3 57.8 °C HP (bar) 13.1 13.5 14.0 14.6 15.2 15.4 15.6 15.7 15.9 16.1 16.3 16.4 16.6 LP (bar) 2.0 2.4 3.0 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.3 5.4 Cap (kW) 108.7 129.2 152.1 177.0 204.1 211.9 218.8 225.8 232.9 240.1 247.4 254.7 262.1 30 P.I. (kW) 52.6 54.1 55.8 57.6 59.6 60.2 60.8 61.3 61.8 62.4 63.0 63.5 64.1 °C HP (bar) 15.0 15.5 16.0 16.6 17.2 17.4 17.6 17.7 17.9 18.1 18.3 18.5 18.7 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 4.9 5.1 5.3 5.5 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° Cap (kW) 45 °C P.I. HP (kW) (bar) 126.1 147.2 170.1 176.7 182.5 188.4 194.5 200.6 206.7 212.9 78.6 80.8 83.3 84.0 84.7 85.3 86.0 86.6 87.3 88.0 23.2 23.9 24.6 24.8 25.0 25.1 25.3 25.5 25.7 25.9 LP (bar) 3.0 3.6 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 124.2 145.0 167.6 174.0 179.8 185.7 191.6 122.3 142.7 165.0 171.4 80.4 82.7 85.2 85.9 86.6 87.2 87.9 82.3 84.6 87.2 87.9 Cooling performance - Standard version R407C % Ethylen Glycol 21 22 Table 18 - Cooling capacities CGAN 900 Standard version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 130.0 154.2 181.1 210.4 242.1 251.1 259.2 267.3 275.6 283.9 292.4 300.9 309.5 25 P.I. (kW) 53.7 55.4 57.3 59.3 61.6 62.3 62.9 63.5 64.2 64.8 65.5 66.1 66.8 °C HP (bar) 13.2 13.7 14.2 14.8 15.5 15.7 15.9 16.0 16.2 16.4 16.6 16.8 17.0 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 Cap (kW) 123.3 146.6 172.3 200.3 230.6 239.3 247.0 254.7 262.6 270.6 278.6 286.8 295.0 30 P.I. (kW) 59.7 61.6 63.7 66.0 68.6 69.3 70.0 70.7 71.4 72.1 72.8 73.5 74.2 °C HP (bar) 15.2 15.7 16.2 16.9 17.6 17.8 17.9 18.1 18.3 18.5 18.7 18.9 19.1 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.3 5.5 Cap (kW) 116.5 138.6 163.1 189.7 218.4 226.6 233.9 241.3 248.8 256.3 264.0 271.7 279.5 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 66.9 17.3 2.0 109.4 75.2 19.8 69.0 17.9 2.5 130.2 77.4 20.3 71.3 18.4 3.0 153.2 79.9 20.9 73.8 19.1 3.6 178.3 82.7 21.6 76.6 19.8 4.2 205.4 85.6 22.4 77.4 20.1 4.4 213.1 86.5 22.6 78.1 20.2 4.5 220.0 87.3 22.8 78.8 20.4 4.7 227.0 88.0 23.0 79.6 20.6 4.9 234.0 88.8 23.2 80.3 20.9 5.0 241.2 89.6 23.4 81.1 21.1 5.2 248.4 90.5 23.6 81.9 21.3 5.4 255.6 91.3 23.8 82.7 21.5 5.5 263.0 92.1 24.1 Cap (kW) 130.7 154.8 181.4 210.4 241.9 250.8 258.9 267.1 275.4 283.8 292.4 301.1 309.9 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 78.9 17.5 2.1 81.6 18.0 2.6 143.4 92.1 20.5 84.7 18.6 3.2 168.4 95.2 21.1 88.1 19.4 3.8 195.7 98.6 21.9 92.0 20.2 4.5 225.5 102.5 22.7 93.1 20.4 4.7 233.9 103.6 23.0 94.2 20.6 4.9 241.6 104.6 23.2 95.2 20.8 5.1 249.5 105.6 23.4 96.3 21.0 5.2 257.4 106.7 23.6 97.4 21.2 5.4 265.5 107.7 23.9 98.5 21.5 5.6 273.6 108.8 24.1 99.6 21.7 5.8 282.0 109.9 24.4 100.8 22.0 6.1 290.4 111.0 24.6 LP (bar) 2.0 2.5 3.0 3.6 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 5.6 Cap (kW) 45 °C P.I. HP (kW) (bar) 121.3 142.8 166.2 191.5 198.7 205.1 211.7 218.3 87.0 89.7 92.6 95.8 96.7 97.5 98.3 99.1 Cap (kW) 45 °C P.I. HP (kW) (bar) 180.1 208.3 216.3 223.6 110.4 114.1 115.1 116.0 23.0 23.6 24.3 25.1 25.3 25.5 25.8 26.0 LP (bar) 2.5 3.0 3.6 4.2 4.4 4.6 4.7 4.9 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 140.6 163.7 188.6 195.7 138.4 161.1 91.8 94.7 97.9 98.8 93.9 96.9 Table 19 - Cooling capacities CGAN 925 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 147.6 174.7 204.6 237.1 272.2 282.1 291.0 300.1 309.3 318.6 328.0 337.6 347.2 25 P.I. (kW) 63.0 65.4 68.0 70.9 74.3 75.3 76.2 77.2 78.2 79.2 80.2 81.3 82.4 °C HP (bar) 13.3 13.8 14.3 15.0 15.7 15.9 16.1 16.3 16.5 16.7 16.9 17.1 17.3 LP (bar) 2.1 2.6 3.2 3.8 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 6.0 Cap (kW) 139.6 165.2 193.5 224.2 257.4 266.8 275.3 283.9 292.7 301.5 310.5 319.6 328.8 30 P.I. (kW) 70.1 72.7 75.6 78.9 82.6 83.7 84.7 85.7 86.8 87.8 88.9 90.1 91.2 °C HP (bar) 15.3 15.8 16.4 17.1 17.8 18.0 18.2 18.5 18.7 18.9 19.1 19.3 19.5 LP (bar) 2.1 2.6 3.2 3.8 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 6.0 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.6 3.2 3.8 4.5 4.7 4.9 5.1 5.3 5.5 5.7 5.9 6.1 24.6 25.5 25.8 26.0 LP (bar) 3.8 4.5 4.7 4.9 46 °C Cap P.I. (kW) (kW) 176.9 112.9 47 °C Cap P.I. (kW) (kW) CG-PRC010-E4 Cooling performance - Standard version R407C % Ethylen Glycol CG-PRC010-E4 Table 20 - Cooling capacities CXAN 200 Standard version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 26.9 31.9 37.4 43.4 49.8 51.6 53.2 54.8 56.5 58.1 59.8 61.4 63.1 25 P.I. (kW) 12.3 12.8 13.3 13.8 14.5 14.6 14.8 15.0 15.1 15.3 15.5 15.7 15.8 °C HP (bar) 14.0 14.6 15.3 16.0 16.9 17.1 17.4 17.6 17.8 18.1 18.3 18.5 18.8 LP (bar) 1.9 2.3 2.8 3.4 3.9 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 25.6 30.3 35.5 41.2 47.3 49.1 50.6 52.1 53.7 55.3 56.8 58.4 60.0 30 P.I. (kW) 13.7 14.2 14.8 15.4 16.1 16.3 16.4 16.6 16.8 17.0 17.2 17.4 17.5 °C HP (bar) 15.9 16.5 17.3 18.1 18.9 19.2 19.4 19.7 19.9 20.1 20.4 20.6 20.9 LP (bar) 1.9 2.4 2.8 3.4 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 24.1 28.5 33.5 38.9 44.7 46.3 47.8 49.2 50.7 52.2 53.7 55.2 56.7 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 15.4 18.1 1.9 16.0 18.7 2.4 26.6 18.0 21.2 16.6 19.5 2.9 31.3 18.7 22.0 17.2 20.3 3.4 36.3 19.4 22.8 18.0 21.2 4.0 41.8 20.1 23.7 18.2 21.5 4.2 43.4 20.4 24.0 18.4 21.7 4.3 44.7 20.6 24.2 18.6 21.9 4.5 46.1 20.8 24.4 18.7 22.2 4.6 47.5 21.0 24.7 18.9 22.4 4.8 48.9 21.2 24.9 19.1 22.7 4.9 50.4 21.4 25.2 19.3 22.9 5.1 51.8 21.6 25.5 19.5 23.2 5.2 53.2 21.8 25.7 Cap (kW) 30.0 35.6 41.6 48.2 55.3 57.2 59.0 60.8 62.5 64.3 66.1 67.8 69.6 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 19.3 18.1 1.9 20.0 18.8 2.3 33.3 22.5 21.3 20.8 19.6 2.8 39.0 23.4 22.1 21.7 20.4 3.4 45.1 24.4 23.0 22.7 21.4 3.9 51.7 25.4 24.0 23.0 21.6 4.1 53.6 25.7 24.3 23.2 21.9 4.3 55.2 26.0 24.5 23.5 22.1 4.4 56.9 26.2 24.8 23.7 22.3 4.6 58.5 26.5 25.0 24.0 22.6 4.7 60.2 26.8 25.3 24.2 22.8 4.9 61.9 27.1 25.5 24.5 23.1 5.0 63.6 27.3 25.8 24.8 23.4 5.2 LP (bar) 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 5.0 5.1 5.3 Cap (kW) 45 °C P.I. HP (kW) (bar) 33.6 21.8 Cap (kW) 45 °C P.I. HP (kW) (bar) 41.8 27.4 25.5 LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 3.5 Table 21 - Cooling capacities CXAN 250 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 33.6 39.7 46.5 53.8 61.6 63.8 65.8 67.7 69.7 71.6 73.6 75.6 77.6 25 P.I. (kW) 15.4 16.0 16.6 17.4 18.2 18.4 18.6 18.9 19.1 19.3 19.5 19.8 20.0 °C HP (bar) 13.9 14.5 15.2 15.9 16.8 17.1 17.3 17.5 17.7 18.0 18.2 18.4 18.7 LP (bar) 1.9 2.3 2.8 3.3 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.1 Cap (kW) 31.9 37.7 44.2 51.1 58.5 60.6 62.5 64.3 66.2 68.1 70.0 71.9 73.7 30 P.I. (kW) 17.2 17.8 18.6 19.4 20.3 20.5 20.8 21.0 21.2 21.5 21.7 22.0 22.2 °C HP (bar) 15.9 16.5 17.2 18.1 19.0 19.2 19.5 19.7 20.0 20.2 20.4 20.7 20.9 LP (bar) 1.9 2.3 2.8 3.3 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.2 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.4 2.8 3.4 4.0 4.1 4.3 4.4 4.6 4.8 4.9 5.1 25.9 LP (bar) 3.4 Cooling performance - Standard version R407C % Ethylen Glycol 23 24 Table 22 - Cooling capacities CXAN 300 Standard version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 40.3 47.7 55.8 64.7 74.1 76.8 79.2 81.6 84.0 86.4 88.8 91.2 93.6 25 P.I. (kW) 18.4 19.1 19.9 20.8 21.7 22.0 22.3 22.5 22.8 23.0 23.3 23.6 23.9 °C HP (bar) 13.7 14.3 15.0 15.7 16.6 16.8 17.0 17.2 17.5 17.7 17.9 18.1 18.4 LP (bar) 1.9 2.3 2.8 3.3 3.8 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.0 Cap (kW) 38.2 45.3 53.1 61.6 70.6 73.2 75.4 77.7 80.0 82.3 84.6 86.9 89.2 30 P.I. (kW) 20.4 21.2 22.1 23.0 24.1 24.4 24.6 24.9 25.2 25.5 25.8 26.0 26.3 °C HP (bar) 15.7 16.3 17.0 17.8 18.6 18.9 19.1 19.3 19.5 19.8 20.0 20.2 20.5 LP (bar) 1.9 2.3 2.8 3.3 3.9 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 Cap (kW) 36.1 42.8 50.3 58.3 66.9 69.3 71.4 73.6 75.7 77.9 80.1 82.3 84.5 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 22.8 17.9 1.9 23.7 18.5 2.3 40.3 26.5 21.0 24.6 19.2 2.8 47.2 27.5 21.7 25.6 20.0 3.3 54.8 28.6 22.5 26.7 20.9 3.9 62.9 29.8 23.4 27.1 21.1 4.1 65.1 30.1 23.7 27.3 21.4 4.2 67.1 30.4 23.9 27.6 21.6 4.3 69.2 30.7 24.1 27.9 21.8 4.5 71.2 31.0 24.4 28.2 22.1 4.6 73.3 31.3 24.6 28.5 22.3 4.8 75.3 31.6 24.8 28.8 22.5 5.0 77.4 32.0 25.1 29.1 22.8 5.1 79.4 32.3 25.3 LP (bar) 2.3 2.8 3.3 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.1 Cap (kW) 45 °C P.I. HP (kW) (bar) 44.0 51.0 30.8 31.9 Cap (kW) 45 °C P.I. HP (kW) (bar) 64.8 74.4 42.2 43.6 24.4 25.3 LP (bar) 2.8 3.4 46 °C Cap P.I. (kW) (kW) 50.3 47 °C Cap P.I. (kW) (kW) 32.7 Table 23 - Cooling capacities CXAN 400 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 51.3 60.8 71.2 82.5 94.5 97.9 100.8 103.8 106.8 109.9 112.9 115.9 118.9 25 P.I. (kW) 24.2 25.0 26.0 27.0 28.2 28.5 28.8 29.1 29.4 29.7 30.0 30.3 30.6 °C HP (bar) 13.5 14.1 14.7 15.3 16.1 16.3 16.5 16.7 16.9 17.1 17.3 17.5 17.7 30 LP Cap P.I. (bar) (kW) (kW) 1.9 48.7 26.9 2.4 57.8 27.9 2.9 67.7 28.9 3.4 78.5 30.0 4.0 90.0 31.3 4.1 93.2 31.6 4.3 96.0 31.9 4.4 98.9 32.3 4.6 101.8 32.6 4.7 104.6 32.9 4.9 107.5 33.2 5.0 110.4 33.6 5.2 113.3 33.9 °C HP (bar) 15.5 16.0 16.7 17.4 18.2 18.4 18.6 18.8 19.0 19.2 19.4 19.6 19.8 Outdoor Ambient Temperature 35 °C 40 °C LP Cap P.I. HP LP Cap P.I. HP (bar) (kW) (kW) (bar) (bar) (kW) (kW) (bar) 1.9 46.0 30.2 17.7 1.9 2.4 54.5 31.2 18.3 2.4 51.1 35.1 20.7 2.9 64.0 32.3 18.9 2.9 60.0 36.3 21.4 3.4 74.2 33.6 19.7 3.4 69.7 37.6 22.2 4.0 85.1 34.9 20.5 4.0 79.9 39.0 23.0 4.1 88.2 35.3 20.7 4.2 82.8 39.4 23.2 4.3 90.9 35.6 20.9 4.3 85.4 39.8 23.4 4.4 93.6 35.9 21.1 4.5 87.9 40.1 23.6 4.6 96.3 36.3 21.3 4.6 90.5 40.5 23.8 4.7 99.1 36.6 21.5 4.8 93.1 40.8 24.1 4.9 101.8 37.0 21.7 4.9 95.7 41.2 24.3 5.0 104.5 37.3 21.9 5.1 98.3 41.6 24.5 5.2 107.2 37.7 22.1 5.2 100.8 41.9 24.7 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.7 4.8 5.0 5.1 5.3 24.9 25.8 LP (bar) 3.5 4.1 46 °C Cap P.I. (kW) (kW) 63.8 43.1 47 °C Cap P.I. (kW) (kW) CG-PRC010-E4 Cooling performance - Standard version R407C % Ethylen Glycol CG-PRC010-E4 Table 24 - Cooling capacities CXAN 450 Standard version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 59.7 70.3 84.9 101.4 118.3 122.9 126.8 130.7 134.6 138.6 142.6 146.6 150.7 25 P.I. (kW) 25.1 26.0 27.3 28.9 30.7 31.2 31.7 32.1 32.6 33.1 33.6 34.1 34.7 °C HP (bar) 13.4 13.9 14.7 15.6 16.6 16.9 17.2 17.4 17.7 17.9 18.2 18.5 18.7 LP (bar) 1.8 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 Cap (kW) 56.6 66.3 79.9 95.6 111.8 116.2 120.0 123.7 127.5 131.3 135.2 139.1 143.0 30 P.I. (kW) 27.8 28.8 30.2 31.9 33.9 34.5 34.9 35.4 35.9 36.5 37.0 37.5 38.1 °C HP (bar) 15.3 15.8 16.6 17.6 18.6 18.9 19.2 19.4 19.7 19.9 20.2 20.5 20.7 LP (bar) 1.9 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.2 5.4 5.6 5.8 Cap (kW) 53.3 62.2 74.7 89.5 105.0 109.3 112.8 116.4 120.1 123.8 127.5 131.2 135.0 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 31.2 17.4 1.9 49.8 35.4 19.8 32.2 17.9 2.3 57.8 36.3 20.3 33.7 18.7 2.9 69.2 37.7 21.1 35.5 19.7 3.6 83.0 39.6 22.1 37.5 20.8 4.3 97.8 41.7 23.2 38.1 21.1 4.5 101.9 42.3 23.5 38.6 21.4 4.7 105.3 42.8 23.7 39.1 21.6 4.9 108.8 43.3 24.1 39.7 21.9 5.1 112.3 43.8 24.3 40.2 22.2 5.3 115.8 44.3 24.6 40.7 22.4 5.5 119.4 44.9 24.9 41.3 22.7 5.7 123.0 45.4 25.2 41.8 23.0 5.8 126.7 46.0 25.5 Cap (kW) 57.9 67.3 80.6 96.2 112.7 117.3 121.1 124.9 128.8 132.7 136.6 140.6 144.6 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 37.1 17.9 1.9 38.4 18.5 2.3 62.4 43.3 20.9 40.3 19.3 2.9 74.4 45.1 21.7 42.6 20.4 3.6 89.0 47.3 22.8 45.1 21.5 4.3 104.7 49.8 24.0 45.8 21.9 4.5 109.2 50.5 24.3 46.4 22.2 4.7 112.8 51.0 24.6 47.0 22.5 4.9 116.5 51.6 24.9 47.6 22.8 5.1 120.2 52.2 25.3 48.2 23.1 5.3 124.0 52.8 25.6 48.8 23.4 5.4 127.8 53.4 25.9 49.4 23.7 5.6 50.0 23.9 5.8 LP (bar) 1.9 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.3 5.5 5.7 5.9 Cap (kW) 45 °C P.I. HP (kW) (bar) 63.4 76.2 90.2 42.5 44.2 46.3 LP (bar) Cap (kW) 45 °C P.I. HP (kW) (bar) 81.4 52.7 23.7 24.7 25.8 LP (bar) 2.9 3.6 4.3 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 62.2 74.8 73.4 43.5 45.2 46.3 Table 25 - Cooling capacities CXAN 490 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 64.8 76.0 91.6 109.3 127.3 132.3 136.4 140.5 144.7 149.0 153.2 157.5 161.8 25 P.I. (kW) 29.6 30.9 32.7 34.8 37.1 37.8 38.4 39.0 39.5 40.1 40.8 41.4 42.0 °C HP (bar) 13.7 14.3 15.2 16.2 17.3 17.6 17.9 18.2 18.4 18.7 19.0 19.3 19.6 LP (bar) 1.8 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 Cap (kW) 61.5 71.9 86.3 103.0 120.2 125.0 128.9 132.9 136.9 141.0 145.1 149.2 153.4 30 P.I. (kW) 33.0 34.3 36.2 38.4 40.9 41.6 42.1 42.7 43.3 44.0 44.6 45.2 45.9 °C HP (bar) 15.7 16.3 17.1 18.2 19.3 19.6 19.9 20.2 20.5 20.8 21.1 21.4 21.7 LP (bar) 1.9 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.2 5.4 5.6 5.8 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.3 5.5 25.5 LP (bar) 3.6 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) Cooling performance - Standard version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% 25 26 Table 26 - Cooling capacities CXAN 500 Standard version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 69.6 82.3 96.3 111.5 127.8 132.5 136.6 140.7 144.9 149.1 153.4 157.7 162.0 25 P.I. (kW) 31.1 32.4 33.8 35.4 37.1 37.7 38.1 38.6 39.1 39.6 40.1 40.6 41.2 °C HP (bar) 14.1 14.8 15.5 16.4 17.3 17.6 17.9 18.1 18.4 18.6 18.9 19.2 19.5 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.7 4.9 5.1 5.2 5.4 Cap (kW) 66.0 78.1 91.4 105.8 121.3 125.7 129.6 133.6 137.6 141.6 145.6 149.7 153.8 30 P.I. (kW) 34.7 36.1 37.7 39.4 41.4 42.0 42.5 43.0 43.5 44.1 44.6 45.2 45.7 °C HP (bar) 16.1 16.8 17.6 18.5 19.5 19.8 20.1 20.3 20.6 20.9 21.2 21.4 21.7 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.3 5.4 Cap (kW) 62.1 73.5 86.1 99.8 114.4 118.5 122.2 125.9 129.7 133.5 137.3 141.1 145.0 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 39.0 18.4 2.0 40.5 19.1 2.4 68.7 45.7 21.7 42.3 20.0 3.0 80.5 47.5 22.6 44.2 20.9 3.5 93.2 49.6 23.5 46.3 21.9 4.1 106.9 51.8 24.6 46.9 22.2 4.3 110.8 52.4 24.9 47.4 22.5 4.5 114.3 53.0 25.2 48.0 22.8 4.6 117.7 53.6 25.5 48.6 23.1 4.8 121.3 54.2 25.8 49.1 23.3 5.0 49.7 23.6 5.1 50.3 23.9 5.3 50.9 24.2 5.5 Cap (kW) 75.1 89.0 104.3 121.0 138.9 144.0 148.5 153.1 157.7 162.3 167.0 171.8 176.5 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 46.2 18.2 2.0 48.0 18.9 2.4 83.5 53.8 21.4 50.0 19.7 2.9 97.9 55.9 22.2 52.2 20.5 3.5 113.5 58.2 23.1 54.6 21.5 4.1 130.4 60.8 24.1 55.3 21.8 4.3 135.2 61.5 24.4 55.9 22.1 4.4 139.4 62.1 24.6 56.6 22.3 4.6 143.7 62.8 24.9 57.2 22.6 4.7 148.0 63.5 25.2 57.9 22.9 4.9 152.4 64.2 25.4 58.6 23.1 5.1 156.8 64.9 25.7 59.3 23.4 5.2 60.0 23.7 5.4 LP (bar) Cap (kW) 45 °C P.I. HP (kW) (bar) LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) Cap (kW) 45 °C P.I. HP (kW) (bar) LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 91.1 105.6 62.5 65.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 Table 27 - Cooling capacities CXAN 600 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 83.8 99.1 116.1 134.4 154.3 160.0 165.0 170.1 175.2 180.3 185.6 190.8 196.1 25 P.I. (kW) 37.2 38.7 40.4 42.3 44.4 45.0 45.6 46.2 46.7 47.3 47.9 48.6 49.2 °C HP (bar) 14.0 14.6 15.4 16.2 17.1 17.4 17.6 17.9 18.1 18.4 18.6 18.9 19.2 LP (bar) 2.0 2.4 2.9 3.4 4.0 4.2 4.4 4.5 4.7 4.8 5.0 5.2 5.3 Cap (kW) 79.5 94.1 110.4 127.9 146.8 152.2 157.0 161.8 166.7 171.6 176.6 181.6 186.6 30 P.I. (kW) 41.3 43.0 44.8 46.9 49.2 49.8 50.4 51.0 51.7 52.3 52.9 53.6 54.3 °C HP (bar) 16.0 16.6 17.4 18.2 19.2 19.5 19.7 20.0 20.2 20.5 20.8 21.0 21.3 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 24.9 25.9 3.0 3.5 89.7 64.0 CG-PRC010-E4 Cooling performance - Standard version R407C % Ethylen Glycol CG-PRC010-E4 Table 28 - Cooling capacities CXAN 700 Standard version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 91.8 108.8 127.5 147.8 169.7 175.9 181.4 187.0 192.7 198.4 204.2 210.1 216.0 25 P.I. (kW) 42.9 44.5 46.3 48.3 50.6 51.2 51.8 52.4 53.0 53.7 54.3 55.0 55.6 °C HP (bar) 13.9 14.5 15.2 16.0 16.9 17.1 17.3 17.6 17.8 18.1 18.3 18.6 18.8 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.7 4.8 5.0 5.2 5.3 5.5 Cap (kW) 87.0 103.1 120.9 140.2 161.0 167.0 172.2 177.6 183.0 188.4 193.9 199.5 205.1 30 P.I. (kW) 47.9 49.7 51.7 54.0 56.4 57.2 57.8 58.5 59.2 59.8 60.5 61.2 62.0 °C HP (bar) 15.9 16.5 17.3 18.1 19.0 19.3 19.5 19.8 20.0 20.3 20.6 20.8 21.1 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 Cap (kW) 81.8 97.0 113.9 132.1 151.8 157.4 162.4 167.4 172.5 177.7 182.9 188.1 193.4 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 53.9 18.1 2.0 55.9 18.8 2.5 90.5 63.1 21.4 58.1 19.6 3.0 106.3 65.5 22.2 60.6 20.5 3.6 123.4 68.1 23.1 63.3 21.4 4.2 141.9 71.0 24.1 64.0 21.7 4.4 147.1 71.9 24.4 64.7 22.0 4.5 151.8 72.6 24.6 65.4 22.2 4.7 156.5 73.3 24.9 66.2 22.5 4.9 161.3 74.1 25.2 66.9 22.7 5.0 166.1 74.9 25.4 67.7 23.0 5.2 171.0 75.7 25.7 68.4 23.3 5.4 69.2 23.6 5.6 Cap (kW) 94.3 112.1 131.8 153.3 176.5 183.2 189.1 195.1 201.2 207.3 213.5 219.8 226.1 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 60.3 17.7 2.0 62.3 18.4 2.5 105.1 69.9 20.8 64.5 19.0 3.0 123.6 72.3 21.5 67.0 19.8 3.5 143.8 74.9 22.3 69.7 20.7 4.2 165.8 77.8 23.2 70.4 20.9 4.3 172.0 78.6 23.4 71.1 21.1 4.5 177.6 79.3 23.7 71.8 21.4 4.7 183.3 80.1 23.9 72.6 21.6 4.8 189.0 80.8 24.1 73.3 21.8 5.0 194.8 81.6 24.4 74.0 22.1 5.2 200.7 82.4 24.6 74.8 22.3 5.3 206.6 83.2 24.9 75.5 22.5 5.5 212.6 84.0 25.1 LP (bar) 2.5 3.0 3.6 4.2 4.4 4.6 4.7 4.9 5.1 5.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 114.0 76.7 Cap (kW) 45 °C P.I. HP (kW) (bar) 133.8 154.3 83.9 86.9 26.0 LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 3.6 Table 29 - Cooling capacities CXAN 800 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 105.4 125.0 146.7 170.4 196.0 203.3 209.8 216.4 223.1 229.9 236.7 243.7 250.6 25 P.I. (kW) 48.4 50.1 52.0 54.0 56.4 57.0 57.6 58.2 58.9 59.5 60.2 60.8 61.5 °C HP (bar) 13.6 14.2 14.8 15.5 16.3 16.6 16.8 17.0 17.2 17.4 17.6 17.9 18.1 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 4.9 5.1 5.3 5.5 Cap (kW) 100.0 118.7 139.5 162.1 186.6 193.6 199.8 206.1 212.5 219.0 225.5 232.1 238.8 30 P.I. (kW) 53.8 55.7 57.8 60.0 62.5 63.3 63.9 64.6 65.2 65.9 66.6 67.3 68.1 °C HP (bar) 15.6 16.1 16.8 17.5 18.4 18.6 18.8 19.0 19.3 19.5 19.7 20.0 20.2 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.5 3.0 3.6 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 5.6 25.1 25.9 LP (bar) 3.6 4.2 131.7 85.9 Cooling performance - Standard version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% 27 28 Table 30 - Cooling capacities CXAN 900 Standard version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 119.8 142.1 166.7 193.5 222.4 230.6 237.9 245.4 252.9 260.5 268.2 275.9 283.7 25 P.I. (kW) 55.3 57.5 60.0 62.7 65.7 66.6 67.4 68.3 69.1 69.9 70.8 71.7 72.6 °C HP (bar) 13.9 14.5 15.2 16.1 17.0 17.2 17.5 17.7 18.0 18.2 18.5 18.7 19.0 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.3 5.5 Cap (kW) 113.6 134.9 158.5 184.0 211.5 219.3 226.3 233.4 240.6 247.8 255.1 262.5 269.9 30 P.I. (kW) 61.5 63.9 66.5 69.5 72.8 73.7 74.6 75.5 76.3 77.3 78.2 79.1 80.1 °C HP (bar) 15.9 16.5 17.3 18.1 19.1 19.3 19.6 19.8 20.1 20.3 20.6 20.9 21.2 LP (bar) 2.0 2.5 3.0 3.6 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 Cap (kW) 107.2 127.4 149.7 173.9 200.0 207.4 214.0 220.7 227.5 234.3 241.2 248.2 255.2 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 68.8 18.1 2.0 71.3 18.8 2.5 119.5 79.9 21.2 74.2 19.5 3.0 140.4 83.0 22.0 77.3 20.4 3.6 163.2 86.3 22.9 80.8 21.4 4.2 187.7 90.0 23.9 81.8 21.6 4.4 194.6 91.0 24.2 82.7 21.9 4.5 200.8 92.0 24.5 83.7 22.2 4.7 207.1 92.9 24.7 84.6 22.4 4.9 213.5 93.9 25.0 85.6 22.7 5.0 220.0 94.9 25.3 86.6 23.0 5.2 226.5 95.9 25.6 87.5 23.2 5.4 233.0 97.0 25.9 88.6 23.5 5.6 Cap (kW) 123.8 146.4 171.4 198.6 228.2 236.6 244.2 252.0 259.9 267.9 276.0 284.3 292.7 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 75.9 17.9 2.1 79.0 18.6 2.6 135.4 88.7 21.0 82.4 19.4 3.1 158.8 92.1 21.8 86.3 20.3 3.8 184.5 95.9 22.7 90.7 21.3 4.4 212.5 100.1 23.7 92.0 21.6 4.6 220.5 101.3 24.0 93.1 21.9 4.8 227.8 102.4 24.3 94.3 22.1 5.0 235.2 103.6 24.6 95.5 22.4 5.2 242.7 104.7 24.9 96.7 22.7 5.4 250.4 105.9 25.2 97.9 23.0 5.6 258.3 107.1 25.5 99.2 23.3 5.8 266.2 108.3 25.8 100.5 23.6 6.0 LP (bar) 2.5 3.0 3.6 4.2 4.4 4.5 4.7 4.9 5.1 5.2 5.4 Cap (kW) 45 °C P.I. HP (kW) (bar) 151.7 96.4 Cap (kW) 45 °C P.I. HP (kW) (bar) 25.7 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 3.8 166.4 108.9 LP (bar) 3.6 Table 31 - Cooling capacities CXAN 925 Standard version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 140.4 165.8 193.9 224.3 257.2 266.6 275.0 283.5 292.2 300.9 309.8 318.9 328.0 25 P.I. (kW) 61.1 63.9 67.0 70.7 74.8 76.1 77.2 78.3 79.5 80.7 82.0 83.3 84.6 °C HP (bar) 13.9 14.6 15.3 16.2 17.1 17.4 17.6 17.9 18.2 18.4 18.7 19.0 19.3 LP (bar) 2.1 2.6 3.1 3.7 4.4 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 Cap (kW) 132.5 156.5 183.0 211.9 243.1 251.9 259.9 268.1 276.3 284.7 293.2 301.9 310.6 30 P.I. (kW) 67.7 70.7 74.1 77.9 82.3 83.5 84.7 85.9 87.1 88.3 89.6 90.9 92.2 °C HP (bar) 15.8 16.5 17.2 18.1 19.1 19.4 19.6 19.9 20.2 20.5 20.8 21.1 21.4 LP (bar) 2.1 2.6 3.1 3.8 4.4 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.6 3.2 3.8 4.5 4.6 4.8 5.0 5.2 5.4 5.6 5.8 169.5 106.6 25.4 CG-PRC010-E4 Cooling performance - Standard version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% CG-PRC010-E4 Table 32 - Cooling capacities CGAN 200 - Super Quiet version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 27.4 32.6 38.2 44.4 51.0 52.8 54.5 56.2 57.8 59.5 61.2 62.9 64.6 25 P.I. (kW) 11.9 12.3 12.7 13.1 13.6 13.7 13.8 14.0 14.1 14.2 14.3 14.5 14.6 °C HP (bar) 13.4 13.9 14.4 15.0 15.7 15.9 16.1 16.3 16.5 16.6 16.8 17.0 17.2 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.1 5.2 Cap (kW) 26.1 30.9 36.3 42.2 48.5 50.3 51.9 53.5 55.1 56.7 58.3 59.9 61.6 30 P.I. (kW) 13.3 13.7 14.2 14.6 15.2 15.3 15.5 15.6 15.7 15.9 16.0 16.2 16.3 °C HP (bar) 15.4 15.9 16.5 17.1 17.8 18.0 18.2 18.4 18.6 18.8 19.0 19.2 19.4 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 5.2 Cap (kW) 24.6 29.2 34.3 39.8 45.8 47.5 49.0 50.5 52.1 53.6 55.2 56.7 58.2 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 15.0 17.6 1.9 15.5 18.1 2.4 27.2 17.5 20.6 15.9 18.7 2.9 32.1 18.0 21.2 16.5 19.4 3.4 37.3 18.6 21.9 17.1 20.1 4.0 43.0 19.2 22.7 17.2 20.3 4.2 44.6 19.4 22.9 17.4 20.5 4.3 46.0 19.6 23.1 17.5 20.7 4.5 47.4 19.7 23.3 17.7 20.9 4.6 48.9 19.9 23.5 17.8 21.1 4.8 50.3 20.1 23.7 18.0 21.3 5.0 51.8 20.2 23.9 18.1 21.5 5.1 53.2 20.4 24.1 18.3 21.7 5.3 54.7 20.6 24.3 Cap (kW) 30.7 36.4 42.6 49.4 56.5 58.6 60.4 62.2 63.9 65.8 67.6 69.4 71.2 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 19.1 17.9 1.9 19.8 18.5 2.4 34.0 22.3 21.1 20.5 19.2 2.9 39.9 23.1 21.8 21.3 20.0 3.4 46.2 24.0 22.6 22.2 20.9 4.0 52.9 24.9 23.5 22.4 21.1 4.2 54.8 25.2 23.8 22.6 21.3 4.3 56.5 25.5 24.0 22.9 21.6 4.5 58.2 25.7 24.2 23.1 21.8 4.6 59.9 26.0 24.5 23.3 22.0 4.8 61.6 26.2 24.7 23.6 22.2 4.9 63.3 26.5 25.0 23.8 22.4 5.1 65.0 26.7 25.2 24.0 22.7 5.3 66.7 27.0 25.5 LP (bar) 2.4 2.9 3.5 4.0 4.2 4.4 4.5 4.7 4.8 5.0 5.2 5.3 Cap (kW) 45 °C P.I. HP (kW) (bar) 29.7 34.6 39.9 41.4 42.7 20.4 21.0 21.7 21.9 22.1 Cap (kW) 45 °C P.I. HP (kW) (bar) 42.8 27.0 24.0 24.7 25.5 25.7 25.9 LP (bar) 2.9 3.5 4.1 4.3 4.4 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 29.2 34.0 33.4 20.9 21.6 22.1 Table 33 - Cooling capacities CGAN 250 - Super Quiet version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 34.3 40.6 47.5 55.0 63.0 65.3 67.3 69.2 71.3 73.3 75.3 77.3 79.3 25 P.I. (kW) 15.1 15.7 16.3 16.9 17.6 17.8 18.0 18.2 18.4 18.6 18.8 19.0 19.2 °C HP (bar) 13.6 14.1 14.7 15.4 16.2 16.4 16.6 16.8 17.0 17.2 17.4 17.6 17.9 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 32.5 38.6 45.2 52.3 59.9 62.0 63.9 65.8 67.7 69.6 71.6 73.5 75.4 30 P.I. (kW) 17.0 17.5 18.2 18.9 19.7 19.9 20.2 20.4 20.6 20.8 21.0 21.2 21.4 °C HP (bar) 15.6 16.2 16.9 17.6 18.4 18.6 18.8 19.0 19.3 19.5 19.7 19.9 20.1 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.2 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.4 2.9 3.4 4.0 4.2 4.4 4.5 4.7 4.8 5.0 5.1 5.3 25.5 LP (bar) 3.5 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 29 Cooling performance - Super Quiet version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% 30 Table 34 - Cooling capacities CGAN 300 - Super Quiet version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 41.4 49.0 57.4 66.5 76.3 79.1 81.5 83.9 86.4 88.9 91.4 93.8 96.3 25 P.I. (kW) 18.0 18.6 19.2 20.0 20.8 21.0 21.2 21.4 21.6 21.9 22.1 22.3 22.5 °C HP (bar) 13.3 13.8 14.4 15.0 15.7 15.9 16.1 16.3 16.5 16.6 16.8 17.0 17.2 LP (bar) 1.9 2.3 2.8 3.4 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.1 Cap (kW) 39.3 46.6 54.7 63.4 72.7 75.3 77.6 80.0 82.3 84.7 87.0 89.4 91.7 30 P.I. (kW) 20.1 20.7 21.5 22.3 23.2 23.4 23.6 23.9 24.1 24.3 24.6 24.8 25.1 °C HP (bar) 15.3 15.8 16.4 17.1 17.8 18.0 18.2 18.4 18.6 18.8 19.0 19.2 19.4 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 22.5 17.5 1.9 34.9 25.3 20.0 23.2 18.1 2.4 41.4 26.1 20.6 24.0 18.7 2.9 48.6 27.0 21.2 24.9 19.4 3.4 56.4 28.0 22.0 25.9 20.2 4.0 64.7 29.0 22.8 26.2 20.4 4.1 67.0 29.3 23.0 26.4 20.6 4.3 69.1 29.6 23.2 26.7 20.8 4.4 71.2 29.8 23.4 26.9 21.0 4.6 73.3 30.1 23.6 27.2 21.2 4.7 75.4 30.4 23.8 27.4 21.4 4.9 77.5 30.7 24.1 27.7 21.6 5.0 79.6 30.9 24.3 28.0 21.8 5.2 81.7 31.2 24.5 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 5.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 45.3 52.5 60.3 62.5 30.3 31.4 32.5 32.8 Outdoor Ambient Temperature 35 °C 40 °C LP Cap P.I. HP LP Cap P.I. HP (bar) (kW) (kW) (bar) (bar) (kW) (kW) (bar) 1.9 49.9 29.7 17.3 1.9 46.9 33.4 19.8 2.4 59.3 30.6 17.8 2.4 55.7 34.4 20.3 2.9 69.6 31.6 18.4 2.9 65.4 35.5 20.9 3.4 80.7 32.6 19.1 3.4 75.9 36.6 21.5 4.0 92.6 33.8 19.8 4.0 87.1 37.8 22.3 4.1 96.0 34.1 20.0 4.1 90.3 38.2 22.5 4.3 98.9 34.4 20.1 4.3 93.1 38.5 22.7 4.4 101.9 34.7 20.3 4.4 95.8 38.8 22.8 4.6 104.8 35.0 20.5 4.6 98.6 39.1 23.0 4.7 107.8 35.3 20.7 4.7 101.4 39.5 23.2 4.8 110.7 35.6 20.9 4.9 104.2 39.8 23.4 5.0 113.6 35.9 21.1 5.0 107.0 40.1 23.6 5.1 116.6 36.2 21.2 5.2 109.7 40.4 23.8 LP (bar) 1.9 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 5.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 60.9 70.8 81.3 84.2 86.8 89.4 92.0 39.9 41.1 42.4 42.8 43.1 43.5 43.8 LP (bar) 1.9 2.4 2.8 3.4 3.9 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 37.1 44.1 51.7 60.0 68.8 71.3 73.5 75.7 77.9 80.2 82.4 84.6 86.9 24.0 24.8 25.6 25.8 LP (bar) 2.9 3.4 4.0 4.2 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 44.6 51.7 43.9 50.9 31.1 32.1 31.8 32.8 Table 35 - Cooling capacities CGAN 400 - Super Quiet version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 55.6 65.9 77.3 89.5 102.6 106.3 109.5 112.7 116.0 119.3 122.5 125.8 129.0 25 P.I. (kW) 23.8 24.5 25.3 26.2 27.2 27.4 27.7 27.9 28.2 28.4 28.7 28.9 29.2 °C HP (bar) 13.2 13.7 14.2 14.8 15.4 15.6 15.8 15.9 16.1 16.3 16.5 16.6 16.8 30 LP Cap P.I. (bar) (kW) (kW) 1.9 52.8 26.5 2.4 62.7 27.3 2.9 73.5 28.2 3.4 85.3 29.2 3.9 97.7 30.2 4.1 101.3 30.5 4.2 104.4 30.8 4.4 107.5 31.1 4.5 110.6 31.3 4.7 113.7 31.6 4.8 116.8 31.9 5.0 119.9 32.2 5.1 123.0 32.4 °C HP (bar) 15.2 15.7 16.2 16.8 17.5 17.7 17.8 18.0 18.2 18.4 18.6 18.7 18.9 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° 23.6 24.3 25.0 25.3 25.4 25.6 25.8 LP (bar) 2.9 3.5 4.0 4.2 4.3 4.5 4.6 46 °C Cap P.I. (kW) (kW) 60.0 69.7 80.0 82.9 40.8 42.1 43.4 43.8 47 °C Cap P.I. (kW) (kW) 68.6 43.1 CG-PRC010-E4 Cooling performance - Super Quiet version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% CG-PRC010-E4 Table 36 - Cooling capacities CGAN 450 - Super Quiet version Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 61.2 72.4 88.0 105.4 123.2 128.0 132.1 136.3 140.4 144.6 148.8 153.0 157.3 25 P.I. (kW) 26.1 26.9 28.0 29.4 30.8 31.3 31.6 32.0 32.4 32.8 33.2 33.7 34.1 °C HP (bar) 14.0 14.4 15.0 15.7 16.5 16.7 16.9 17.1 17.3 17.5 17.7 17.9 18.1 LP (bar) 2.9 3.3 3.9 4.6 5.4 5.6 5.7 5.9 6.1 6.3 6.5 6.7 6.8 Cap (kW) 58.1 68.4 82.9 99.6 116.7 121.3 125.2 129.2 133.2 137.2 141.3 145.3 149.4 30 P.I. (kW) 29.1 29.9 31.2 32.7 34.4 34.9 35.3 35.7 36.2 36.6 37.1 37.5 38.0 °C HP (bar) 15.9 16.4 17.0 17.8 18.6 18.8 19.0 19.2 19.4 19.6 19.9 20.1 20.3 LP (bar) 2.9 3.3 3.9 4.6 5.4 5.6 5.8 5.9 6.1 6.3 6.5 6.7 6.9 Cap (kW) 54.8 64.2 77.6 93.3 109.7 114.2 118.0 121.8 125.6 129.5 133.4 137.3 141.3 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 32.8 18.1 2.9 33.7 18.6 3.3 59.8 38.1 21.0 35.0 19.2 3.9 72.0 39.5 21.7 36.6 20.0 4.6 86.8 41.2 22.5 38.5 20.9 5.4 102.4 43.1 23.4 39.0 21.1 5.6 106.7 43.6 23.7 39.4 21.4 5.8 110.4 44.1 23.9 39.9 21.6 5.9 114.0 44.5 24.1 40.4 21.8 6.1 117.7 45.0 24.4 40.8 22.0 6.3 121.4 45.5 24.6 41.3 22.2 6.5 125.2 46.0 24.9 41.8 22.5 6.7 128.9 46.5 25.1 42.3 22.7 6.9 132.8 47.0 25.4 Cap (kW) 60.2 70.5 84.9 101.8 119.4 124.2 128.2 132.3 136.4 140.5 144.7 148.9 153.1 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 38.7 17.5 1.9 39.9 18.0 2.3 65.4 45.3 20.5 41.7 18.8 2.9 78.6 47.0 21.3 43.8 19.7 3.6 94.4 49.0 22.2 46.0 20.6 4.4 111.2 51.3 23.2 46.6 20.9 4.6 115.9 51.9 23.5 47.2 21.1 4.8 119.7 52.4 23.7 47.7 21.3 4.9 123.6 53.0 24.0 48.3 21.6 5.1 127.6 53.5 24.2 48.8 21.8 5.3 131.6 54.1 24.5 49.4 22.1 5.5 135.6 54.6 24.8 50.0 22.3 5.7 139.6 55.2 25.0 50.5 22.6 5.9 143.7 55.7 25.3 LP (bar) 3.3 3.9 4.6 5.4 5.6 5.8 6.0 6.1 6.3 6.5 6.7 6.9 Cap (kW) 45 °C P.I. HP (kW) (bar) 66.1 79.8 44.6 46.3 Cap (kW) 45 °C P.I. HP (kW) (bar) 86.5 54.9 24.4 25.3 LP (bar) 3.9 4.6 46 °C Cap P.I. (kW) (kW) 78.4 47 °C Cap P.I. (kW) (kW) 47.4 Table 37 - Cooling capacities CGAN 490 - Super Quiet version % Ethylen Glycol Leaving Chilled Water Temp. 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 67.1 79.3 96.2 115.2 134.4 139.6 144.0 148.4 152.9 157.3 161.8 166.4 170.9 25 P.I. (kW) 30.7 31.8 33.4 35.2 37.1 37.7 38.1 38.6 39.1 39.6 40.2 40.7 41.2 °C HP (bar) 13.3 13.8 14.4 15.2 16.1 16.3 16.5 16.7 16.9 17.2 17.4 17.6 17.8 LP (bar) 1.9 2.3 2.9 3.6 4.4 4.6 4.7 4.9 5.1 5.3 5.5 5.7 5.8 Cap (kW) 63.9 75.1 90.8 108.7 127.1 132.1 136.3 140.6 144.8 149.1 153.5 157.8 162.2 30 P.I. (kW) 34.3 35.5 37.2 39.1 41.3 41.9 42.4 42.9 43.5 44.0 44.6 45.1 45.7 °C HP (bar) 15.3 15.8 16.5 17.3 18.3 18.5 18.7 18.9 19.2 19.4 19.6 19.9 20.1 LP (bar) 1.9 2.3 2.9 3.6 4.4 4.6 4.7 4.9 5.1 5.3 5.5 5.7 5.9 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.3 2.9 3.6 4.4 4.6 4.8 5.0 5.1 5.3 5.5 5.7 5.9 25.0 LP (bar) 3.6 46 °C Cap P.I. (kW) (kW) 84.9 56.2 47 °C Cap P.I. (kW) (kW) 31 Cooling performance - Super Quiet version R407C % Ethylen Glycol 32 Table 38 - Cooling capacities CGAN 500 - Super Quiet version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 70.4 83.3 97.6 113.1 129.7 134.5 138.7 142.9 147.2 151.5 155.9 160.3 164.7 25 P.I. (kW) 30.4 31.5 32.7 34.0 35.5 36.0 36.4 36.8 37.2 37.6 38.0 38.5 38.9 °C HP (bar) 13.7 14.2 14.8 15.6 16.4 16.6 16.8 17.0 17.2 17.4 17.7 17.9 18.2 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.3 5.4 Cap (kW) 66.8 79.1 92.7 107.4 123.2 127.8 131.7 135.8 139.8 143.9 148.1 152.3 156.5 30 P.I. (kW) 34.1 35.3 36.6 38.1 39.8 40.3 40.7 41.2 41.6 42.1 42.6 43.0 43.5 °C HP (bar) 15.7 16.3 17.0 17.7 18.6 18.8 19.0 19.3 19.5 19.7 20.0 20.2 20.5 LP (bar) 2.0 2.4 3.0 3.5 4.1 4.3 4.5 4.6 4.8 4.9 5.1 5.3 5.5 Cap (kW) 62.9 74.5 87.4 101.3 116.3 120.5 124.3 128.1 131.9 135.8 139.7 143.7 147.6 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 38.4 18.0 2.0 39.7 18.6 2.5 69.7 44.8 21.2 41.2 19.3 3.0 81.7 46.5 21.9 42.9 20.1 3.5 94.8 48.3 22.8 44.7 21.0 4.1 108.8 50.3 23.7 45.3 21.3 4.3 112.8 50.9 24.0 45.7 21.5 4.5 116.3 51.4 24.2 46.2 21.8 4.6 119.9 51.9 24.5 46.7 22.0 4.8 123.5 52.4 24.7 47.2 22.3 5.0 127.1 53.0 25.0 47.7 22.5 5.1 130.8 53.5 25.3 48.3 22.8 5.3 134.5 54.1 25.5 48.8 23.0 5.5 138.2 54.6 25.8 Cap (kW) 76.1 90.3 106.0 123.1 141.5 146.7 151.4 156.1 160.8 165.6 170.4 175.3 180.2 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 45.2 17.6 2.0 71.5 50.8 20.1 46.7 18.2 2.4 84.8 52.5 20.7 48.4 18.8 2.9 99.6 54.3 21.3 50.2 19.6 3.5 115.6 56.3 22.1 52.2 20.3 4.1 133.0 58.5 22.9 52.8 20.6 4.3 137.9 59.1 23.2 53.3 20.8 4.4 142.2 59.6 23.4 53.9 21.0 4.6 146.7 60.2 23.6 54.4 21.2 4.8 151.1 60.8 23.9 55.0 21.5 4.9 155.6 61.4 24.1 55.5 21.7 5.1 160.2 62.0 24.3 56.1 21.9 5.3 164.8 62.6 24.6 56.7 22.2 5.4 169.4 63.2 24.8 LP (bar) 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 Cap (kW) 45 °C P.I. HP (kW) (bar) 75.7 87.8 52.5 54.4 LP (bar) 24.8 25.7 3.0 3.6 °C HP (bar) LP (bar) 24.1 24.9 25.8 3.0 3.5 4.2 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 91.4 106.0 89.9 Table 39 - Cooling capacities CGAN 600 - Super Quiet version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 84.9 100.5 117.8 136.6 157.0 162.8 167.9 173.1 178.4 183.7 189.1 194.5 199.9 25 P.I. (kW) 36.1 37.4 38.7 40.2 41.9 42.4 42.9 43.3 43.8 44.2 44.7 45.2 45.7 °C HP (bar) 13.4 13.9 14.5 15.1 15.9 16.1 16.3 16.5 16.7 16.9 17.1 17.3 17.5 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 Cap (kW) 80.6 95.5 112.1 130.1 149.5 155.0 159.9 164.9 169.9 175.0 180.1 185.2 190.4 30 P.I. (kW) 40.3 41.7 43.2 44.9 46.7 47.3 47.7 48.2 48.7 49.3 49.8 50.3 50.9 °C HP (bar) 15.4 15.9 16.5 17.2 18.0 18.2 18.4 18.6 18.8 19.0 19.3 19.5 19.7 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.7 4.9 5.1 5.2 5.4 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° 45 LP Cap P.I. (bar) (kW) (kW) 2.0 2.4 3.0 92.8 61.0 3.5 107.7 63.1 4.1 123.8 65.4 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 62.4 64.6 63.9 CG-PRC010-E4 Cooling performance - Super Quiet version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% CG-PRC010-E4 Table 40 - Cooling capacities CGAN 700 - Super Quiet version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 99.2 117.7 138.0 160.0 183.8 190.6 196.6 202.7 208.8 215.0 221.3 227.6 233.9 25 P.I. (kW) 42.6 44.0 45.7 47.5 49.6 50.2 50.8 51.3 51.9 52.5 53.1 53.7 54.3 °C HP (bar) 13.7 14.2 14.9 15.6 16.4 16.6 16.8 17.0 17.3 17.5 17.7 17.9 18.2 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 Cap (kW) 94.1 111.6 131.0 151.9 174.5 181.0 186.7 192.5 198.3 204.2 210.1 216.1 222.1 30 P.I. (kW) 47.6 49.3 51.1 53.2 55.5 56.2 56.8 57.4 58.1 58.7 59.4 60.0 60.7 °C HP (bar) 15.7 16.3 17.0 17.7 18.6 18.8 19.0 19.3 19.5 19.7 20.0 20.2 20.5 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.2 5.3 5.5 Cap (kW) 88.7 105.2 123.4 143.2 164.6 170.7 176.1 181.5 187.0 192.6 198.2 203.8 209.5 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 53.6 18.0 2.0 55.5 18.6 2.5 98.2 62.6 21.1 57.5 19.3 3.0 115.3 64.9 21.9 59.8 20.1 3.6 133.9 67.4 22.7 62.4 21.0 4.2 153.9 70.2 23.6 63.1 21.2 4.3 159.6 71.0 23.9 63.8 21.5 4.5 164.7 71.7 24.2 64.4 21.7 4.7 169.8 72.4 24.4 65.1 22.0 4.8 174.9 73.1 24.6 65.8 22.2 5.0 180.2 73.9 24.9 66.5 22.5 5.2 185.4 74.6 25.2 67.3 22.7 5.4 190.7 75.4 25.4 68.0 23.0 5.5 196.0 76.2 25.7 Cap (kW) 102.4 121.8 143.2 166.6 191.9 199.2 205.6 212.1 218.7 225.4 232.1 238.9 245.7 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 59.6 17.4 2.0 96.1 67.1 19.8 61.5 17.9 2.5 114.2 69.1 20.4 63.5 18.5 3.0 134.5 71.3 21.0 65.7 19.2 3.5 156.5 73.7 21.7 68.2 20.0 4.1 180.4 76.4 22.5 68.9 20.2 4.3 187.2 77.1 22.7 69.6 20.4 4.5 193.2 77.8 22.9 70.2 20.6 4.6 199.4 78.5 23.1 70.9 20.8 4.8 205.6 79.2 23.3 71.6 21.0 5.0 211.9 79.9 23.5 72.3 21.2 5.1 218.3 80.7 23.8 73.0 21.4 5.3 224.7 81.4 24.0 73.7 21.7 5.5 231.1 82.2 24.2 LP (bar) 2.5 3.0 3.6 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 5.6 Cap (kW) 45 °C P.I. HP (kW) (bar) 106.7 123.9 73.3 76.0 Cap (kW) 45 °C P.I. HP (kW) (bar) 125.1 145.7 168.0 174.4 180.1 185.8 80.2 82.7 85.5 86.3 87.1 87.8 24.7 25.6 LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 123.2 143.4 165.5 121.2 141.2 3.0 3.6 Table 41 - Cooling capacities CGAN 800 - Super Quiet version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 114.3 135.6 159.2 184.9 212.9 220.9 228.0 235.2 242.4 249.8 257.2 264.7 272.3 25 P.I. (kW) 47.8 49.3 51.0 52.8 54.9 55.5 56.0 56.6 57.1 57.7 58.3 58.9 59.5 °C HP (bar) 13.3 13.8 14.3 14.9 15.6 15.8 16.0 16.2 16.4 16.6 16.8 17.0 17.2 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.3 5.4 Cap (kW) 108.5 128.9 151.5 176.1 202.7 210.4 217.2 224.0 231.0 238.0 245.1 252.2 259.5 30 P.I. (kW) 53.2 54.9 56.7 58.8 61.1 61.7 62.3 62.9 63.5 64.2 64.8 65.5 66.1 °C HP (bar) 15.2 15.7 16.3 17.0 17.7 17.9 18.1 18.3 18.5 18.7 18.9 19.1 19.3 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 4.9 5.1 5.3 5.5 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge 33 Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 23.7 24.4 25.2 25.5 25.7 25.9 LP (bar) 3.0 3.6 4.2 4.4 4.5 4.7 82.1 84.7 87.5 84.0 86.6 Cooling performance - Super Quiet version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% 34 Table 42 - Cooling capacities CGAN 900 - Super Quiet version Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 129.7 153.7 180.2 209.0 240.1 249.0 256.8 264.8 272.8 281.0 289.2 297.4 305.8 25 P.I. (kW) 54.4 56.3 58.5 60.8 63.5 64.2 64.9 65.7 66.4 67.1 67.9 68.6 69.4 °C HP (bar) 13.5 14.0 14.6 15.3 16.0 16.3 16.5 16.7 16.9 17.1 17.3 17.5 17.8 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.6 4.8 5.0 5.2 5.3 5.5 Cap (kW) 123.0 145.9 171.3 198.8 228.4 236.8 244.3 251.8 259.5 267.2 275.0 282.9 290.8 30 P.I. (kW) 60.7 62.8 65.2 67.8 70.8 71.6 72.4 73.1 73.9 74.8 75.6 76.4 77.3 °C HP (bar) 15.5 16.0 16.7 17.4 18.2 18.4 18.6 18.9 19.1 19.3 19.5 19.8 20.0 LP (bar) 2.0 2.5 3.0 3.6 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 Cap (kW) 116.1 137.8 161.9 187.9 215.9 223.8 230.9 238.0 245.3 252.6 259.9 267.4 274.8 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 68.1 17.7 2.0 108.9 76.6 20.2 70.4 18.3 2.5 129.3 79.1 20.8 73.0 19.0 3.0 151.8 82.0 21.5 75.9 19.7 3.6 176.3 85.1 22.3 79.1 20.6 4.2 202.5 88.5 23.2 80.0 20.8 4.4 210.0 89.5 23.4 80.8 21.0 4.5 216.6 90.4 23.6 81.7 21.3 4.7 223.3 91.3 23.9 82.5 21.5 4.9 230.1 92.2 24.1 83.4 21.7 5.0 237.0 93.1 24.4 84.3 22.0 5.2 243.9 94.1 24.6 85.2 22.2 5.4 250.9 95.0 24.9 86.1 22.5 5.6 257.9 96.0 25.1 Cap (kW) 130.3 154.2 180.5 209.2 240.1 248.9 256.8 264.9 273.1 281.4 289.8 298.3 306.9 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 79.7 17.7 2.1 82.6 18.3 2.6 142.7 93.3 20.7 85.8 18.9 3.2 167.4 96.5 21.4 89.4 19.7 3.8 194.3 100.1 22.2 93.5 20.5 4.5 223.6 104.1 23.1 94.7 20.7 4.7 231.9 105.3 23.4 95.7 21.0 4.9 239.5 106.3 23.6 96.8 21.2 5.1 247.2 107.4 23.8 98.0 21.4 5.2 254.9 108.5 24.1 99.1 21.7 5.4 262.9 109.6 24.3 100.3 21.9 5.6 270.9 110.8 24.6 101.5 22.2 5.8 279.1 111.9 24.9 102.7 22.5 6.1 287.4 113.1 25.1 45 LP Cap P.I. (bar) (kW) (kW) 2.0 2.5 3.0 141.2 92.1 3.6 163.9 95.4 4.2 4.4 4.5 4.7 4.9 5.1 5.2 5.4 5.6 °C HP (bar) LP (bar) 24.3 25.1 3.0 3.6 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 139.0 161.3 136.8 94.2 97.6 96.4 Table 43 - Cooling capacities CGAN 925 - Super Quiet version % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 147.4 174.3 204.0 236.1 270.7 280.5 289.3 298.2 307.3 316.4 325.7 335.0 344.5 25 P.I. (kW) 63.5 66.0 68.8 71.9 75.5 76.5 77.5 78.5 79.5 80.6 81.7 82.8 84.0 °C HP (bar) 13.4 14.0 14.6 15.2 16.0 16.2 16.4 16.6 16.8 17.1 17.3 17.5 17.7 LP (bar) 2.1 2.6 3.2 3.8 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 6.0 Cap (kW) 139.3 164.7 192.7 223.1 255.8 265.1 273.4 281.9 290.5 299.2 308.0 316.9 326.0 30 P.I. (kW) 70.8 73.5 76.6 80.0 83.9 85.1 86.1 87.2 88.3 89.4 90.6 91.8 93.0 °C HP (bar) 15.4 16.0 16.6 17.3 18.2 18.4 18.6 18.8 19.0 19.3 19.5 19.7 20.0 LP (bar) 2.1 2.6 3.2 3.8 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 6.0 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.6 3.2 3.8 4.5 4.7 4.9 5.1 5.3 5.5 5.7 5.9 6.1 Cap (kW) 45 °C P.I. HP (kW) (bar) 178.6 112.1 206.3 115.9 25.0 26.0 LP (bar) 3.8 4.5 46 °C Cap P.I. (kW) (kW) 175.3 114.6 47 °C Cap P.I. (kW) (kW) CG-PRC010-E4 Cooling performance - Super Quiet version R407C % Ethylen Glycol 37% 33% 27% 20% 10% 0% 0% 0% 0% 0% 0% 0% 0% CG-PRC010-E4 Table 44 - Cooling capacities CXAN 200 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. °C HP (bar) 14.0 14.6 15.3 16.1 17.0 17.3 17.5 17.7 18.0 18.2 18.5 18.7 18.9 LP (bar) 1.9 2.3 2.8 3.4 3.9 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 25.5 30.3 35.5 41.1 47.2 48.9 50.5 52.0 53.5 55.1 56.7 58.2 59.8 30 P.I. (kW) 13.8 14.3 14.9 15.5 16.2 16.4 16.6 16.8 16.9 17.1 17.3 17.5 17.7 °C HP (bar) 16.0 16.6 17.4 18.2 19.1 19.4 19.6 19.8 20.1 20.3 20.6 20.8 21.0 LP (bar) 1.9 2.4 2.8 3.4 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.0 5.2 Cap (kW) 24.1 28.5 33.4 38.8 44.5 46.2 47.6 49.1 50.6 52.0 53.5 55.0 56.5 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 15.5 18.2 1.9 16.0 18.8 2.4 26.6 18.1 21.3 16.7 19.6 2.9 31.2 18.8 22.1 17.3 20.4 3.4 36.2 19.5 22.9 18.1 21.3 4.0 41.7 20.3 23.9 18.3 21.6 4.2 43.2 20.5 24.1 18.5 21.9 4.3 44.6 20.7 24.4 18.7 22.1 4.5 46.0 20.9 24.6 18.9 22.4 4.6 47.3 21.1 24.9 19.1 22.6 4.8 48.7 21.3 25.1 19.3 22.9 4.9 50.1 21.5 25.4 19.5 23.1 5.1 51.5 21.8 25.7 19.7 23.4 5.2 52.9 22.0 26.0 Cap (kW) 30.0 35.5 41.5 48.0 54.9 56.9 58.6 60.4 62.1 63.9 65.6 67.4 69.1 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 19.4 18.3 1.9 20.2 19.0 2.3 33.1 22.8 21.5 21.0 19.8 2.8 38.8 23.7 22.4 22.0 20.7 3.4 44.9 24.7 23.3 23.0 21.7 3.9 51.4 25.8 24.3 23.3 21.9 4.1 53.2 26.1 24.6 23.5 22.2 4.3 54.8 26.4 24.9 23.8 22.5 4.4 56.5 26.6 25.1 24.1 22.7 4.6 58.1 26.9 25.4 24.4 22.9 4.7 59.7 27.2 25.7 24.6 23.2 4.9 61.4 27.5 25.9 24.9 23.5 5.0 25.2 23.8 5.2 LP (bar) 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.6 4.8 5.0 5.1 5.3 Cap (kW) 45 °C P.I. HP (kW) (bar) 33.5 21.9 Cap (kW) 45 °C P.I. HP (kW) (bar) 25.7 LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 3.5 Table 45 - Cooling capacities CXAN 250 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 33.5 39.7 46.4 53.6 61.4 63.6 65.5 67.4 69.3 71.3 73.3 75.2 77.2 25 P.I. (kW) 15.5 16.1 16.8 17.6 18.4 18.7 18.9 19.1 19.3 19.6 19.8 20.1 20.3 °C HP (bar) 14.0 14.6 15.3 16.1 17.1 17.3 17.6 17.8 18.0 18.3 18.5 18.7 19.0 LP (bar) 1.9 2.3 2.8 3.3 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.1 Cap (kW) 31.8 37.6 44.0 50.9 58.3 60.3 62.2 64.0 65.9 67.7 69.6 71.4 73.3 30 P.I. (kW) 17.3 18.0 18.7 19.6 20.5 20.8 21.1 21.3 21.6 21.8 22.1 22.3 22.6 °C HP (bar) 16.0 16.7 17.4 18.3 19.2 19.5 19.8 20.0 20.3 20.5 20.7 21.0 21.3 LP (bar) 1.9 2.3 2.8 3.3 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.2 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.4 2.9 3.4 4.0 4.1 4.3 4.4 4.6 4.8 4.9 LP (bar) 35 Cooling performance - Super Quiet version R407C -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 26.9 31.9 37.4 43.3 49.7 51.5 53.1 54.7 56.3 58.0 59.6 61.3 62.9 25 P.I. (kW) 12.3 12.8 13.3 13.9 14.5 14.7 14.9 15.1 15.2 15.4 15.6 15.8 16.0 36 Table 46 - Cooling capacities CXAN 300 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. °C HP (bar) 13.9 14.5 15.2 15.9 16.8 17.1 17.3 17.5 17.7 18.0 18.2 18.5 18.7 LP (bar) 1.9 2.3 2.8 3.3 3.8 4.0 4.1 4.3 4.4 4.6 4.7 4.9 5.0 Cap (kW) 38.2 45.2 53.0 61.3 70.3 72.8 75.0 77.3 79.5 81.8 84.1 86.3 88.6 30 P.I. (kW) 20.6 21.4 22.3 23.3 24.4 24.7 25.0 25.3 25.6 25.9 26.2 26.5 26.8 °C HP (bar) 15.8 16.5 17.2 18.0 18.9 19.2 19.4 19.6 19.9 20.1 20.3 20.6 20.8 LP (bar) 1.9 2.3 2.8 3.3 3.9 4.0 4.2 4.3 4.5 4.6 4.8 4.9 5.1 Cap (kW) 36.0 42.7 50.1 58.0 66.5 68.9 71.0 73.1 75.2 77.4 79.5 81.7 83.8 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 23.0 18.0 1.9 23.9 18.7 2.3 40.1 26.8 21.2 24.9 19.4 2.8 47.0 27.8 22.0 26.0 20.3 3.3 54.5 29.0 22.8 27.1 21.2 3.9 62.4 30.2 23.8 27.5 21.5 4.1 64.7 30.6 24.0 27.8 21.7 4.2 66.7 30.9 24.3 28.1 21.9 4.3 68.6 31.2 24.5 28.4 22.2 4.5 70.7 31.5 24.8 28.7 22.4 4.6 72.7 31.8 25.0 29.0 22.7 4.8 74.7 32.2 25.3 29.3 22.9 5.0 76.7 32.5 25.5 29.6 23.2 5.1 78.7 32.8 25.8 LP (bar) 2.3 2.8 3.3 3.9 4.1 4.2 4.4 4.5 4.7 4.8 5.0 5.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 43.8 50.7 31.2 32.4 Cap (kW) 45 °C P.I. HP (kW) (bar) 64.8 74.4 42.2 43.6 24.7 25.6 LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 2.8 3.4 Table 47 - Cooling capacities CXAN 400 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 51.3 60.8 71.2 82.5 94.5 97.9 100.8 103.8 106.8 109.9 112.9 115.9 118.9 25 P.I. (kW) 24.2 25.0 26.0 27.0 28.2 28.5 28.8 29.1 29.4 29.7 30.0 30.3 30.6 °C HP (bar) 13.5 14.1 14.7 15.3 16.1 16.3 16.5 16.7 16.9 17.1 17.3 17.5 17.7 30 LP Cap P.I. (bar) (kW) (kW) 1.9 48.7 26.9 2.4 57.8 27.9 2.9 67.7 28.9 3.4 78.5 30.0 4.0 90.0 31.3 4.1 93.2 31.6 4.3 96.0 31.9 4.4 98.9 32.3 4.6 101.8 32.6 4.7 104.6 32.9 4.9 107.5 33.2 5.0 110.4 33.6 5.2 113.3 33.9 °C HP (bar) 15.5 16.0 16.7 17.4 18.2 18.4 18.6 18.8 19.0 19.2 19.4 19.6 19.8 Outdoor Ambient Temperature 35 °C 40 °C LP Cap P.I. HP LP Cap P.I. HP (bar) (kW) (kW) (bar) (bar) (kW) (kW) (bar) 1.9 46.0 30.2 17.7 1.9 2.4 54.5 31.2 18.3 2.4 51.1 35.1 20.7 2.9 64.0 32.3 18.9 2.9 60.0 36.3 21.4 3.4 74.2 33.6 19.7 3.4 69.7 37.6 22.2 4.0 85.1 34.9 20.5 4.0 79.9 39.0 23.0 4.1 88.2 35.3 20.7 4.2 82.8 39.4 23.2 4.3 90.9 35.6 20.9 4.3 85.4 39.8 23.4 4.4 93.6 35.9 21.1 4.5 87.9 40.1 23.6 4.6 96.3 36.3 21.3 4.6 90.5 40.5 23.8 4.7 99.1 36.6 21.5 4.8 93.1 40.8 24.1 4.9 101.8 37.0 21.7 4.9 95.7 41.2 24.3 5.0 104.5 37.3 21.9 5.1 98.3 41.6 24.5 5.2 107.2 37.7 22.1 5.2 100.8 41.9 24.7 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.4 2.9 3.4 4.0 4.2 4.3 4.5 4.7 4.8 5.0 5.1 5.3 24.9 25.8 LP (bar) 3.5 4.1 63.8 43.1 CG-PRC010-E4 Cooling performance - Super Quiet version R407C -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 40.2 47.6 55.7 64.5 73.8 76.5 78.9 81.2 83.6 85.9 88.3 90.7 93.1 25 P.I. (kW) 18.5 19.2 20.1 21.0 22.0 22.3 22.6 22.8 23.1 23.4 23.7 24.0 24.2 CG-PRC010-E4 Table 48 - Cooling capacities CXAN 450 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Cap (kW) 59.7 70.3 84.9 101.4 118.3 122.9 126.8 130.7 134.6 138.6 142.6 146.6 150.7 25 P.I. (kW) 25.1 26.0 27.3 28.9 30.7 31.2 31.7 32.1 32.6 33.1 33.6 34.1 34.7 °C HP (bar) 13.4 13.9 14.7 15.6 16.6 16.9 17.2 17.4 17.7 17.9 18.2 18.5 18.7 LP (bar) 1.8 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 Cap (kW) 56.6 66.3 79.9 95.6 111.8 116.2 120.0 123.7 127.5 131.3 135.2 139.1 143.0 30 P.I. (kW) 27.8 28.8 30.2 31.9 33.9 34.5 34.9 35.4 35.9 36.5 37.0 37.5 38.1 °C HP (bar) 15.3 15.8 16.6 17.6 18.6 18.9 19.2 19.4 19.7 19.9 20.2 20.5 20.7 LP (bar) 1.9 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.2 5.4 5.6 5.8 Cap (kW) 53.3 62.2 74.7 89.5 105.0 109.3 112.8 116.4 120.1 123.8 127.5 131.2 135.0 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 31.2 17.4 1.9 49.8 35.4 19.8 32.2 17.9 2.3 57.8 36.3 20.3 33.7 18.7 2.9 69.2 37.7 21.1 35.5 19.7 3.6 83.0 39.6 22.1 37.5 20.8 4.3 97.8 41.7 23.2 38.1 21.1 4.5 101.9 42.3 23.5 38.6 21.4 4.7 105.3 42.8 23.7 39.1 21.6 4.9 108.8 43.3 24.1 39.7 21.9 5.1 112.3 43.8 24.3 40.2 22.2 5.3 115.8 44.3 24.6 40.7 22.4 5.5 119.4 44.9 24.9 41.3 22.7 5.7 123.0 45.4 25.2 41.8 23.0 5.8 126.7 46.0 25.5 Cap (kW) 57.9 67.3 80.6 96.2 112.7 117.3 121.1 124.9 128.8 132.7 136.6 140.6 144.6 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 37.1 17.9 1.9 38.4 18.5 2.3 62.4 43.3 20.9 40.3 19.3 2.9 74.4 45.1 21.7 42.6 20.4 3.6 89.0 47.3 22.8 45.1 21.5 4.3 104.7 49.8 24.0 45.8 21.9 4.5 109.2 50.5 24.3 46.4 22.2 4.7 112.8 51.0 24.6 47.0 22.5 4.9 116.5 51.6 24.9 47.6 22.8 5.1 120.2 52.2 25.3 48.2 23.1 5.3 124.0 52.8 25.6 48.8 23.4 5.4 127.8 53.4 25.9 49.4 23.7 5.6 50.0 23.9 5.8 LP (bar) 1.9 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.3 5.5 5.7 5.9 Cap (kW) 45 °C P.I. HP (kW) (bar) 63.4 76.2 90.2 42.5 44.2 46.3 LP (bar) Cap (kW) 45 °C P.I. HP (kW) (bar) 81.4 52.7 23.7 24.7 25.8 LP (bar) 2.9 3.6 4.3 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 62.2 74.8 73.4 43.5 45.2 46.3 Table 49 - Cooling capacities CXAN 490 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 64.8 76.0 91.6 109.3 127.3 132.3 136.4 140.5 144.7 149.0 153.2 157.5 161.8 25 P.I. (kW) 29.6 30.9 32.7 34.8 37.1 37.8 38.4 39.0 39.5 40.1 40.8 41.4 42.0 °C HP (bar) 13.7 14.3 15.2 16.2 17.3 17.6 17.9 18.2 18.4 18.7 19.0 19.3 19.6 LP (bar) 1.8 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.0 5.2 5.4 5.6 5.8 Cap (kW) 61.5 71.9 86.3 103.0 120.2 125.0 128.9 132.9 136.9 141.0 145.1 149.2 153.4 30 P.I. (kW) 33.0 34.3 36.2 38.4 40.9 41.6 42.1 42.7 43.3 44.0 44.6 45.2 45.9 °C HP (bar) 15.7 16.3 17.1 18.2 19.3 19.6 19.9 20.2 20.5 20.8 21.1 21.4 21.7 LP (bar) 1.9 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.2 5.4 5.6 5.8 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° 2.3 2.9 3.6 4.3 4.5 4.7 4.9 5.1 5.3 5.5 25.5 LP (bar) 3.6 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 37 Cooling performance - Super Quiet version R407C Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 38 Table 50 - Cooling capacities CXAN 500 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. °C HP (bar) 14.1 14.8 15.5 16.4 17.3 17.6 17.9 18.1 18.4 18.6 18.9 19.2 19.5 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.7 4.9 5.1 5.2 5.4 Cap (kW) 65.9 78.0 91.3 105.6 121.0 125.4 129.3 133.2 137.2 141.1 145.2 149.2 153.3 30 P.I. (kW) 34.8 36.3 37.9 39.7 41.7 42.3 42.8 43.3 43.9 44.4 45.0 45.5 46.1 °C HP (bar) 16.1 16.8 17.6 18.5 19.5 19.8 20.1 20.3 20.6 20.9 21.2 21.4 21.7 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 5.3 5.5 Cap (kW) 62.1 73.4 86.0 99.5 114.0 118.2 121.8 125.5 129.2 133.0 136.8 140.6 144.4 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 39.2 18.4 2.0 40.7 19.1 2.4 68.6 45.9 21.7 42.5 20.0 3.0 80.3 47.8 22.6 44.4 20.9 3.5 93.0 49.9 23.5 46.6 21.9 4.1 106.5 52.2 24.6 47.2 22.2 4.3 110.4 52.8 24.9 47.8 22.5 4.5 113.8 53.4 25.2 48.4 22.8 4.6 117.3 54.0 25.5 48.9 23.1 4.8 120.8 54.6 25.8 49.5 23.3 5.0 50.1 23.6 5.1 50.7 23.9 5.3 51.3 24.2 5.5 Cap (kW) 75.0 88.8 104.1 120.7 138.5 143.5 148.0 152.5 157.1 161.7 166.4 171.1 175.8 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 46.4 18.2 2.0 48.3 18.9 2.4 83.4 54.1 21.4 50.3 19.7 2.9 97.7 56.2 22.2 52.5 20.5 3.5 113.2 58.6 23.1 55.0 21.5 4.1 129.9 61.2 24.1 55.7 21.8 4.3 134.7 62.0 24.4 56.4 22.1 4.4 138.9 62.6 24.6 57.0 22.3 4.6 143.1 63.3 24.9 57.7 22.6 4.7 147.4 64.0 25.2 58.4 22.8 4.9 151.8 64.7 25.4 59.1 23.1 5.1 156.1 65.4 25.7 59.8 23.4 5.2 60.5 23.7 5.4 LP (bar) Cap (kW) 45 °C P.I. HP (kW) (bar) LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) Cap (kW) 45 °C P.I. HP (kW) (bar) LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 90.8 105.3 62.9 65.4 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 Table 51 - Cooling capacities CXAN 600 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 83.7 99.0 115.9 134.2 154.0 159.6 164.6 169.6 174.7 179.9 185.0 190.2 195.5 25 P.I. (kW) 37.3 38.9 40.6 42.5 44.7 45.3 45.9 46.5 47.1 47.7 48.3 49.0 49.6 °C HP (bar) 14.0 14.6 15.4 16.2 17.1 17.4 17.6 17.9 18.1 18.4 18.6 18.9 19.2 LP (bar) 2.0 2.4 2.9 3.4 4.0 4.2 4.4 4.5 4.7 4.8 5.0 5.2 5.3 Cap (kW) 79.4 94.0 110.2 127.7 146.5 151.8 156.6 161.4 166.2 171.1 176.0 181.0 186.0 30 P.I. (kW) 41.5 43.2 45.1 47.2 49.5 50.2 50.8 51.4 52.1 52.7 53.4 54.0 54.7 °C HP (bar) 16.0 16.6 17.4 18.3 19.2 19.5 19.7 20.0 20.2 20.5 20.8 21.0 21.3 LP (bar) 2.0 2.4 2.9 3.5 4.1 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.4 2.9 3.5 4.1 4.3 4.4 4.6 4.8 4.9 5.1 24.9 25.9 3.0 3.5 89.4 64.4 CG-PRC010-E4 Cooling performance - Super Quiet version R407C -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 69.5 82.2 96.2 111.3 127.5 132.2 136.3 140.4 144.5 148.7 153.0 157.3 161.5 25 P.I. (kW) 31.2 32.5 33.9 35.6 37.4 37.9 38.4 38.9 39.4 39.9 40.4 41.0 41.5 CG-PRC010-E4 Table 52 - Cooling capacities CXAN 700 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. °C HP (bar) 13.9 14.5 15.2 16.0 16.9 17.1 17.3 17.6 17.8 18.1 18.3 18.6 18.8 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.3 5.5 Cap (kW) 86.9 103.0 120.7 139.9 160.6 166.5 171.8 177.1 182.4 187.8 193.3 198.8 204.3 30 P.I. (kW) 48.1 49.9 52.0 54.3 56.8 57.6 58.2 58.9 59.6 60.3 61.0 61.8 62.5 °C HP (bar) 15.9 16.5 17.3 18.1 19.0 19.3 19.5 19.8 20.0 20.3 20.6 20.8 21.1 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 Cap (kW) 81.7 96.9 113.6 131.8 151.3 156.9 161.8 166.8 171.9 177.0 182.2 187.4 192.6 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 54.1 18.1 2.0 56.2 18.8 2.5 90.3 63.4 21.4 58.4 19.6 3.0 106.0 65.9 22.2 61.0 20.5 3.6 123.0 68.6 23.1 63.7 21.4 4.2 141.3 71.6 24.1 64.5 21.7 4.4 146.5 72.4 24.4 65.2 22.0 4.5 151.2 73.2 24.6 66.0 22.2 4.7 155.9 73.9 24.9 66.7 22.5 4.9 160.6 74.7 25.2 67.5 22.7 5.0 165.4 75.5 25.4 68.2 23.0 5.2 170.2 76.3 25.7 69.0 23.3 5.4 69.8 23.6 5.6 Cap (kW) 94.2 111.9 131.4 152.7 175.8 182.3 188.2 194.1 200.1 206.2 212.3 218.5 224.7 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 60.6 17.7 2.0 62.7 18.3 2.5 104.8 70.5 20.8 65.1 19.0 3.0 123.2 73.0 21.5 67.6 19.8 3.5 143.2 75.7 22.3 70.5 20.7 4.2 164.9 78.7 23.2 71.3 20.9 4.3 171.1 79.6 23.4 72.0 21.1 4.5 176.6 80.3 23.7 72.7 21.3 4.7 182.2 81.1 23.9 73.5 21.6 4.8 187.9 81.9 24.1 74.3 21.8 5.0 193.6 82.7 24.4 75.0 22.0 5.2 199.4 83.5 24.6 75.8 22.3 5.3 205.2 84.3 24.9 76.6 22.5 5.5 211.1 85.2 25.1 LP (bar) 2.5 3.0 3.6 4.2 4.4 4.6 4.7 4.9 5.1 5.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 113.6 77.2 Cap (kW) 45 °C P.I. HP (kW) (bar) 133.1 153.3 84.8 88.0 26.0 LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 3.6 Table 53 - Cooling capacities CXAN 800 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 105.3 124.9 146.5 170.0 195.4 202.7 209.1 215.7 222.3 229.0 235.8 242.6 249.5 25 P.I. (kW) 48.6 50.4 52.4 54.5 56.9 57.6 58.3 58.9 59.6 60.2 60.9 61.6 62.3 °C HP (bar) 13.6 14.2 14.8 15.5 16.3 16.5 16.8 17.0 17.2 17.4 17.6 17.9 18.1 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 4.9 5.1 5.3 5.5 Cap (kW) 99.9 118.5 139.2 161.6 185.9 192.8 199.0 205.3 211.6 218.0 224.4 230.9 237.5 30 P.I. (kW) 54.1 56.1 58.2 60.6 63.2 64.0 64.7 65.4 66.1 66.8 67.5 68.3 69.0 °C HP (bar) 15.6 16.1 16.8 17.5 18.4 18.6 18.8 19.0 19.3 19.5 19.7 20.0 20.2 LP (bar) 2.0 2.5 3.0 3.5 4.1 4.3 4.5 4.6 4.8 5.0 5.1 5.3 5.5 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.5 3.0 3.6 4.2 4.4 4.5 4.7 4.9 5.0 5.2 5.4 5.6 25.1 26.0 LP (bar) 3.6 4.2 130.9 86.8 39 Cooling performance - Super Quiet version R407C -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 91.7 108.6 127.3 147.5 169.3 175.5 181.0 186.6 192.2 197.9 203.7 209.5 215.3 25 P.I. (kW) 43.0 44.7 46.5 48.6 50.9 51.6 52.2 52.8 53.4 54.1 54.7 55.4 56.1 40 Table 54 - Cooling capacities CXAN 900 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. °C HP (bar) 13.9 14.5 15.2 16.1 17.0 17.2 17.5 17.7 18.0 18.2 18.5 18.7 19.0 LP (bar) 2.0 2.5 3.0 3.5 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.3 5.5 Cap (kW) 113.4 134.6 158.0 183.3 210.5 218.2 225.1 232.1 239.2 246.3 253.5 260.7 268.0 30 P.I. (kW) 61.9 64.4 67.2 70.3 73.8 74.8 75.7 76.6 77.5 78.5 79.5 80.5 81.5 °C HP (bar) 15.9 16.5 17.3 18.1 19.1 19.3 19.6 19.8 20.1 20.3 20.6 20.9 21.2 LP (bar) 2.0 2.5 3.0 3.6 4.2 4.3 4.5 4.7 4.8 5.0 5.2 5.4 5.5 Cap (kW) 107.0 127.0 149.2 173.1 198.8 206.1 212.6 219.2 225.9 232.6 239.4 246.3 253.2 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 69.3 18.1 2.0 72.0 18.7 2.5 119.1 80.7 21.2 75.0 19.5 3.0 139.8 83.9 22.0 78.3 20.4 3.6 162.3 87.5 22.9 82.0 21.4 4.2 186.4 91.3 23.9 83.1 21.6 4.4 193.2 92.4 24.2 84.0 21.9 4.5 199.3 93.4 24.5 85.0 22.2 4.7 205.5 94.4 24.7 86.0 22.4 4.9 211.8 95.5 25.0 87.0 22.7 5.0 218.1 96.5 25.3 88.0 23.0 5.2 224.5 97.6 25.6 89.1 23.2 5.4 230.9 98.7 25.8 90.1 23.5 5.6 Cap (kW) 123.4 145.8 170.5 197.4 226.6 234.9 242.4 250.0 257.8 265.7 273.7 281.9 290.1 Outdoor Ambient Temperature 35 °C 40 °C P.I. HP LP Cap P.I. HP (kW) (bar) (bar) (kW) (kW) (bar) 76.6 18.1 2.1 79.8 18.8 2.6 134.6 89.7 21.3 83.4 19.7 3.1 157.8 93.2 22.1 87.5 20.6 3.8 183.2 97.2 23.0 92.0 21.6 4.4 210.8 101.6 24.1 93.3 21.9 4.6 218.6 102.8 24.4 94.5 22.2 4.8 225.8 103.9 24.7 95.7 22.5 5.0 233.1 105.1 25.0 96.9 22.8 5.2 240.6 106.3 25.3 98.2 23.1 5.4 248.1 107.5 25.6 99.5 23.4 5.6 255.8 108.7 25.9 100.7 23.7 5.8 102.1 24.1 6.0 LP (bar) 2.5 3.0 3.6 4.2 4.4 4.6 4.7 4.9 5.1 5.2 5.4 Cap (kW) 45 °C P.I. HP (kW) (bar) 150.7 97.7 Cap (kW) 45 °C P.I. HP (kW) (bar) 25.7 LP (bar) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 46 °C Cap P.I. (kW) (kW) 47 °C Cap P.I. (kW) (kW) 3.6 Table 55 - Cooling capacities CXAN 925 Super Quiet version % Ethylen Glycol 0.37 0.33 0.27 0.2 0.1 Leaving Chilled Water Temp. -12 °C -8 °C -4 °C 0 °C 4 °C 5 °C 6 °C 7 °C 8 °C 9 °C 10 °C 11 °C 12 °C Cap (kW) 140.1 165.4 193.2 223.4 255.9 265.1 273.4 281.8 290.3 298.9 307.7 316.6 325.6 25 P.I. (kW) 61.5 64.4 67.7 71.5 75.8 77.1 78.3 79.5 80.7 82.0 83.3 84.6 85.9 °C HP (bar) 14.0 14.7 15.5 16.4 17.4 17.7 17.9 18.2 18.5 18.8 19.1 19.4 19.7 LP (bar) 2.1 2.6 3.1 3.7 4.4 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 Cap (kW) 132.1 156.0 182.3 210.8 241.6 250.3 258.2 266.2 274.4 282.6 291.0 299.5 308.1 30 P.I. (kW) 68.3 71.4 74.9 78.9 83.4 84.7 85.9 87.1 88.4 89.7 91.0 92.3 93.6 °C HP (bar) 16.0 16.7 17.5 18.4 19.4 19.7 20.0 20.3 20.5 20.8 21.1 21.4 21.8 LP (bar) 2.1 2.6 3.1 3.8 4.4 4.6 4.8 5.0 5.2 5.4 5.6 5.8 6.0 Cap = Total Capacity P.I. = Compressor Power Input HP = High Pressure gauge LP = Low Pressure gauge Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° LP (bar) 2.6 3.2 3.8 4.5 4.7 4.8 5.0 5.2 5.4 5.6 168.0 108.0 25.7 LP (bar) 3.8 CG-PRC010-E4 Cooling performance - Super Quiet version R407C -12 -8 -4 0 4 5 6 7 8 9 10 11 12 Cap (kW) 119.7 141.8 166.3 192.9 221.5 229.6 236.9 244.2 251.6 259.1 266.7 274.3 282.0 25 P.I. (kW) 55.7 58.0 60.5 63.4 66.6 67.5 68.4 69.2 70.1 71.0 72.0 72.9 73.9 Heating performance - Standard version and Super Quiet version R407C Table 56 - Heating capacities CXAN 200 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -7 -4 0 4 7 10 14 18 25°C Cap (kW) 30.0 32.5 35.3 39.6 43.9 47.7 51.9 58.0 64.7 30°C P.I. (kW) 10.9 11.0 11.0 11.1 11.1 11.1 11.2 11.2 11.2 Cap (kW) 30.1 32.5 27.0 39.5 43.7 47.5 51.6 57.6 64.2 P.I. (kW) 12.3 12.3 12.3 12.4 12.4 12.4 12.4 12.4 12.4 Cap (kW) 30.2 32.5 35.2 39.3 43.5 47.2 51.3 57.2 138.0 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 13.8 13.9 32.6 13.9 35.2 13.9 39.2 13.9 43.3 13.9 46.9 13.9 50.9 13.8 56.8 13.8 63.2 45°C 50°C P.I. (kW) Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 15.5 15.5 15.5 15.5 15.4 15.4 15.4 15.3 35.2 39.1 43.1 46.6 50.5 56.2 62.6 17.4 17.4 17.4 17.3 17.3 17.2 17.2 39.0 42.9 46.3 50.2 55.8 62.0 19.5 19.5 19.4 19.4 19.3 19.2 P.I. (kW) Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 19.3 19.3 19.4 19.5 19.5 19.6 19.6 19.7 43.8 48.5 53.5 57.8 62.6 69.6 77.4 21.5 21.6 21.7 21.7 21.8 21.8 21.9 48.5 53.3 57.5 62.2 68.9 76.5 24.0 24.2 24.2 24.3 24.3 24.4 P.I. (kW) Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 22.9 23.0 23.1 23.3 23.4 23.5 23.6 23.7 59.3 65.2 70.5 76.3 84.7 94.0 25.6 25.8 25.9 26.0 26.1 26.3 59.3 65.0 70.1 75.6 83.7 92.7 28.5 28.6 28.7 28.8 28.9 29.1 Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 67.4 72.7 80.6 88.9 96.3 104 116 129 34.2 34.4 34.5 34.7 34.9 35.0 35.1 35.3 80.5 88.5 95.6 103 115 127 38.3 38.5 38.6 38.7 38.9 39.1 Table 57 - Heating capacities CXAN 250 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 37.0 40.0 43.6 48.9 54.4 59.2 64.5 72.2 80.8 30°C P.I. (kW) 14.0 14.0 14.1 14.2 14.3 14.4 14.5 14.6 14.7 Cap (kW) 37.0 40.1 43.5 48.8 54.1 58.8 64.0 71.6 79.9 P.I. (kW) 15.4 15.5 15.6 15.8 15.8 15.9 16.0 16.1 16.2 Cap (kW) 37.3 40.2 43.5 48.6 53.8 58.4 63.5 70.9 79.1 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 17.2 17.3 40.4 17.3 43.6 17.4 48.5 17.5 53.6 17.5 58.1 17.6 63.0 17.7 70.2 17.9 78.2 45°C 50°C Table 58 - Heating capacities CXAN 300 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 45.3 49.1 53.6 60.2 67.0 72.9 79.4 89.0 99 30°C P.I. (kW) 16.8 16.9 17.0 17.1 17.2 17.3 17.4 17.6 17.7 Cap (kW) 45.3 49.1 40.8 59.8 66.4 72.2 78.5 87.8 98 P.I. (kW) 18.6 18.7 18.8 18.9 19.0 19.1 19.2 19.3 19.4 Cap (kW) 45.5 49.1 53.3 59.5 65.9 71.5 77.7 86.7 165.2 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 20.6 20.7 49.3 20.8 53.3 20.9 59.3 21.0 65.5 21.1 71.0 21.2 77.0 21.3 85.7 21.4 95.3 45°C 50°C Table 59 - Heating capacities CXAN 400 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 61.6 66.8 72.9 82.0 91.3 100 108 121 136 30°C P.I. (kW) 22.4 22.6 22.7 22.9 23.1 23.3 23.4 23.6 23.8 Cap (kW) 61.7 66.7 55.7 81.5 90.5 99 107 120 134 P.I. (kW) 24.9 25.0 25.1 25.3 25.4 25.6 25.7 25.9 26.1 Cap (kW) 61.9 66.8 72.4 81.1 89.9 98 106 119 195 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 27.6 62.3 27.7 67.0 27.8 72.5 28.0 80.8 28.1 89.4 28.2 97 28.5 105 28.7 117 28.8 131 45°C P.I. (kW) 30.7 30.8 31.0 31.1 31.3 31.4 31.5 31.7 31.8 50°C Cap = Total Capacity P.I. = Compressor Power Input Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° CG-PRC010-E4 41 Heating performance - Standard version and Super Quiet version R407C Table 60 - Heating capacities CXAN 450 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 74.3 63.2 88.1 99.2 110.5 120.4 131.2 147.2 164.7 30°C P.I. (kW) 25.2 25.4 25.5 25.7 25.9 26.0 26.1 26.4 26.6 Cap (kW) 74.2 80.4 87.6 99.9 111.0 119.0 131.2 145.1 163.9 P.I. (kW) 27.9 28.0 28.2 28.4 28.6 28.7 28.8 29.0 29.2 Cap (kW) 74.4 80.3 87.2 97.6 108.3 117.8 128.0 143.1 159.7 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 31.0 74.7 31.1 80.3 31.2 87.0 31.4 97.1 31.6 107.4 31.7 116.6 31.8 126.5 32.0 141.1 32.1 157.3 45°C P.I. (kW) 34.3 34.4 34.5 34.8 35.0 35.1 35.2 35.4 35.6 50°C Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 80.6 87.0 96.7 106.6 115.5 125.0 139.2 154.8 38.1 38.3 38.5 38.7 38.9 39.0 39.2 39.4 96.4 105.9 114.5 123.7 137.3 152.3 42.6 42.8 43.1 43.2 43.4 43.6 Table 61- Heating capacities CXAN 490 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 80.0 68.1 94.4 106.2 118.3 129.1 140.9 158.4 177.8 30°C P.I. (kW) 27.1 27.0 26.9 27.0 27.2 27.5 28.0 28.7 29.6 Cap (kW) 80.1 86.5 93.9 107.1 118.8 127.5 140.8 156.0 176.9 P.I. (kW) 30.5 30.4 30.2 30.2 30.3 30.5 30.8 31.5 32.2 Cap (kW) 80.6 86.5 93.7 104.7 116.0 126.1 137.3 153.8 172.2 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 34.5 81.2 34.2 86.8 34.1 93.7 34.0 104.1 34.0 115.1 34.1 124.9 34.4 135.6 34.8 151.7 35.5 169.5 45°C 50°C P.I. (kW) 38.8 38.4 38.2 38.0 38.0 38.1 38.2 38.7 39.2 Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 93.8 103.9 114.3 123.8 134.1 149.6 166.9 42.9 42.7 42.6 42.6 42.7 43.1 43.5 103.6 113.7 122.8 132.8 147.7 164.4 47.8 47.7 47.7 47.8 48.0 48.4 P.I. (kW) Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 38.6 38.6 38.9 39.1 39.1 39.3 39.3 39.5 87.5 97 107 116 125 139 155 43.1 43.3 43.5 43.5 43.7 43.7 43.9 97 107 115 124 138 153 48.1 48.3 48.3 48.5 48.5 48.7 Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 99 107 119 130 141 153 169 188 50.8 51.0 51.2 51.7 51.9 52.1 52.3 52.5 119 130 140 151 167 185 56.9 57.1 57.3 57.5 57.8 58.2 Table 62 - Heating capacities CXAN 500 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 74.0 80.0 87.2 98 109 118 129 144 162 30°C P.I. (kW) 27.9 27.9 28.1 28.4 28.6 28.8 29.0 29.2 29.4 Cap (kW) 74.1 80.1 87.1 98 108 118 128 143 160 P.I. (kW) 30.9 31.1 31.3 31.5 31.5 31.7 31.9 32.1 32.3 Cap (kW) 74.5 80.4 87.0 97 108 117 127 142 158 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 34.4 34.7 80.8 34.7 87.2 34.9 97 35.1 107 35.1 116 35.3 126 35.5 140 35.7 156 45°C 50°C Table 63 - Heating capacities CXAN 600 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 90.6 98 107 120 134 146 159 178 199 30°C P.I. (kW) 33.6 33.8 34.0 34.2 34.4 34.7 34.9 35.3 35.5 Cap (kW) 90.7 98 82 120 133 144 157 176 196 P.I. (kW) 37.2 37.4 37.6 37.8 38.0 38.2 38.4 38.6 38.9 Cap (kW) 91.1 98 107 119 132 143 155 173 330 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 41.2 91.7 41.4 99 41.6 107 41.8 119 42.0 131 42.2 142 42.4 154 42.6 171 42.8 191 45°C P.I. (kW) 45.6 45.8 46.0 46.2 46.6 46.8 47.0 47.3 47.5 50°C Cap = Total Capacity P.I. = Compressor Power Input Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° 42 CG-PRC010-E4 Heating performance - Standard version and Super Quiet version R407C Table 64 - Heating capacities CXAN 700 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 109 118 129 145 161 176 192 215 240 30°C P.I. (kW) 38.9 39.1 39.3 39.7 39.9 40.1 40.3 40.5 41.0 Cap (kW) 109 118 99 144 160 175 190 213 238 P.I. (kW) 43.3 43.5 43.7 43.9 44.1 44.3 44.3 44.5 44.9 Cap (kW) 109 118 128 143 159 173 188 211 367 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 48.3 108 48.5 116 48.5 125 48.7 140 48.9 154 49.1 168 49.1 182 49.4 203 49.6 227 45°C 50°C P.I. (kW) 54.0 54.2 54.2 54.4 54.4 54.6 54.6 54.8 54.8 Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 126 139 154 167 181 201 224 60.7 60.7 60.9 60.9 60.9 60.9 61.1 139 153 166 179 199 222 67.8 67.8 67.8 67.8 67.8 67.8 P.I. (kW) 61.3 61.5 62.0 62.2 62.6 62.8 63.0 63.4 63.6 Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 135 145 161 178 193 209 232 258 68.5 68.9 69.1 69.3 69.7 69.9 70.1 70.6 161 177 191 207 229 254 76.7 77.1 77.3 77.5 77.7 78.1 P.I. (kW) 68.5 68.7 69.1 69.3 69.7 69.9 70.4 70.6 71.0 Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 162 180 198 214 231 256 284 76.4 76.9 77.3 77.5 77.9 78.1 78.5 180 197 212 229 253 280 85.3 85.5 85.9 86.1 86.5 86.9 P.I. (kW) 77.5 76.9 76.5 76.0 76.0 76.3 76.5 77.3 78.4 Cap (kW) P.I. (kW) Cap (kW) P.I. (kW) 191 211 233 252 273 304 339 85.9 85.5 85.3 85.3 85.5 86.1 87.0 211 231 250 270 300 334 95.5 95.3 95.3 95.5 96.0 96.8 Table 65 - Heating capacities CXAN 800 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 123 134 146 164 183 199 217 243 271 30°C P.I. (kW) 44.7 45.2 45.4 45.8 46.2 46.6 46.8 47.3 47.7 Cap (kW) 123 133 111 163 181 197 215 240 268 P.I. (kW) 49.8 50.0 50.2 50.6 50.8 51.2 51.5 51.9 52.3 Cap (kW) 124 134 145 162 180 195 213 237 391 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 55.2 125 55.4 134 55.7 145 56.1 162 56.3 179 56.5 194 56.9 210 57.3 235 57.5 261 45°C 50°C Table 66 - Heating capacities CXAN 900 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 138 149 163 183 203 221 241 269 301 30°C P.I. (kW) 50.4 50.6 51.0 51.2 51.7 51.9 52.3 52.5 52.9 Cap (kW) 138 149 124 182 201 219 238 266 296 P.I. (kW) 55.7 55.9 56.3 56.7 56.9 57.1 57.5 57.8 58.2 Cap (kW) 138 149 161 180 200 217 235 263 414 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 61.7 139 62.0 149 62.2 162 62.6 180 63.0 199 63.2 215 63.4 233 63.8 259 64.1 288 45°C 50°C Table 67 - Heating capacities CXAN 925 Standard and Super Quiet version Air temp-dew bulb=90% RH (°C) -10 -7 -4 0 4 7 10 14 18 25°C Cap (kW) 163 138 192 216 241 263 287 322 362 30°C P.I. (kW) 54.2 54.0 53.8 54.0 54.4 55.0 55.9 57.4 59.1 Cap (kW) 163 176 191 218 242 259 286 317 360 P.I. (kW) 61.0 60.8 60.4 60.4 60.6 61.0 61.7 63.0 64.5 Cap (kW) 164 176 191 213 236 256 279 313 350 Leaving Hot Water Temp. 35°C 40°C P.I. Cap (kW) (kW) 69.0 165 68.3 177 68.1 190 67.9 212 67.9 234 68.1 254 68.8 276 69.6 308 70.9 345 45°C 50°C Cap = Total Capacity P.I. = Compressor Power Input Waterflow (l/s) = Cap/(4.18 x ∆t), With ∆t = Entering - Leaving Water Temperature (°C) and Cap (kW) Delta t = 5° CG-PRC010-E4 43 Water side performance Table 68 - Water pressure drop at nominal waterflow rate (Without Hydraulic module option) Min. Waterflow rate - 0% EG Min. Waterflow rate - 30% EG Nom. Waterflow rate Pressure drop nominal (l/s) (l/s) (l/s) (kPa) CGAN CXAN 200 0.48 0.86 2.43 29 CGAN CXAN 250 0.48 0.86 2.99 33 CGAN CXAN 300 0.87 1.57 3.64 38 CGAN CXAN 400 0.87 1.57 4.92 46 CGAN CXAN 450 0.87 1.57 5.83 43 CGAN CXAN 490 0.87 1.57 6.33 45 CGAN CXAN 500 1.23 2.21 6.17 30 CGAN CXAN 600 1.23 2.21 7.52 36 CGAN CXAN 700 2.23 4.02 8.75 30 CGAN CXAN 800 2.23 4.02 10.25 35 CGAN CXAN 900 2.23 4.02 11.55 35 CGAN CXAN 925 2.23 4.02 12.78 42 CGAN CXAN 450 2.73 3.90 5.59 6.90 8.01 8.99 CGAN CXAN 490 2.91 4.15 5.93 7.30 8.46 9.48 CGAN CXAN 500 3.52 5.04 7.20 8.88 10.30 11.56 CGAN CXAN 600 3.86 5.52 7.90 9.74 11.31 12.69 CGAN CXAN 700 4.98 7.14 10.25 12.65 14.70 16.50 CGAN CXAN 800 5.37 7.71 11.07 13.67 15.89 17.85 CGAN CXAN 900 6.00 8.63 12.41 15.35 17.85 20.06 CGAN CXAN 925 6.00 8.63 12.41 15.35 17.85 20.06 Table 69 - Water pressure drop (Without Hydraulic module option) CGAN CXAN 200 1.37 1.99 2.87 3.56 4.15 4.68 ∆P kPa 10 20 40 60 80 100 CGAN CXAN 250 1.60 2.30 3.33 4.12 4.80 5.40 CGAN CXAN 300 1.82 2.61 3.75 4.64 5.39 6.06 CGAN CXAN 400 2.24 3.20 4.57 5.63 6.53 7.33 Table 70 - Available pressure at unit connection (With Hydraulic module option) CGAN CXAN 200 Water flow rate l/s 1.45 1.69 2.18 2.42 2.66 3.15 3.39 3.87 CGAN CXAN 250 Available pressure 1P kPa 224 218 205 195 185 164 152 127 2P kPa 202 197 186 179 171 149 137 111 Water flow rate CGAN CXAN 300 Available pressure 1P kPa 219 212 191 180 168 141 126 90 l/s 1.79 2.09 2.68 2.98 3.28 3.87 4.17 4.77 2P kPa 199 193 177 166 154 126 109 71 Water flow rate l/s 2.18 2.54 3.27 3.63 3.99 4.72 5.08 5.81 CGAN CXAN 400 Available pressure 1P kPa 217 207 185 174 160 128 110 67 2P kPa 198 191 171 158 144 110 91 48 Water flow rate l/s 2.95 3.44 4.43 4.92 5.41 6.40 6.89 7.87 CGAN CXAN 450 Available pressure 1P kPa 203 191 160 139 116 64 34 - 2P kPa 189 176 142 121 97 44 16 - Water flow rate l/s 3.33 3.89 5.00 5.55 6.11 7.22 7.77 8.88 CGAN CXAN 490 Available pressure 1P kPa 240 232 213 201 188 159 140 100 2P kPa 231 221 200 187 173 141 122 79 Water flow rate l/s 3.62 4.22 5.43 6.03 6.63 7.84 8.44 9.65 Available pressure 1P kPa 235 225 200 186 170 130 108 58 2P kPa 225 213 186 171 154 111 87 34 Table 70 (continued) CGAN CXAN 500 Water flow rate L/s 3.68 4.30 5.53 6.14 6.75 7.98 8.60 9.82 CGAN CXAN 600 Available pressure 1P* Kpa 242 235 217 207 195 166 149 113 2P* Kpa 231 223 203 191 179 147 129 89 Water flow rate L/s 4.49 5.24 6.74 7.49 8.24 9.74 10.49 11.98 CGAN CXAN 700 Available pressure 1P* Kpa 235 225 201 186 168 128 103 50 2P* Kpa 222 211 185 168 148 104 77 18 Water flow rate L/s 5.23 6.10 7.84 8.71 9.58 11.32 12.19 13.94 CGAN CXAN 800 Available pressure 1P* Kpa 240 233 211 197 182 143 121 71 2P* Kpa 227 218 192 176 159 113 88 32 Water flow rate L/s 6.15 7.18 9.23 10.25 11.28 13.33 14.35 16.40 CGAN CXAN 900 Available pressure 1P* Kpa 234 224 193 174 151 98 67 - 2P* Kpa 219 207 171 148 121 62 28 - Water flow rate L/s 6.93 8.09 10.40 11.55 12.71 15.02 16.17 18.48 CGAN CXAN 925 Available pressure 1P* Kpa 181 172 150 137 122 86 64 16 2P* Kpa 182 173 151 137 121 81 59 9 Water flow rate L/s 7.49 8.74 11.24 12.49 13.74 16.24 17.49 19.98 Available pressure 1P* Kpa 177 167 141 125 107 63 38 - 2P* Kpa 178 168 141 124 103 57 31 - 1P = Single pump - 2P = Dual pump 44 CG-PRC010-E4 Water side performance Figure 2 - CGAN/CXAN 200 - 400 pump curve 30 25 20 Hm 1 15 2 10 5 0 0 5 10 15 m3/h 20 25 30 1. Single pump 2. Dual pump Figure 3 - CGAN/CXAN 450 - 800 pump curve 30 25 Hm 20 1 15 2 10 5 0 0 10 20 30 40 50 60 70 m3/h 1. Single pump 2. Dual pump CG-PRC010-E4 45 Water side performance Figure 4 - CGAN/CXAN 900 - 925 pump curve 25 20 1 2 Hm 15 10 5 0 0 10 20 30 40 50 60 70 80 m3/h 1. Single pump 2. Dual pump 46 CG-PRC010-E4 Notes CG-PRC010-E4 47 Safety recommendations Maintenance contract Training To avoid accidents and damage, the following recommendations should be observed during maintenance and service visits: 1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter “Installation”. Always provide a pressure regulator. 2. Disconnect the main supply before any servicing on the unit. 3. Service work on the refrigeration system and the electrical system should be carried out only by qualified and experienced personnel. It is strongly recommended that you sign a maintenance contract with your local Service Agency. This contract provides regular maintenance of your installation by a specialist in our equipment. Regular maintenance ensures that any malfunction is detected and corrected in good time and minimizes the possibility that serious damage will occur. Finally, regular maintenance ensures the maximum operating life of your equipment. We would remind you that failure to respect these installation and maintenance instructions may result in immediate cancellation of the warranty. The equipment described in this manual is the result of many years of research and continuous development. To assist you in obtaining the best use of it and maintaining it in perfect operating condition over a long period of time, the manufacturer has at your disposal a refrigeration and air conditioning service school. The principal aim of this is to give operators and technicians a better knowledge of the equipment they are using, or that is under their charge. Emphasis is particularly given to the importance of periodic checks on the unit operating parameters as well as on preventive maintenance, which reduces the cost of owning the unit by avoiding serious and costly breakdown. Literature Order Number CG-PRC010-E4 Date 0805 Supersedes CG-PRC010-E4_0204 Literature Stocking Location Europe Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice. www.trane.com For more information, contact your local sales office or e-mail us at [email protected] American Standard Europe BVBA Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium