Telechargé par Adel Ben

Weishaupt WM-L20

publicité
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
83252902 1/2019-09
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
1
User instructions .............................................................................................................. 4
1.1 Target group .................................................................................................................. 4
1.2 Symbols .......................................................................................................................... 4
1.3 Guarantee and Liability ............................................................................................... 5
2
Safety ..................................................................................................................................... 6
2.1 Designated application ...............................................................................................
2.2 Safety measures ...........................................................................................................
2.2.1 Normal operation ...................................................................................................
2.2.2 Electrical connection ............................................................................................
2.3 Alterations to the construction of the equipment .................................................
2.4 Noise emission .............................................................................................................
2.5 Disposal .........................................................................................................................
3
6
6
6
6
7
7
7
Product description ........................................................................................................ 8
3.1 Type key ......................................................................................................................... 8
3.2 Serial number ................................................................................................................ 8
3.3 Function .......................................................................................................................... 9
3.3.1 Air supply ................................................................................................................ 9
3.3.2 Oil supply ............................................................................................................. 10
3.3.3 Electrical components ....................................................................................... 12
3.4 Technical data ............................................................................................................. 13
3.4.1 Approval data ...................................................................................................... 13
3.4.2 Electrical data ..................................................................................................... 14
3.4.3 Ambient conditions ............................................................................................ 15
3.4.4 Fuels ...................................................................................................................... 15
3.4.5 Emissions ............................................................................................................. 15
3.4.6 Rating .................................................................................................................... 16
3.4.7 Dimensions .......................................................................................................... 17
3.4.8 Weight .................................................................................................................. 18
4
Installation ........................................................................................................................ 19
4.1 Installation conditions ................................................................................................
4.2 Check rating ................................................................................................................
4.3 Set mixing head ..........................................................................................................
4.3.1 Setting diagram ..................................................................................................
4.3.2 Set mixing head without combustion head extension ...............................
4.3.3 Set mixing head with combustion head extension .....................................
4.4 Burner installation ......................................................................................................
5
19
20
21
21
22
24
26
Installation ........................................................................................................................ 28
5.1 Oil supply ..................................................................................................................... 28
5.2 Electrical connection ................................................................................................. 30
6
83252902 1/2019-09 La
Operation .......................................................................................................................... 32
2-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7
Commissioning .............................................................................................................. 33
7.1 Prerequisite .................................................................................................................
7.1.1 Connect measuring devices ............................................................................
7.2 Adjusting the burner ..................................................................................................
7.3 Set oil pressure switch .............................................................................................
7.4 Concluding work ........................................................................................................
7.5 Check combustion .....................................................................................................
7.6 Ratings apportionment .............................................................................................
33
34
36
41
42
43
44
8
Shutdown .......................................................................................................................... 45
9
Servicing ............................................................................................................................ 46
9.1 Notes on servicing .....................................................................................................
9.2 Service plan .................................................................................................................
9.3 Hinge open the burner ..............................................................................................
9.4 Set ignition electrodes ..............................................................................................
9.5 Replace nozzle ............................................................................................................
9.6 Removing and refitting air damper actuator .........................................................
9.7 Removing air regulator ..............................................................................................
9.8 Set air regulator ..........................................................................................................
9.9 Removing and refitting oil quantity regulator actuator .......................................
9.10 Set pump coupling ..................................................................................................
9.11 Removing fan wheel ................................................................................................
10
Troubleshooting ............................................................................................................ 57
10.1 Procedures for fault conditions ............................................................................
10.1.1 Fault ....................................................................................................................
10.1.2 Lockout ..............................................................................................................
10.2 Rectifying faults ........................................................................................................
11
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
Technical documentation ......................................................................................... 62
11.1 Conversion table unit of pressure ........................................................................ 62
12
Project planning ............................................................................................................. 63
12.1 Oil supply ..................................................................................................................
12.1.1 Ring main operation ........................................................................................
12.1.2 Oil circulation unit ............................................................................................
12.2 Flue gas system .......................................................................................................
12.3 Additional requirements .........................................................................................
83252902 1/2019-09 La
63
64
64
64
65
13
Spares ................................................................................................................................. 66
14
Notes ................................................................................................................................... 80
15
Key word index .............................................................................................................. 81
3-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
1 User instructions
1 User instructions
Translation of original
operating instructions
This manual forms part of the equipment and must be kept on site.
Carefully read the manual prior to working on the unit.
It is supplemented by the installation and operating instructions for the Combustion
Manager.
1.1 Target group
The manual is intended for the operator and qualified personnel. It should be observed by all personnel working with the unit.
Work on the unit must only be carried out by personnel who have the relevant training and instruction.
Persons with limited physical, sensory or mental capabilities may only work on the
unit if they are supervised or have been trained by an authorised person.
Children must not play with the unit.
1.2 Symbols
Immediate danger with high risk.
Non observance can lead to serious injury or death.
DANGER
Danger with medium risk.
Non observance can lead to environmental damage,
serious injury or death.
WARNING
Danger with low risk.
Non observance can cause damage to the equipment and injury to personnel.
CAUTION
Important information
Requires direct action
Result after an action
Itemisation
Range of values
…
83252902 1/2019-09 La
4-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
1 User instructions
1.3 Guarantee and Liability
Guarantee and liability claims for personal and equipment damage are excluded, if
they can be attributed to one or more of the following causes:
non approved application,
non-observance of the manual,
operation with faulty safety equipment,
continual operation despite a fault,
improper installation, commissioning, operation and service,
repairs, which have been carried out incorrectly,
the use of non original Weishaupt parts,
force majeure,
unauthorised modifications made to the unit,
the installation of additional components, which have not been tested with the
unit,
the installation of combustion chamber inserts, which impede full flame formation,
unsuitable fuels,
defects in the inlet lines.
83252902 1/2019-09 La
5-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
2 Safety
2 Safety
2.1 Designated application
The burner is suitable for continuous operation (only in conjunction with QRI flame
sensor) on heat exchangers to EN 303 and EN 267.
If the burner is not used on combustion chambers to EN 303 and EN 267, a safety
assessment of combustion and flame stability during individual process conditions
and of the shutdown limits of the combustion plant has to be carried out and documented.
The combustion air must be free from aggressive compounds (e.g. Halogens). If the
combustion air in the boiler room is contaminated, increased cleaning and servicing
will be required. In this case ducted air intake is recommended.
The burner should only be used in enclosed rooms.
Improper use could:
endanger the health and safety of the user or third parties,
cause damage to the unit or other material assets.
2.2 Safety measures
Safety relevant fault conditions must be eliminated immediately.
Components, which show increased wear and tear or whose design lifespan is or
will be exceeded prior to the next service should be replaced as a precaution.
2.2.1 Normal operation
All labels on the unit must be kept in a legible condition.
Stipulated settings, service and inspection work should be carried out at regular
intervals.
Only operate the unit with its cover closed.
Do not touch moving parts during operation.
2.2.2 Electrical connection
For work carried out on live components:
Observe the accident prevention instructions DGUV Regulation 3 and adhere to
local directives,
tools in accordance with EN 60900 should be used.
83252902 1/2019-09 La
6-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
2 Safety
2.3 Alterations to the construction of the equipment
All conversions require written approval from Max Weishaupt GmbH.
No additional components may be fitted, which have not been tested for use
with the equipment.
Use only original Weishaupt replacement parts.
2.4 Noise emission
The noise emissions are determined by the acoustic behaviour of all components
fitted to the combustion system.
Prolonged exposure to high noise levels can lead to loss of hearing. Provide operating personnel with protective equipment.
Noise emissions can further be reduced with a sound attenuator.
2.5 Disposal
Dispose of all materials and components in a safe and environmentally friendly way
at an authorised location. Observe local regulations.
83252902 1/2019-09 La
7-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3 Product description
3.1 Type key
WM-L20/2-A R
Type
WM
L
20
2
A
Series: Monoblock monarch®
Fuel: Oil EL
Size
Ratings size
Construction
Version
R
Type of control: modulating
3.2 Serial number
The serial number on the name plate identifies the product. This is required by
Weishaupt's customer service department.
1
1 Name plate
Ser.No.
83252902 1/2019-09 La
8-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.3 Function
3.3.1 Air supply
Air dampers
The air dampers regulate the air quantity required for combustion. The combustion
manager controls the air dampers via actuator. At burner shutdown the air dampers
close automatically. At burner shutdown the air dampers close automatically.
Fan wheel
The fan wheel supplies the air from the air intake housing to the combustion head.
Flame tube
The air gap between flame tube and diffuser is adjusted by positioning the flame
tube. This adjusts the mixing pressure and the air quantity required for combustion.
83252902 1/2019-09 La
9-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.3.2 Oil supply
Oil pump
The pump draws the oil through the supply line and carries it under pressure to the
oil nozzle. The pressure regulating valve keeps the oil pressure constant.
Solenoid valves
The solenoid valves open and close the oil supply.
Oil quantity regulator
The oil quantity regulator is driven by the combustion manager via actuator. An oil
metering vee slot in the oil quantity regulator changes the spill back quantity of the
fuel and thus the atomised quantity of the oil at the oil nozzle. The oil quantity regulator has two metering slots. Each metering slot is matched with a specific oil
throughput. The identity code numbers on the shaft of the oil quantity regulator denote the oil throughput range.
1
2
Identity code
1
2
Factory setting see burner data sheet.
Oil throughput
up to 280 kg/h
greater than 280 kg/h
Maximum oil pressure switch
The maximum oil pressure switch monitors the pressure in the return. If the value
set is exceeded, the burner switches off.
Minimum oil pressure switch (optional)
Depending on the burner application, optional equipment may be required for optimum operation [ch. 12.3].
The minimum oil pressure switch monitors the pump pressure in the supply. If the
preset pressure is not achieved, the combustion manager initiates a lockout.
83252902 1/2019-09 La
10-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
Sequence of operation
During the pre-purge time all solenoid valves are closed. For burner ignition, the
combustion manager opens the solenoid valves.
The oil quantity regulator is in the open position (ignition position).
Due to the low resistance of the oil quantity regulator in the return only a small
quantity of oil is atomised at the nozzle, the larger quantity flows to the pump return.
If the load increases, the metering slot in the oil quantity regulator is reduces, this
reduces the oil flow in the return and thus increases the oil quantity at the nozzle
outlet.
1
3
2
4
P
P
5
1
2
3
4
5
6
7
7
M
6
5
Oil pump
Minimum oil pressure switch (optional)
Solenoid valve supply (fitted in flow direction)
Nozzle head with nozzle
Solenoid valve return (fitted against flow direction)
Oil quantity regulator
Max. oil pressure switch
One solenoid valve in the supply is always switched electrically in series with one
solenoid valve in the return. The voltage of the solenoid coil is therefore 115 V at
230 V / 50 Hz mains voltage.
83252902 1/2019-09 La
11-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.3.3 Electrical components
Combustion Manager
The combustion manager W-FM is the control unit of the burner.
It controls the sequence of operation, monitors the flame and communicates with all
components.
Display and operating unit (ABE)
The ABE is used to display and alter the operational values and parameters of the
combustion manager. It is connected by connection line and can be remove from
the burner.
Burner motor
The burner motor drives the fan wheel and the oil pump.
Without variable speed drive the combustion manager controls a contactor or star
delta switching.
With variable speed drive, a frequency converter is connected upstream.
Ignition unit
The electronic ignition unit creates a spark at the electrode, which ignites the fuel/
air mixture.
Flame sensor
The combustion manager monitors the flame signal via the flame sensor.
If the flame signal becomes too weak, the combustion manager carries out a controlled shutdown.
See installation and operating manual of the Combustion Manager W-FM for flame
signal required.
Limit switch
The limit switch in the housing prevents burner start in the open position.
83252902 1/2019-09 La
12-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.4 Technical data
3.4.1 Approval data
DIN CERTCO
5G1031
Basic standards
EN 267:2011
Additional standards, see EU conformity certification.
83252902 1/2019-09 La
13-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.4.2 Electrical data
Burner control
Mains voltage / mains frequency
Consumption at start
Consumption during operation
Power consumption
Internal unit fuse
External fuse
230 V/50 Hz
max 295 W
max 185 W
max 1.6 A
T6.3H, IEC 127-2/5
max 16 AB
Burner motor WM-D112/140-2/3K5
Efficiency [η]
87.7 % (at 100 % load)
88.8% (at 75 % load)
Type
Poles
Nominal load
Mains frequency
Mains voltage
Speed
Disposal
Design height
Ambient temperature
Coolant temperature
Operating temperature
Explosion protection
Consumption
Power consumption
External fuse direct start
87.4 % (at 50 % load)
IE3
see name plate
Max Weishaupt GmbH
Max-Weishaupt-Straße 14
88475 Schwendi
District Court Ulm HRB
640125
WM-D112/140-2/3K5
2
3.5 kW
50 Hz
380 … 415 V
2940 min-1 (rpm)
see Ch. 2.3 Disposal
1000 m
-15 … +40°C
–
max 40°C
–
max 4.1 kW
max 7.2 A
25 A
External fuse YΔ start
16 A
External fuse frequency converter mounted
20 A
External fuse frequency converter separate
16 A
Efficiency class
Year of manufacture
Manufacturer
83252902 1/2019-09 La
14-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.4.3 Ambient conditions
Temperature in operation
–10(1 … +40 °C
Temperature during transport / storage
–20 … +70 °C
relative humidity
max 80 %, no dew point
Installation elevation
max 2000 m(2
(1
With the relevant suitable fuel oil and layout of oil supply.
(2
Consultation with Weishaupt is required for higher installation elevation.
3.4.4 Fuels
Fuel oil EL to DIN 51603-1
Fuel oil EL A Bio 10 to DIN 51603-6
Fuel oil EL to ÖNORM-C1109 (Austria)
Fuel oil EL to SN 181 160-2 (Switzerland)
3.4.5 Emissions
Flue gas
To EN 267 the burner complies with emission class 2.
The NOx values are influenced by:
combustion chamber dimensions
flue gas system
fuel
combustion air (temperature and humidity)
medium temperature
Combustion chamber dimensions, see Weishaupt Partner Portal / Documents and
Applications / Online Applications / NOX calculation for burners.
Sound levels
Dual number noise emission values
Measured sound power level LWA (re 1 pW)
87 dB(A)(1
Uncertainty value KWA
Measured sound pressure level LpA (re 20 μPa)
4 dB(A)
80 dB(A)(2
Uncertainty value KpA
4 dB(A)
(1
Determined to ISO 9614-2.
(2
Determined at 1 metre distance from the front of the burner.
The measured noise levels plus uncertainty values form the upper limit value, which
could occur when measuring.
83252902 1/2019-09 La
15-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.4.6 Rating
Combustion heat rating
Combustion heat rating
600 … 2100 kW
50 … 176 kg/h(1
(1
The oil throughput data relates to a calorific value of 11.9 kWh/kg for fuel oil EL.
Capacity graph
Capacity graph to EN 267.
The capacity data given relates to an installation elevation of 500 m above sea
level. For installation elevations above 500 m a capacity reduction of
approx. 1 % per 100 m applies.
A limited capacity graph is valid for ducted air intake.
13
12
11
10
9
8
7
6
5
4
3
2
1
0
-1
2
-2
-3
500
700
50
900
70
1100
90
1300
110
1500
130
1
1 Combustion heat rating [kW] or [kg/h]
2 Combustion chamber pressure [mbar]
83252902 1/2019-09 La
16-84
1700
1900
150
2100
170
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
3.4.7 Dimensions
86
m
9m
8 mm
424 mm
198 mm
340 mm
84
0
209 mm
mm
409 mm
225 mm
408 mm
573 mm
220 mm
Burner
254 mm
1
810 mm
1 227 … 247 mm without combustion head extension
327 ± 3 mm with combustion head extension (100 mm)
427 ± 3 mm with combustion head extension (200 mm)
527 ± 3 mm with combustion head extension (300 mm)
83252902 1/2019-09 La
17-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
3 Product description
50 mm
165 mm
200 mm
Mixing head
3.4.8 Weight
approx. 96 kg
83252902 1/2019-09 La
18-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
4 Installation
4.1 Installation conditions
Burner type and capacity graph
Burner and heat exchanger must be matched.
Check burner type and burner capacity.
Installation location
Prior to installation ensure that:
the space for the burner hinging range is sufficient [ch. 3.4.7],
sufficient combustion air is available, if necessary install ducted air intake,
Prepare heat exchanger
The refractory 3 must not protrude beyond the front edge of the combustion head.
The refractory can take a conical shape (min 60°).
Refractory may not be required on boilers with water-cooled front, unless the manufacturer gives other instructions.
Following installation, the aperture 4 between flame tube and refractory should be
filled with flame-proof, resilient insulating material. Do not make solid.
Heat exchangers with deep refractories or thick doors, or heat exchangers with reverse flame combustion chambers may require a combustion head extension. Head
extensions of 100, 200 and 300 mm are available. Dimension 2 then changes according to the head extension used.
M12
1
45°
260 mm
220 mm
60°
4
260 mm
3
298 mm
2
The burner has to be hinged open by approx. 70 … 80° to allow removal of the mixing head.
1 Flange gasket
2 min 227 mm (combustion head OPEN)
max 247 mm (combustion head CLOSED)
3 Refractory
4 Aperture
83252902 1/2019-09 La
19-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
4.2 Check rating
The burner as delivered has been:
pre-sized for a specific oil throughput,
equipped with an oil nozzle type -w- K3 S1 50°.
The exact details are documented on the burner data sheet.
Pump pressure setting
30 bar
Determine exact oil throughput at oil meter or by weighing.
Nozzle selection table -w- K3 S1 50°
The following minimum capacity values are achieved with an oil quantity regulator
setting of 90°.
Nozzle size [kg/h]
90
100
110
120
130
140
150
160
170
180
83252902 1/2019-09 La
Burner capacity [kW] at pump pressure
20 bar
22 bar
24 bar
26 bar
851
893
934
976
898
941
984
1027
987
1035
1083
1130
1095
1147
1200
1252
1214
1272
1330
1389
1297
1359
1421
1483
1416
1483
1549
1616
1505
1576
1648
1719
1624
1700
1776
1853
1708
1788
1867
1947
20-84
28 bar
1017
1070
1178
2305
1447
1545
1682
1791
1929
2026
30 bar
1059
1113
1226
1357
1505
1607
1749
1862
2005
2106
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
4.3 Set mixing head
4.3.1 Setting diagram
Set mixing head relative to the combustion heat rating required. Therefore the flame
tube setting and air damper setting are matched.
Do not operate the burner outside of the capacity graph.
Determine the required flame tube setting (dimension S1) and air damper setting
from diagram and note down.
Example
Burner rating required
Combustion chamber pressure
Flame tube setting dimension S1
(auxiliary dimension E)
Air damper setting
13
12
60°
11
Example 1
1300 kW
1.5 mbar
123 mm
(10 mm)
55°
Example 2
1750 kW
2.5 mbar
114 mm
(19 mm)
> 90°
70° 80°
5
6
50°
10
9
40°
8
3
7
30°
6
20°
5
4
3
2
1
0
-1
2
-2
103
(30)
123 118 113 108
(10) (15) (20) (25)
-3
-4
4
-5
500
700
900
1100
1300
1500
1700
1900
2100
1
1
2
3
4
Combustion heat rating [kW]
Combustion chamber pressure [mbar]
Air damper setting in degree of angle(1
Flame tube setting dimension S1 [mm](1
(auxiliary dimension E [mm])(1
5 Setting range of air dampers with flame tube setting CLOSED (123 mm)
6 Setting range for flame tube with air damper setting > 90°
(1
Different settings may be required depending on site conditions.
83252902 1/2019-09 La
21-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
4.3.2 Set mixing head without combustion head extension
Hinge open the burner [ch. 9.3].
1. Set distance nozzle support to nozzle body
The distance between nozzle support and nozzle body 2 must be 90 mm.
If necessary adjust nozzle body:
Undo screws 1 on nozzle support.
set distance nozzle support to nozzle body to 90 mm,
Re-tighten screws.
90
1
mm
2
2. Set nozzle distance
Check nozzle distance (dimension A) using auxiliary dimension 2 between diffuser sleeve and burner flange.
Nozzle distance (dimension A)
7 mm
10 mm
13 mm
Auxiliary dimension 2
25 mm
28 mm
31 mm
Factory setting
The diffuser could become soiled if incorrectly positioned.
Determine auxiliary dimension 2 at a minimum of 3 points (each offset by 120°).
Check alignment of nozzle assembly to diffuser (even aperture).
If necessary set nozzle distance:
Undo screws 1.
Rotate diffuser sleeve 3, until auxiliary dimension 2 has been reached.
Re-tighten screws.
1
3
2
1
A
83252902 1/2019-09 La
22-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
3. Set distance flame tube to diffuser
The distance of flame tube to diffuser (dimension S1) determined from the setting
diagram is set between the flame tube and diffuser sleeve using auxiliary dimension
E.
Measure auxiliary dimension E and compare to the table below.
Distance determined
Flame tube to diffuser (dimension S1)
123 mm
118 mm
113 mm
108 mm
103 mm
Auxiliary dimension E
10 mm (combustion head CLOSED)
15 mm
20 mm
25 mm
30 mm (combustion head OPEN)
If the distance varies from the measured value by more than 5 mm, set flame tube:
Undo screws 1.
Adjust flame tube 2 until auxiliary dimension E has been reached, ensuring not
to alter the setting of the diffuser sleeve 3.
Centralise flame tube whilst checking the distance at a minimum of 3 positions
(each offset by 120°).
Re-tighten screws.
2
1
3
E
1
S1
Set ignition electrodes [ch. 9.4]
83252902 1/2019-09 La
23-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
4.3.3 Set mixing head with combustion head extension
Hinge open the burner [ch. 9.3].
Remove nozzle assembly.
1. Check flame tube length
Check total length of flame tube, see table.
Extension
Total length
100 mm
349 mm ±1
200 mm
449 mm ±1
300 mm
549 mm ±1
2. Nozzle distance and flame tube setting
The nozzle distance and the flame tube setting must be matched to one another.
Check nozzle distance, see table.
Nozzle distance (dimension A)
7 mm
10 mm
13 mm
Flame tube setting 4
11 mm
14 mm
17 mm
Factory setting
If necessary set nozzle distance:
Undo locking screws 3.
Adjust diffuser and set nozzle distance (dimension A).
Re-tighten locking screws.Re-tighten locking screws.
Match flame tube setting to nozzle distance:
Undo screws 1.
Adjust flame tube 2, until flame tube setting 4 has been reached.
Centralise flame tube whilst checking the distance at a minimum of 3 positions (each offset by 120°).
Re-tighten screws.
After every alteration to the nozzle distance or to the flame tube setting:
Check distance flame tube to diffuser.
Set ignition electrodes [ch. 9.4]
2
1
4
1
3
A
83252902 1/2019-09 La
24-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
3. Set distance flame tube to diffuser
The distance flame tube to diffuser (dimension S1) determined from the setting diagram is set at setting bolt 1 using auxiliary dimension EV.
Measure auxiliary dimension EV and compare to the table below.
Distance determined
Flame tube to diffuser (dimension S1)
123 mm
118 mm
113 mm
108 mm
103 mm
Auxiliary dimension Ev
30 mm (combustion head CLOSED)
25 mm
20 mm
15 mm
10 mm (combustion head OPEN)
If auxiliary dimensions EV varies from the measured value by more than 5 mm:
Undo locknut on setting bolt 1.
Turn setting bolt until auxiliary dimension EV has been reached.
Re-tighten locknut.
1
Ev
S1
83252902 1/2019-09 La
25-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
4.4 Burner installation
Fit flange gasket 3 and hinged flange 2 to the boiler plate using screws 1.
The aperture between combustion head and refractory should be filled with
flame-proof, resilient insulating material. Do not make solid.
1
3
2
Using suitable lifting equipment lift burner and, using hinge pins 1 fit into hinged
flange, observe pivoting direction.
Without combustion head extension
Close burner and secure with dome nut 2.
1
2
83252902 1/2019-09 La
26-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
4 Installation
With combustion head extension
Connect pressure hoses ensuring correct allocation.
Place ignition lines from the hinged flange into the burner housing.
R
V
Close burner and secure with dome nut 2.
Remove view port cover.
Plug in ignition lines 1.
Refit view port cover.
2
1
83252902 1/2019-09 La
27-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
5 Installation
5 Installation
5.1 Oil supply
Observe EN 12514-2, DIN 4755, TRÖI and local regulations.
Check conditions for oil pump
Suction resistance
Supply pressure
Supply temperature
(1
Measured at the pump.
max 0.4 bar(1
max 5 bar(1
max 140 °C(1
Check conditions for oil hoses
Length
Oil hose connection
Threaded socket connection
Nominal pressure
Thermal load
1000 / 1300 mm
M30 x 1.5
M30 x 1.5 x G1
10 bar
max 100 °C
Connect oil supply
Damage to the oil pump caused by incorrect connection
Mixing up supply and return can damage the oil pump.
Ensure correct connection of oil hoses to the supply and return of the pump.
CAUTION
1
2
1 Supply
2 Return
83252902 1/2019-09 La
28-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
5 Installation
Connect oil supply and observe:
do not twist oil hoses
avoid mechanical tension
consider length of hose required for the hinge range,
do not kink oil hoses (curve radius 1 of 145 mm must be maintained).
If these conditions for connection can not be met:
Adapt oil supply on site.
1
Purge oil supply and ensure it is tight
CAUTION
Damage to oil meter in oil circulating device resulting from purging
If an oil circulating device is fitted, the purging process could damage the integrated oil meter.
Replace oil meter with adapter during purging.
Oil pump seized due to running dry
Pump could be damaged.
Fill oil supply with oil and purge.
CAUTION
Ensure oil supply is tight.
83252902 1/2019-09 La
29-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
5 Installation
5.2 Electrical connection
DANGER
WARNING
Risk of electric shock
Working on the device when voltage is applied can lead to electric shock.
Isolate the device from the power supply prior to starting any work.
Safeguard against accidental restart.
Electric shock caused by frequency converter
It is possible that electrical components continue to carry voltage and cause electric shock even after the voltage supply has been disconnected.
Wait approx. 5 minutes before commencing work.
Electric voltage has dissipated.
The electrical connection must only be carried out by qualified electricians. Observe local regulations.
Connect combustion manager
Use cable entry grommets on the housing.
Connect wiring to wiring diagram enclosed.
Control circuits, which are taken directly via a 16 AB fuse from a 3 phase or
single phase alternating current supply, must only be connected between a phase
conductor and earth potential neutral conductor.
On mains supply, which does not have a neutral, the control voltage must be supplied via an isolating transformer. The pole of the transformer, which is to be used
as the neutral conductor, must be earthed.
Phase L must not be mixed up with the neutral conductor N. Contact protection will
otherwise no longer be given. Malfunctions, which endanger operational safety
could occur.
The cable cross section of the voltage supply must be suitable for the nominal current of the external fuse (maximum 16 AB). All other cable connections must be
suitable for the relevant internal unit fuse (T6.3H).
Earthing and neutral conductor must conform to local regulations.
The following applies for cable length:
all cable lengths maximum 100 m,
use only original Weishaupt parts as Bus line,
install Bus line as line configuration.
83252902 1/2019-09 La
30-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
5 Installation
Connecting the burner motor
The motor must be protected against thermal overload and short circuit. Weishaupt
recommend the use of a motor protection switch.
Open terminal box on motor.
Connect voltage supply to wiring diagram enclosed, observe motor rotation.
Variable speed drive (optional)
If the frequency converter is located on the motor, the cable to the frequency converter is not screened.
If the frequency converter is separate the control line and the motor connection
must be screened.
Apply screen to the screen clamp on frequency converter.
Use screen cable glands (metal) on the burner.
83252902 1/2019-09 La
31-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
6 Operation
6 Operation
For further details see installation and operating instructions Combustion Manager.
Display and operating unit (ABE)
4
1
3
2
1 Dial knob
navigation through parameter structure; changing values
select
return/cancel
return to operating display
2 [Enter]
3 [esc]
4 [info]
OFF function
Press [ENTER] and [esc] simultaneously.
Immediate lockout.
The lockout is stored in the fault history.
83252902 1/2019-09 La
32-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7 Commissioning
7.1 Prerequisite
Commissioning must only be carried out by qualified personnel.
Only correctly carried out commissioning ensures the operational safety.
Prior to commissioning ensure that:
all assembly and installation work has been carried out correctly,
sufficient combustion air is available, if necessary install ducted air intake
the annulus between flame tube and heat exchanger is filled
the heat exchanger is filled with medium
the regulating, control and safety devices are functioning and set correctly
the flue gas ducts are unimpeded
a measuring point conforming to standards is available to measure the flue
gas
the heat exchanger and flue gas ducting up to the test point are sound (extraneous air influences the test results)
the operating instructions of the heat exchanger are complied with
a heat demand is available
Additional system-related tests could be necessary. Please observe the operating
guidelines for the individual components.
On installations with process equipment, the conditions for safe operation and
commissioning must be met, see worksheet 8-1 (Print No. 831880xx).
83252902 1/2019-09 La
33-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7.1.1 Connect measuring devices
Pressure measuring device for mixing pressure
Open pressure test point for mixing pressure 1 and connect pressure measuring device.
1
Oil pressure measuring devices on oil pump
WARNING
Oil leakage from oil pressure measuring devices due to constant load
Oil pressure measuring devices could be damaged and cause environmental pollution through leakage.
Close or remove oil pressure measuring devices once commissioning is complete.
Vacuum gauge for suction resistance/supply pressure.
Pressure gauge for pump pressure.
Close fuel shut off devices.
Remove closing plug on the pump.
Connect vacuum gauge 1 and pressure gauge 2.
1
83252902 1/2019-09 La
2
34-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
Oil pressure measuring device connected to the return line
WARNING
Oil leakage from oil pressure measuring devices due to constant load
Oil pressure measuring devices could be damaged and cause environmental pollution through leakage.
Close or remove oil pressure measuring devices once commissioning is complete.
Pressure gauge for return pressure.
Remove bypass plug from the return line for pressure gauge 1.
Connect pressure gauge.
1
83252902 1/2019-09 La
35-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7.2 Adjusting the burner
In addition to this chapter, the installation and operating manual of the Combustion
Manager should be observed. This manual contains detailed information about:
menu structure and navigation,
parameter settings,
editing of points,
function, etc.
Prerequisite
Open oil shut off devices.
Switch on voltage supply.
1. Switch off burner
The ABE is in OperationalStat in the sub menu NormalOperation and displays current values.
Exit level using the [esc] key.
Select ManualOperation.
Select Autom/Manual/Off.
Set Burner Off.
The burner switches off.
Exit level using the [esc] key.
2. Enter password
Select Param & Display.
Select Access with HE (password for heating engineer).
Enter HE password using dial knob and confirm with [ENTER].
3. Check load limits
Select RatioControl.
Select OilSettings.
Select LoadLimits.
Select MinLoadOil and set 0.0%.
Select MaxLoadOil and set 100%.
Use [esc] key to return to the display LoadLimits.
4. Check ignition position
The setting of the oil quantity regulator in ignition position is pre-set when supplied
(see burner data sheet).
Select SpecialPositions.
Select IgnitionPos.
Select IgnPosOil (setting oil quantity regulator in ignition position).
Check IgnPosOil.
Use [esc] key to return to the display IgnitionPos.
83252902 1/2019-09 La
36-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
5. Check mixing pressure in ignition position
Select ProgramStop.
Select 36 IgnPos.
Use [esc] key to return to the display with OilSettings.
Select Autom/Manual/Off.
Select Manual (Burner On).
The burner starts and stops in ignition position without flame formation
Check rotation direction of burner motor
The mixing pressure in ignition position must be 2 … 4 mbar above the combustion
chamber pressure.
If necessary, adjust mixing pressure via air damper setting:
Select OilSettings
Select SpecialPositions.
Select IgnitionPos.
Select IgnitionPosAir and adjust.
Use [esc] key to return to the display IgnitionPos.
Only in conjunction with frequency converter
In oil operation, the ignition speed should be 100 %.
6. Ignition
Set Program stop to 44 Interv 1.
The burner ignites and the actuators stop in the ignition position.
The pump pressure in ignition position must be26 … 29 bar, see burner data sheet.
Check pump pressure at pressure gauge.
Remove end cap 1.
Undo lock nut 2.
Set pump pressure using pressure regulating screw.
increase pressure: clockwise rotation,
decrease pressure: anticlockwise rotation.
2
1
Check combustion values in ignition position.
Set O2 content of approx. 5 % by positioning oil quantity regulator (IgnPosOil), whilst observing return pressure and maintaining 12 bar.
83252902 1/2019-09 La
37-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7. Set intermediate load points
Set ProgramStop to deactivated.
Use [esc] key to return to the display SpecialPositions.
Select CurveParams.
Press [ENTER].
Point 1 is displayed.
Point 1 has been factory preset to a specific oil throughput, see burner data sheet.
Check combustion values
Adjust air damper setting (Air):
Press [ENTER] key.
Select Change point?.
Select Actuator positions with start.
Call up and change values with dial knob and [ENTER].
Exit point 1 using [esc] key and save with [ENTER] key.
Press [esc] key.
The menu displays Point, Manual and the current actuator positions.
In menu Point all load points can be adjusted.
In menu point Manual the current burner capacity can be adjusted manually.
Select Manual and confirm with [ENTER].
Increase burner rating using dial knob whilst observing combustion values (excess air) and flame stability.
Set load point using [ENTER] key if either:
the O2 content in the flue gas increases to above 7 %,
the soot limit is reached,
the CO content increases,
the flame reaches the limit of stability.
The new load point is displayed in menu Point and can be adjusted.
Correct combustion values via oil quantity regulator position (Burn).
Exit setting using [esc] and save with [ENTER].
Exit load point using [esc].
Repeat steps until full load (Load: 100) has been reached.
8. Adjust full load
When adjusting, the ratings data given by the boiler manufacturer and the capacity
graph of the burner should be observed [ch. 3.4.6].
The burner has been factory pre-sized for a specific oil throughput, see burner data
sheet.
Only in conjunction with frequency converter
Select speed at full load as low as possible, but not less than 90 %. Observe flame
stability.
Set pump pressure and oil quantity regulator position to the data given on the
burner data sheet.
Determine oil throughput, if necessary adjust position of oil quantity regulator
(Burn) until the oil throughput required is achieved.
Check combustion values
Determine combustion limit and set excess air [ch. 7.5].
The pump pressure must not be altered once this work has been completed.
83252902 1/2019-09 La
38-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
9. Re-define point 1
Drive to point 1 in menu Point, whilst observing the combustion values.
Check combustion values and correct if necessary.
Carry out load apportionment [ch. 7.6].
Only in conjunction with frequency converter
In oil operation, the speed should only be reduced so far, that the pump pressure
set at full load does not fall by more than 15 %.
To allow a reduction of MinLoad after commissioning, point 1 should be set below
the required partial load. However, it must lie within the capacity graph of the
burner.
10. Delete intermediate load points
Delete all load points except for point 1 and full load (Load: 100).
When an intermediate load point is deleted, all points above this intermediate load
point are reduced by one number.
11. Set new intermediate load points
Starting at point 1, new load points must be set until full load is reached.
A maximum of 15 load points can be programmed.
A minimum of 5 load points are required for modulating operation.
Increase burner rating in menu Manual, whilst observing combustion values.
Set new intermediate load point using [ENTER] key.
Optimise combustion at intermediate load point.
Carry out load apportionment [ch. 7.6].
Repeat steps until full load (Load: 100) has been reached.
Exit level using the [esc] key.
83252902 1/2019-09 La
39-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
12. Check start behaviour
Restart burner in Manual operation.
Check start behaviour and if necessary correct ignition position.
If the ignition position has been altered:
Re-check start behaviour.
If the oil temperature has been altered:
Re-check start behaviour.
Restart each point and check combustion values.
13. Define partial load
Select LoadLimits.
Select MinLoad.
Define and set partial load whilst:
Maintain return pressure of 8 bar.
observing data provided by boiler manufacturer,
observing the burner capacity graph [ch. 3.4.6].
14. Set burner to automatic operation
Exit level using the [esc] key.
Select Autom/Manual/Off.
Set Automatic.
Exit level using the [esc] key.
If necessary adjust load controller.
15. Carry out data backup
Exit level using the [esc] key.
Select Updating.
Select Param backup.
Select LMV → AZL .
Start data backup by pressing [ENTER] key.
The values have been backed up from the combustion manager to the ABE.
Exit level using the [esc] key.
83252902 1/2019-09 La
40-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7.3 Set oil pressure switch
Minimum oil pressure switch in the flow (optional)
Depending on the burner application, optional equipment may be required for optimum operation [ch. 12.3].
Remove end cap.
Set minimum oil pressure switch in the supply to 5 bar below the minimum pump
pressure.
Refit end cap.
Maximum oil pressure switch in the return
Remove end cap.
Set maximum oil pressure switch in the return to 5 bar, for ring main operation
set to 5 bar above the ring main pressure..
Refit end cap.
83252902 1/2019-09 La
41-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7.4 Concluding work
WARNING
Oil leakage from oil pressure measuring devices due to constant load
Oil pressure measuring devices could be damaged and cause environmental pollution through leakage.
Close or remove oil pressure measuring devices once commissioning is complete.
Check control and safety devices.
Check tightness of oil carrying components.
Enter combustion values and settings in the commissioning record and/or test
sheet.
Inform the operator about the use of the equipment.
Hand the installation and operating manual to the operator and inform him that
this should be kept with the appliance.
Point out to operator that the installation should be serviced annually.
83252902 1/2019-09 La
42-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7.5 Check combustion
Determine excess air
Slowly close air damper(s) in the relevant operating point, until the combustion
limit is reached (soot number approx. 1).
Measure and document O2 content.
Read air number (λ).
Increase air number to ensure sufficient excess air:
by 0.15 … 0.2 (equates to 15 … 20 % excess air),
by more than 0.2 for more difficult conditions, such as:
dirty combustion air,
fluctuating intake temperature,
fluctuating chimney draught.
Example
λ + 0.15 = λ*
Set air number (λ*), do not exceed CO content of 50 ppm.
Measure and document O2 content.
Check flue gas temperature
Check flue gas temperature.
Ensure that the flue gas temperature complies with the data provided by the
boiler manufacturer.
If necessary adjust flue gas temperature, e g.:
Increase burner capacity in partial load to avoid condensation in the flue gas
ducts, except on condensing units.
Reduce burner capacity in full load to improve efficiency.
Adjust heat exchanger to the data provided by the manufacturer.
Determine flue gas losses
Drive to full load.
Measure combustion air temperature (tL) near the air damper(s).
Measure oxygen content (O2) and flue gas temperature (tA) at the same time at
one point.
Determine flue gas losses using the following formula:
qA =
qA
tA
tL
O2
(tA - tL ) (
A2
)+B
21- O2
Flue gas losses [%]
Flue gas temperature [°C]
Combustion air temperature [°C]
Volumetric content of oxygen in dry flue gas [%]
Fuel factors
A2
B
83252902 1/2019-09 La
Fuel oil
0.68
0.007
43-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
7 Commissioning
7.6 Ratings apportionment
The load points are automatically assigned relative to the capacity. Incorrect load
distribution can cause operating problems during the load control.
Assign capacity in % for load point using the following formula.
Enter the calculated capacity for load point in Load.
Load [%] =
83252902 1/2019-09 La
44-84
Throughput load point
Throughput full load
100
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
8 Shutdown
8 Shutdown
For breaks in operation:
Switch off burner.
Close fuel shut off devices.
83252902 1/2019-09 La
45-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9 Servicing
9.1 Notes on servicing
DANGER
WARNING
Risk of electric shock
Working on the device when voltage is applied can lead to electric shock.
Isolate the device from the power supply prior to starting any work.
Safeguard against accidental restart.
Electric shock caused by frequency converter
It is possible that electrical components continue to carry voltage and cause electric shock even after the voltage supply has been disconnected.
Wait approx. 5 minutes before commencing work.
Electric voltage has dissipated.
Danger of getting burned on hot components
Hot components can lead to burns.
Allow components to cool.
WARNING
Servicing must only be carried out by qualified personnel. The combustion plant
should be serviced annually. Depending on site conditions more frequent checks
may be required.
Components, which show increased wear and tear or whose design lifespan is or
will be exceeded prior to the next service should be replaced as a precaution.
Weishaupt recommends a service contract is entered into to ensure regular inspections.
The following components must only be replaced and must not be repaired:
combustion manager
flame sensor
actuator
oil solenoid valve
nozzle head,
pressure switch,
oil nozzle.
Prior to every servicing
Inform the operator about the extent of service work to be carried out.
Switch off mains switch of installation and safeguard against accidental reactivation.
Close fuel shut off devices.
Following servicing
Check tightness of oil carrying components.
Check function of:
ignition,
flame monitoring,
oil pump (pump pressure and suction resistance),
Pressure switch
control and safety devices.
Check combustion values, if necessary re-adjust the burner.
Enter combustion values and settings in the commissioning record and/or test
sheet.
83252902 1/2019-09 La
46-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.2 Service plan
Components
Fan wheel
Coupling cross on coupling
centre piece
Criteria / design lifespan(1
Soiling
Damage
Wear
Service procedure
Clean
Replace
Replace
Air duct
Air damper
Soiling
Soiling
Distance to housing < 0.3 mm
Sleeve bearing air damper shaft Has play
Air regulator cladding
Damage/brittleness/soiling
View port cover
Air escaping
Ignition cable
Damage
Ignition electrode
Soiling
Damage/wear
Combustion Manager
250 000 burner starts or 10 years(2
Flame sensor
Soiling
Damage
Flame tube/diffuser
Oil nozzle
Oil hose
250 000 burner starts or 10 years(2
Soiling
Damage
Soiling/wear
Recommendation: at least every 2 years
Clean
Clean
Adjust [ch. 9.8]
Replace [ch. 9.8]
Replace
Replace
Replace
Clean
Replace
Replace
Clean
Replace
Clean
Replace
Replace
Recommendation: at least every 2 years
Replace
Damage/oil escaping
Recommendation: every 5 years
Replace
Pressure hose nozzle assembly Damage/oil escaping
(with combustion head exten5 years
sion)
Oil solenoid valve
Soundness
Replace oil pump or solenoid valve
(2
Oil quantity regulator
250 000 burner starts or 10 years
Excess air due to wear
Replace
Hysteresis behaviour/damage/oil escaping
250 000 burner starts or 10 years(2
Oil pressure switch
Switch point
Check
(2
250 000 burner starts or 10 years
Replace
(1
The specified design lifespan applies for typical use in heating, hot water and steam systems as well as for thermal
process systems to EN 746.
(2
If a criterion is reached, carry out maintenance measures.
83252902 1/2019-09 La
47-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.3 Hinge open the burner
Observe notes on servicing [ch. 9.1].
Damage to oil hoses due to mechanical strain
If oil hoses are leaking, oil can escape and lead to environmental damage.
Avoid mechanical strain on the oil hoses when hinging open the burner.
WARNING
Check hinge pin 1 on burner flange is fitted correctly.
Remove dome nut 2.
Carefully hinge open the burner.
1
83252902 1/2019-09 La
48-84
2
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.4 Set ignition electrodes
Observe notes on servicing [ch. 9.1].
The distance between the ignition electrodes and other components must be
greater than the spark gap between the electrodes.
The ignition electrodes must not touch the nozzle's atomising cone.
Hinge open the burner [ch. 9.3].
Remove nozzle assembly (only with combustion head extension).
Undo screw 1 on the ignition electrode holder.
Set ignition electrodes.
Tighten screw.
1
4.
83252902 1/2019-09 La
49-84
.. 6
mm
3 ... 4 mm
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.5 Replace nozzle
Observe notes on servicing [ch. 9.1].
Do not clean nozzles, always fit new nozzles.
Hinge open the burner.
Remove ignition electrodes.
Counter-hold on the nozzle assembly using a spanner and remove nozzle.
Fit new nozzle ensuring it is seated tightly.
Fit and adjust ignition electrodes [ch. 9.4].
With combustion head extension
Hinge open the burner.
Remove pressure hoses.
Remove fixing screws from nozzle assembly bracket.
Remove nozzle assembly.
Measure distance to diffuser and record.
Remove diffuser and nozzle support complete with ignition electrodes.
Counter-hold on the nozzle assembly using a spanner and remove nozzle.
Fit new nozzle ensuring it is seated tightly.
Refit diffuser and nozzle support with ignition electrodes.
Check, and if necessary adjust, nozzle distance to diffuser.
Refit in reverse order, ensuring correct allocation of pressure hoses.
1
2
1 Nozzle
2 Nozzle assembly
83252902 1/2019-09 La
50-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.6 Removing and refitting air damper actuator
Observe notes on servicing [ch. 9.1].
Removing
Remove actuator cover.
Unplug plug and remove cable entry gland 1.
Undo locknut 2 on the coupling.
Remove screws 3.
Remove actuator from the coupling.
2
3
1
Refitting
Refit actuator in reverse order, ensuring correct alignment of shaft key.
Check address and Bus termination, see installation and operating manual Combustion Manager.
83252902 1/2019-09 La
51-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.7 Removing air regulator
Observe notes on servicing [ch. 9.1].
Remove air damper actuator [ch. 9.6].
Remove inlet mesh 2.
Remove air regulator 1.
1
2
83252902 1/2019-09 La
52-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.8 Set air regulator
Observe notes on servicing [ch. 9.1].
Remove air inlet mesh [ch. 9.7].
If necessary remove air regulator [ch. 9.7].
Set air dampers
Only tamper proof screws should be used in the air regulator section.
If the distance of the air dampers to the housing on the actuator side is less than
the dimension of 0.3 mm:
Undo screws 1.
Align air dampers.
Re-tighten screws.
Ensure air dampers have freedom of movement.
Check sleeve bearing
It must not be possible to axially move the air dampers without using force (0 mm
play).
If axial play 2 is present at the air dampers:
Replace sleeve bearing.
83252902 1/2019-09 La
53-84
1
0.4 mm ±0.1
1
2
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.9 Removing and refitting oil quantity regulator actuator
Observe notes on servicing [ch. 9.1].
Removing
Remove actuator cover.
Unplug plug and remove cable entry gland 3.
Remove view port 1 – or – if the actuator is not at 0°, remove plug 2.
Undo locknut 5.
Remove screws 4.
Remove actuator from the coupling.
1
2
5
4
3
If the intermediate housing or the coupling need to be replaced:
Undo second locknut 2 of coupling.
Carefully pull coupling from drive shaft.
Remove shaft keys 1.
Undo fixing screws and remove intermediate housing 3.
1
1
3
2
Refitting
Refit actuator in reverse order.
Ensure correct alignment of shaft keys.
Push coupling carefully and without pressure onto shaft.
Check address and Bus termination, see installation and operating manual Combustion Manager.
83252902 1/2019-09 La
54-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.10 Set pump coupling
Observe notes on servicing [ch. 9.1].
A flexible pump coupling is fitted between fan wheel and oil pump.
Remove air regulator cover.
Undo Allen screw 2 on the pump coupling.
Align pump coupling in such a way that no axial loading force is applied to the
drive shaft and the coupling centre piece 1 is provided with an axial play of
1.5 mm.
Tighten Allen screw.
2
1
83252902 1/2019-09 La
55-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
9 Servicing
9.11 Removing fan wheel
Observe notes on servicing [ch. 9.1].
A tamper proof screw must be used when installing the fan wheel.
Remove screw 1.
Remove fan wheel with fan wheel puller from motor shaft.
1
83252902 1/2019-09 La
56-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
10 Troubleshooting
10 Troubleshooting
10.1 Procedures for fault conditions
Check prerequisites for operation:
Voltage supply available.
Heating switch is set to On.
Temperature regulator or pressure regulator on heat exchanger has been set
correctly.
Boiler or heating circuit control is functioning and set correctly.
The combustion manager recognises irregularities of the burner and displays these
on the display and operating unit (ABE).
The following conditions can occur:
Fault [ch. 10.1.1]
Lockout [ch. 10.1.2]
83252902 1/2019-09 La
57-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
10 Troubleshooting
10.1.1 Fault
If a fault occurs, the combustion manager initiates a controlled shutdown.
The display and operating unit alternately shows the shutdown behaviour and the
fault diagnosed as a plain text display.
Example
Safety
shutdown
Safety loop
is open
The burner restarts automatically as soon as the fault condition has been rectified.
The following faults may be corrected by the operator:
Fault
Cause
Safety circuit open
Temperature limiter or pressure limiter
on heat exchanger has triggered(1
Low water safety interlock on heat exchanger has triggered(1
Rectification
Reset temperature limiter or pressure
limiter on heat exchanger.
Top up water.
Reset low water safety interlock on
heat exchanger.
(1
Notify your heating contractor or Weishaupt Customer Service if the problem occurs repeatedly.
All other faults must only be rectified by qualified personnel.
Read the error code and proceed according to the error message, see installation and operating manual combustion manager.
83252902 1/2019-09 La
58-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
10 Troubleshooting
10.1.2 Lockout
If a lockout condition occurs, the combustion manager initiates a fault shutdown
and burner lockout.
The display and operating unit alternately shows the shutdown behaviour and the
fault diagnosed as a plain text display.
Example
Lockout
Air pressure is
off
Once the fault has been rectified, the combustion manager has to be reset for restart.
Lockouts must only be rectified by qualified personnel.
Read the error code and proceed according to the error message, see installation and operating manual combustion manager.
Resetting
WARNING
Damage resulting from incorrect fault repair
Incorrect fault repair can cause damage to the equipment and injure personnel.
Do not carry out more than 2 lockout resets successively.
Faults must be rectified by qualified personnel.
If the ABE displays a fault:
Exit display using the [esc] key.
Reset burner using the [ENTER] key.
If the [esc] key has been pressed twice, reset can only be carried out via the menu.
Select Operating display.
Select Status/Reset.
Current lockout is displayed.
Exit display using the [esc] key.
Reset burner using the [ENTER] key.
Exchanging the unit
If the combustion manager or the ABE are replaced:
Select and check fault history and lockout history and include a copy when returning the unit for exchange.
83252902 1/2019-09 La
59-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
10 Troubleshooting
10.2 Rectifying faults
The following faults must only be rectified by qualified personnel:
Fault
Cause
Rectification
Burner motor does not run
No voltage
Check voltage supply
Overload relay or motor protection
Check setting
switch has tripped
Motor contactor / frequency converter
Replace motor contactor / frequency
defective
converter
Motor defective
Replace motor
No ignition
Ignition electrodes too far apart or short
Set ignition electrode [ch. 9.4]
circuit
Ignition electrode dirty or wet
Clean and adjust ignition electrode
[ch. 9.4]
Ceramic insulator defective
Replace ignition electrode.
Ignition cable defective
Replace ignition cable
Ignition unit defective
Replace ignition unit
Fuel valve does not open
No voltage
Check voltage supply
Coil defective
Replace coil
Oil pump supplies no oil
Shut off device closed
Open shut off device
Oil supply leaking
Check oil supply [ch. 12.1]
Anti siphon valve does not open
Check valve and replace if necessary
Oil filter of oil supply soiled
Clean filter insert or replace
Oil pump defective
Replace oil pump
No oil throughput at the nozzle Nozzle blocked
Replace nozzle
No flame formation despite igni- Ignition electrode set incorrectly
Set ignition electrode [ch. 9.4]
tion and fuel
Mixing pressure too high
Correct mixing pressure in ignition
load setting, if necessary adjust
mixing head [ch. 4.3]
Poor start behaviour of burner
Mixing pressure too high
Correct mixing pressure in ignition
load setting, if necessary adjust
mixing head [ch. 4.3]
Ignition electrode set incorrectly
Set ignition electrode [ch. 9.4]
Too much or too little fuel
Correct fuel quantity in ignition position via fuel actuator
Combustion manager does not Flame sensor soiled
Clean flame sensor
detect a flame signal
Flame signal insufficient
Check flame signal
Check flame sensor
Check burner setting
Flame sensor defective
Replace flame sensor
Combustion pulsating or burner Incorrect combustion air quantity
Check combustion values
booming
Mixing head set incorrectly
Set mixing head [ch. 4.3]
Back pressure from the system
Check flue gas system [ch. 12.2]
Flame failure during operation
Oil supply leaking / suction resistance
Check oil supply [ch. 12.1]
too high
Oil nozzle soiled/worn
Replace nozzle
Flame signal insufficient
Check flame signal
Check flame sensor
Check burner setting
83252902 1/2019-09 La
60-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
10 Troubleshooting
The following faults must only be rectified by qualified personnel:
Fault
Cause
Oil pump makes severe mech- Oil pump sucks air
anical noise
Suction resistance in oil line too high
Oil nozzle atomisation uneven
Combustion head is contaminated with oil or has heavy carbon deposits
Fuel valve does not close tight
Heavy material erosion on the
flame tube
83252902 1/2019-09 La
Rectification
Ensure oil supply is tight
Clean filter
Check oil supply [ch. 12.1]
Nozzle soiled/worn
Replace nozzle
Oil nozzle defective
Replace nozzle
Mixing head set incorrectly
Set mixing head [ch. 4.3]
Incorrect combustion air quantity
Adjust burner
Boiler room ventilated insufficient
Ensure sufficient boiler room ventilation
Nozzle assembly and diffuser not
Check centralisation of nozzle ascentred
sembly to diffuser
Dirt particles in the fuel valve
Replace fuel valve
High boiler room temperatures or acidic
Use H1 flame tube with higher temcombustion air due to ambient condiperature resistance
tions
61-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
11 Technical documentation
11 Technical documentation
11.1 Conversion table unit of pressure
Bar
0.1 mbar
1 mbar
10 mbar
100 mbar
1 bar
10 bar
83252902 1/2019-09 La
Pa
10
100
1 000
10 000
100 000
1 000 000
62-84
hPa
0.1
1
10
100
1 000
10 000
Pascal
kPa
0.01
0.1
1
10
100
1 000
MPa
0.00001
0.0001
0.001
0.01
0.1
1
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
12 Project planning
12 Project planning
12.1 Oil supply
Observe EN 12514-2, DIN 4755, TRÖI and local regulations.
General information relating to the oil supply
Do not use cathode protection system with steel tanks.
With oil temperatures < 5 °C, the separation of paraffin can cause oil lines, oil filters and nozzles to become blocked. Avoid placing oil tanks and pipelines in
areas subject to frost.
The oil supply should be installed in such a way that it is possible to hinge open
the burner.
Fit oil filter in front of pump, maximum mesh aperture 100 μm.
Suction resistance and supply pressure
CAUTION
Pump damage due to excessive suction resistance
A suction resistance greater than 0.4 bar can damage the pump.
Reduce suction resistance – or – install oil supply pump or suction unit, whilst
observing the maximum supply pressure at the oil filter.
The suction resistance depends on:
suction line length and diameter,
pressure loss of oil filter and other components,
lowest oil level in the oil storage tank (max 3.5 m below the oil pump).
Shut off devices at the burner
CAUTION
Damage caused by the shut off device closing too fast
Pressure surges and cavitation can damage the components of the oil supply.
When testing the operation of the limit switches the shut off device must only be
closed until the safety shut off responds.
The shut off device can only be closed completely when the oil pump has shut
off.
The isolating valves operate mechanically in compound and are fitted with a limit
switch, which inhibits burner operation when the isolating valves are closed.
Protect shut off devices in the return line from accidental closure.
The installation of non return valves is not permitted.
83252902 1/2019-09 La
63-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
12 Project planning
12.1.1 Ring main operation
Oil supply via ring main system is recommended for:
large industrial and district heating installations, which are run almost continually,
larger distances,
several burners.
For installation and function drawing for ring main operation, see Technical worksheets.
The installation of a duplex oil pump station as ring main pump is recommended.
Cleaning and service work on the pump or oil filter is then possible during burner
operation.
The supply quantity must be a minimum of one and a half to twice the total firing
rates of all burners supplied by the ring main.
The burners are connected to the ring main via a two pipe system.
Set ring main pressure for fuel oil EL via pressure regulating valve to
1 … 1.5 bar.
The oil filter must be suitable for the ring main pressure.
An oil circulation device or Weishaupt gas/air separator should be fitted at each
oil outlet point. Observe information label on separator.
12.1.2 Oil circulation unit
The ring main supply can be fitted with an oil circulation unit.
The unit contains:
oil meter,
oil filter,
circulation tank,
safety valve.
Recommendation Weishaupt oil circulation unit W-OC-…
12.2 Flue gas system
When designing the flue gas system observe BDH Info sheet No. 32 "Requirements on flue gas systems, see www.bdh-koeln.de.
83252902 1/2019-09 La
64-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
12 Project planning
12.3 Additional requirements
Additional requirements for burners for liquid and gaseous fuels to EN 267:
the pressure equipment operates in accordance with the Pressure Equipment
Directive 2014/68/EU,
as components of industrial thermal process plants in accordance
with EN 746-2,
on steam and hot water water-tube boilers in accordance with EN 12952-8.
PED
2014/68/EU
X
EN
746-2
EN
12952-8
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Components
Requirement
Burner control,
combustion manager
Flame monitor,
flame sensor
Control device air/fuel ratio
Air monitoring device, air pressure switch
Minimum fuel pressure monitoring device
Maximum fuel pressure monitoring device
Oil solenoid valve
Manual shut off device for all
fuels
Safety devices for save operation
Designed for continuous operation greater than 1200 kW
self-checking
X
Electrical equipment
Only for burners with return flow nozzle.
(2
Only for continuous operation without monitoring.
(1
83252902 1/2019-09 La
65-84
ISO 23552-1
Min. pressure switch to
EN 1854
Min. oil pressure switch(2
Max. oil pressure switch(1
2 x flow, 2 x return, EN 23553-1
Isolating valve
Connected to the input of the
combustion manager in the
closed circuit current principle
EN 50156
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
13 Spares
1.01
1.07
(1
1.06
(1
1.03
(1
1.05
1.10
1.04
(1
1.02
1.09
1.08
1.20
1.11
1.12
1.14
1.16
1.14
1.15
1.21
1.18
1.15
1.13
83252902 1/2019-09 La
1.19
66-84
1.17
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
Pos.
1.01
1.02
1.03
1.04
1.05
1.06
1.07
1.08
1.09
1.10
1.11
1.12
1.13
1.14
1.15
1.16
1.17
1.18
1.19
1.20
1.21
83252902 1/2019-09 La
Description
View port cover complete
View port set
View port closing cover
– Spring nut 4 x 9
Hinge pin 14 x 277
Circlip 10
Hinged flange
– Screw M12 x 35
– Washer B13 DIN 125 St
Screw M12 x 70 DIN 931 8.8
Dome nut M12 DIN 1587
Washer B13 DIN 125 St
Flange gasket 330/340 x 202 - TK298
Cable entry W-FM complete
Air regulator housing
Air regulator cladding
Screw M6 x 185 DIN 912
Screw M6 x 35 / 250
Washer 5.1 x 11 x 0.6
Air regulator cover
Lining air regulator cover
Spring nut 6 x 20
Name plate
Cable gland set
67-84
Order No.
211 204 01 022
211 104 01 192
211 104 01 132
412 509
211 304 01 077
431 604
211 204 01 027
402 705
430 801
401 701
412 401
430 801
211 204 01 057
211 104 01 052
211 204 02 157
211 204 02 167
402 408
211 204 02 137
430 015
211 204 02 197
211 204 02 187
412 506
211 204 01 067
211 204 00 512
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
2.05
2.04
2.01
2.02
2.06
2.06
2.03
2.07
2.08
2.09
2.10
2.16
2.15
2.17
(1
2.18
(1
(1
(1
(1
(1
2.20
2.26
(1
2.22
2.21
(1
2.25
2.19
2.23
2.24
2.24
2.12
2.27
2.13
2.21
2.14
2.14
2.22
2.11
83252902 1/2019-09 La
68-84
(1
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
Pos.
2.01
2.02
2.03
2.04
2.05
2.06
2.07
2.08
2.09
2.10
2.11
2.12
2.13
2.14
2.15
2.16
2.17
2.18
2.19
2.20
2.21
2.22
2.23
2.24
2.25
2.26
2.27
83252902 1/2019-09 La
Description
Motor WM-D112/140-2/3K5
with motor contactor
Motor contactor B7, 230V 50Hz
Cable gland set
Motor WM-D112/140-2/3K5
for frequency converter mounted
Frequency converter configured
WM-D112/140-2/3K5 for W-FM 200
Shaft key 6 x 6 x 45
Fan wheel TS-S 268 x 104 S1 (50Hz)
– fan wheel puller (tool)
Washer 8.5 x 22
Screw M8 x 20 DIN 7991 with Precote
Inlet nozzle 285 x 209 x 43 (50Hz)
Air inlet mesh
– Screw M5 x 16 Duo Taptite
Air regulator complete
Air regulator
Air damper
– Screw M4 x 10 DIN 912 with TufLok
Actuator SQM45.291 B9 3Nm
– Cable entry cpl. with 2 W-FM plugs
Shaft key 3 x 3.7 DIN 6888
Air damper shaft with coupling
Air damper shaft with spring pin
Sleeve bearing set air regulator
Air regulator scale
Adjusting lever
Screw M5 x 12 with Precote
Ball joint rod
Screw M6 x 16 with TufLok
Screw M6 x 110 DIN 7500
Washer A6.4 DIN 125
Washer 5.1 x 11 x 0.6
69-84
Order No.
215 204 07 010
702 818
211 204 00 512
215 204 07 020
211 204 07 077
490 316
211 204 08 011
111 111 00 012
111 612 08 097
404 414
211 204 02 017
211 204 02 222
409 312
211 204 02 142
211 204 02 147
211 204 02 077
402 264
651 501
217 605 12 052
490 157
211 204 02 202
211 204 02 212
211 104 02 502
211 314 02 177
211 104 02 047
211 104 02 187
211 104 02 192
402 268
409 364
430 400
430 015
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
3.50*
3.50*
3.04
3.51*
3.01
3.51*
3.03
3.02
3.01
3.02
3.
3.08
3.02
3.05
3.
3.07
3.03
3.02
3.06
3.05
3.10
3.11
3.12
3.13
3.21
3.09
3.22
3.24
3.20
3.12
3.14
3.19
3.25
3.22
3.23
3.28
3.27
3.02
3.05
3.26
3.15
3.18
3.17
3.02
3.16
3.29
3.45
3.49
3.47
3.46
3.48
3.30
3.31
3.32
3.35
3.44
3.34
3.38
3.39
3.41
3.40
3.42
83252902 1/2019-09 La
70-84
3.02
3.02
3.05
3.29
3.33
3.37
3.40
3.05
3.03
3.48
3.43
3.02
3.03
3.35
3.36
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
Pos.
3.01
3.02
3.03
3.04
3.05
3.06
3.07
3.08
3.09
3.10
3.11
3.12
3.13
3.14
3.15
3.16
3.17
3.18
3.19
3.20
3.21
3.22
3.23
3.24
3.25
3.26
3.27
3.28
3.29
3.30
3.31
3.32
3.33
3.34
3.35
3.36
83252902 1/2019-09 La
Description
Threaded socket 6LL M10X1 X G 1/4
Sealing ring A13.5 x 17 x 1.5 DIN 7603 Cu
Solenoid valve 6027 NC DN3.5 110-120V 50Hz
Solenoid coil 110-120V 50Hz 20W
Screwed union 24-SDSX-L10-G¼A-ST-CH60
Screwed union 24-SWT-L10-ST
Bypass plug BUZ 10-L with nut
Pressure gauge 0 to 40 bar with ball valve
Oil line 10 x 1.0 return solenoid valve
Screwed union 24-BDE-L10-G¼B-ST-C21
Threaded socket G⅜ x G¼I x 20
Sealing ring A 17 x 21 x 1.5 DIN 7603 Cu
Oil quantity regulator W-ÖMR 1 f. W-FM
Screwed union 24-SDSX-L10-G⅜A-ST-CH60
Oil line 10 x 1.0 suppl. oil regulator
Screwed union 24-SWL-L10-ST
Screwed union 24-SWE-L10-ST
Oil line 10 x 1.0 x 68 distributor piece
Threaded socket G¼I x G½I x 40
Sealing ring C6.2 x 17.5 x 2 DIN 16258 Cu
Pressure switch type DSB 146 F931 1-10bar
Shaft key 3 x 3.7 DIN 6888
Interm. housing for oil regulator series B
View port 33 x 33 x 6
Oblong plug GPN 270 R 3015
Spring coupling bar series 2
Actuator SQM45.291 B9 3Nm
– Cable entry cpl. with 1 W-FM plugs
Oil line 10 x 1.0 flow S-SV
Threaded socket 10 x G¼ x 50
Threaded socket 10L M16 x 1.5 x G½ x 34
Sealing ring A21 x 26 x 1.5 DIN 7603 Cu
Pump TA2C 4010-7W
Edge sealing ring GP-SR-G½B-H4.5-ST
Screwed union 24-BDEX-L18-G½B-ST-C21
Screwed union 24-SWS-L18-L10-ST-CP1L
Union nut 24-N-L18-ST
71-84
Order No.
140 223 85 067
440 010
604 872
604 692
452 253
452 501
211 304 13 012
110 011 50 012
215 204 06 028
452 603
211 373 15 127
440 003
211 704 15 202
452 277
215 204 06 038
452 551
452 451
212 374 06 038
290 504 13 037
440 007
640 102
490 157
211 704 15 272
211 404 17 027
446 115
217 704 15 107
651 501
217 605 12 042
215 204 06 018
151 101 26 012
111 574 06 017
440 020
601 050
450 652
450 650
452 151
452 803
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
3.50*
3.50*
3.04
3.51*
3.01
3.51*
3.03
3.02
3.01
3.02
3.
3.08
3.02
3.05
3.
3.07
3.03
3.02
3.06
3.05
3.10
3.11
3.12
3.13
3.21
3.09
3.22
3.24
3.20
3.12
3.14
3.19
3.25
3.22
3.23
3.28
3.27
3.02
3.05
3.26
3.15
3.18
3.17
3.02
3.16
3.29
3.45
3.49
3.47
3.46
3.48
3.30
3.31
3.32
3.35
3.44
3.34
3.38
3.39
3.41
3.40
3.42
83252902 1/2019-09 La
72-84
3.02
3.02
3.05
3.29
3.33
3.37
3.40
3.05
3.03
3.48
3.43
3.02
3.03
3.35
3.36
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
Pos.
Description
3.37 Collar screw GP-BDBS-L15-G½-ST
3.38 Sealing ring A27 x 32 x 2 DIN 7603 Cu
3.39 Threaded socket DN 20 M30 x 1.5 x M26 x1.5
3.40 Oil hose DN20 1000 lg identification black
3.41 Threaded socket DN 20 M30 x 1.5 x G1
3.42 Sealing ring A33 x 39 x 2 DIN 7603 Cu
3.43 Pipe elbow DN 20 M30x1.5xM30x1.5 x G⅛
3.44 Threaded socket DN 20 M30 x 1.5 x G½
3.45 Vacuum gauge -1+9 bar for TA pump
3.46 Pressure gauge 0 to 40 bar for TA pump
3.47 Pump coupling 54.3 x D 35
3.48 Universal joint
3.49 Coupling centre piece 235 mm
3.50 Pressure hose DN 6 650 mm*
3.51 Nut M16 x 1.5 *
* Only in conjunction with combustion head extension.
83252902 1/2019-09 La
73-84
Order No.
450 651
440 039
111 782 06 027
491 034
112 151 00 057
440 032
453 251
112 654 00 017
210 204 06 192
210 204 06 182
218 324 09 012
111 151 09 017
211 402 09 012
210 201 10 012
210 104 10 087
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
4.01
4.03
4.04
4.05
4.06
4.05
4.12
4.09
4.08
4.07
4.01
4.02*
4.04
4.05
4.06*
4.05
4.10*
4.09*
4.12
4.11*
83252902 1/2019-09 La
74-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
Pos.
4.01
Description
Flame tube
– WM-L20/2
– H1 WM-L20/2
4.02 Extension pipe
– extended by 100 mm*
– extended by 200 mm*
– extended by 300 mm*
4.03 Diffuser 165 x 50
4.04 Ignition electrode holder
4.05 Ignition electrode
4.06 Ignition cable 11 /4.1
– 400 mm (Standard)
– 500mm (for 100 mm extension)*
– 500mm (for 200 mm extension)*
– 700mm (for 300 mm extension)*
4.07 Fixing plate for nozzle assembly
4.08 Nozzle support
4.09 Nozzle head
– Standard
– extended by 100 mm*
– extended by 200 mm*
– extended by 300 mm*
4.10 Nozzle support for extension*
4.11 Diffuser for extension*
4.12 Spill type nozzle
– K3S1 70 kg 50°
– K3S1 80 kg 50°
– K3S1 90 kg 50°
– K3S1 100 kg 50°
– K3S1 110 kg 50°
– K3S1 120 kg 50°
– K3S1 130 kg 50°
– K3S1 140 kg 50°
– K3S1 150 kg 50°
– K3S1 160 kg 50°
– K3S1 170 kg 50°
– K3S1 180 kg 50°
– K3S1 190 kg 50°
– K3S1 200 kg 50°
– K3S1 210 kg 50°
* Only in conjunction with combustion head extension.
83252902 1/2019-09 La
75-84
Order No.
111 762 14 047
111 762 14 067
150 518 14 057
150 518 14 067
150 518 14 077
211 204 14 012
211 104 10 107
211 104 10 047
211 104 11 032
211 104 11 042
211 104 11 052
218 204 11 072
211 104 10 097
211 204 10 017
215 204 10 012
210 205 10 012
210 205 10 022
210 205 10 032
210 104 10 067
210 204 14 022
602 557
602 558
602 559
602 560
602 561
602 562
602 563
602 564
602 565
602 566
602 567
602 568
602 583
602 569
602 584
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
5.10
5.08
5.09
5.07
5.06
5.05
5.11
5.21
5.04
5.12
5.03
5.13
5.05
5.01
5.14
5.15
5.02
5.16
5.20
5.17
5.19
5.18
83252902 1/2019-09 La
76-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
Pos.
5.01
5.02
5.03
5.04
5.05
5.06
5.07
5.08
5.09
5.10
5.11
5.12
5.13
5.14
5.15
5.16
5.17
5.18
5.19
5.20
83252902 1/2019-09 La
Description
ABE for W-FM 100/200
– Western Europe 1 (GB, D, F, I, E, P)
– Western Europe 2 (GB, NL, DK, S, N, FIN)
– Eastern Europe 1 (GB, PL, H, CZ, KRO, SLO)
– Eastern Europe 2 (GB, D, RUS, TR, RO, BG)
Plug cable W-FM…ABE
– ABE fitted to housing
– ABE fitted external 4000 mm
– ABE fitted external 2500 mm
– ABE fitted external 1500 mm
Cover
– ABE inbuilt
– ABE external
Combustion manager 230 V 50/60 Hz
– W-FM 100 without load controller
– W-FM 100 with load controller
– W-FM 200
Stay bolt cover W-FM
Mounting plate for W-FM
Flame sensor QRI 2B2.B180B
Flange for flame sensor QRI
Seal for flame sensor flange
Limit switch
Transf. for W-FM 100/200 AGG 5.220 230 V
Seal for ignition unit 2 pole
Ignition unit type W-ZG02 230V with W-FM plug
Plug cable W-FM transf. 12-0-12V
Plug cable W-FM transf. 230V/12V
Plug cable for pressure switch DSB158
Plug cable W-FM - air actuator
Plug cable SQM to SQM 500mm with angle
Plug cable with plug X8-02 solenoid valve
Plug cable with plug X8-03 solenoid valve
77-84
Order No.
600 439
600 440
600 441
600 442
217 706 12 102
217 706 12 192
217 706 12 432
217 706 12 422
211 204 12 012
211 204 12 022
217 706 12 862
217 706 12 872
600 463
211 104 12 037
218 204 12 017
600 652
217 706 12 097
217 104 12 017
211 104 01 062
600 331
217 204 11 017
217 704 11 052
217 104 12 012
217 706 12 012
211 104 12 412
217 605 12 212
215 104 12 032
212 324 12 032
218 324 12 012
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
5.10
5.08
5.09
5.07
5.06
5.05
5.11
5.21
5.04
5.12
5.03
5.13
5.05
5.01
5.14
5.15
5.02
5.16
5.20
5.17
5.19
5.18
83252902 1/2019-09 La
78-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
13 Spares
Pos.
5.21
83252902 1/2019-09 La
Description
W-FM plug
– X3-01 Motor On
– X3-02 Air pressure switch
– X3-03 Limit switch burner flange
– X3-04 Mains and safety circuit
– X4-01 Oil/Gas change-over
– X4-02 Ignition unit
– X4-03 Solenoid valve venting APS
– X5-01 Min. oil press. DSA58
– X5-02 Max. oil press. DSA46
– X5-03 Control circuit
– X6-01 Start release
– X6-02 Magnetic coupling - oil pump
– X6-03 Oil safety valve
– X7-01 Oil valve stage 2
– X7-02 Oil valve stage 3
– X7-03 Start release Gas
– X8-01 Oil - Gas- display
– X8-02 Oil valve additional
– X8-03 Oil valve 1; 2 x 110V
– X9-01 Gas, PV, V1, V2, SV
– X9-02 N, PE
– X9-03 Gas max./min.
– X10-01 Transformer 230/12V
– X10.02.1 Flame sensor QRB
– X10-02.2 Flame sensor QRI
– X50 CAN-Bus ABE
– X51 CAN-Bus actuator
– X52 Transformer 2 x 12V
– X60 Temperature sensor
– X61 Actual value U/I
– X62 Set value U/I
– X63 Output 4-20mA
– X70 Proximity switch motor
– X71 Gas meter
– X72 Oil meter
– X73 Frequency converter
79-84
Order No.
716 300
716 301
716 302
716 303
716 304
716 305
716 306
716 307
716 308
716 309
716 310
716 311
716 312
716 313
716 314
716 315
716 316
716 317
716 318
716 319
716 320
716 321
716 322
716 323
716 332
716 325
716 326
716 327
716 328
716 329
716 330
716 331
716 333
716 334
716 335
716 336
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
14 Notes
14 Notes
83252902 1/2019-09 La
80-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
15 Key word index
15 Key word index
A
ABE ........................................................................................ 12
Actuator......................................................................... 51, 54
Adjustment ........................................................................... 36
Air damper ................................................................ 9, 21, 53
Air damper setting .............................................................. 21
Air inlet mesh ....................................................................... 53
Air number ............................................................................ 43
Air regulator.................................................................. 52, 53
Ambient conditions............................................................. 15
Aperture ........................................................................ 19, 26
Approval data....................................................................... 13
Atomising pressure..................................................... 20, 37
B
Backup .................................................................................. 40
Bar .......................................................................................... 62
Boiler room ............................................................................. 6
Breaks in operation............................................................. 45
Burner control...................................................................... 14
Burner motor ................................................................ 12, 14
C
Capacity ................................................................................ 16
Capacity graph .................................................................... 16
CO content .......................................................................... 43
Combustion air ...................................................................... 6
Combustion chamber pressure ....................................... 16
Combustion control............................................................ 43
Combustion head ............................................................... 26
Combustion head extension.............................. 17, 19, 24
Combustion heat rating ............................................. 16, 21
Combustion limit ................................................................. 43
Combustion Manager ........................................................ 12
Commissioning.................................................................... 33
Consumption........................................................................ 14
Continuous operation .......................................................... 6
Conversion table ................................................................. 62
Coupling................................................................................ 54
D
Data backup ......................................................................... 40
Design lifespan ............................................................... 6, 46
Dimension E ......................................................................... 21
Dimension S1 ...................................................................... 21
Dimensions........................................................................... 17
Display ................................................................................... 32
Display and operating unit ................................. 12, 32, 57
Disposal .................................................................................. 7
Drilling diagram.................................................................... 19
Ducted air intake ............................................................ 6, 16
E
Electrical connection.......................................................... 30
Electrical data ...................................................................... 14
Electrodes............................................................................. 49
Emission................................................................................ 15
Emission class ..................................................................... 15
Excess air.............................................................................. 43
83252902 1/2019-09 La
Exchanging the unit ............................................................ 59
Extension............................................................................... 24
F
Fabrication number............................................................... 8
Fan pressure ........................................................................ 34
Fan wheel......................................................................... 9, 56
Fault ............................................................................... 58, 60
Filter ....................................................................................... 63
Flame sensor........................................................................ 12
Flame signal ......................................................................... 12
Flame tube....................................................................... 9, 19
Flame tube length ............................................................... 24
Flame tube setting ...................................................... 21, 24
Flow pressure ...................................................................... 28
Flow temperature ................................................................ 28
Flue gas losses.................................................................... 43
Flue gas measurement....................................................... 43
Flue gas system................................................................... 64
Flue gas temperature ......................................................... 43
Frequency converter .......................................................... 12
Fuel......................................................................................... 15
Fuel oil ................................................................................... 15
Full load ................................................................................. 38
Fusing .................................................................................... 14
G
Gas/air separator ................................................................ 64
Guarantee............................................................................... 5
H
Heat exchanger ................................................................... 19
Humidity ................................................................................ 15
I
Ignition electrode ................................................................ 49
Ignition electrodes .............................................................. 49
Ignition position ................................................................... 36
Ignition unit ........................................................................... 12
Installation............................................................................. 19
Installation elevation ................................................... 15, 16
Installation location ............................................................. 19
L
Liability..................................................................................... 5
Lifespan............................................................................ 6, 46
Limit switch........................................................................... 12
Load distribution ................................................................. 44
Lockout................................................................... 57, 58, 60
M
Mains voltage ....................................................................... 14
Max. oil pressure switch ............................................ 10, 41
mbar ....................................................................................... 62
Measuring device................................................................ 34
Metering slot ........................................................................ 10
Min. oil pressure switch............................................. 10, 41
Mixing head ..................................................................... 9, 21
81-84
Installation and operating instruction
Oil burner WM-L20/2-A R (W-FM100/200)
15 Key word index
Mixing pressure ................................................................... 34
Motor.............................................................................. 12, 31
Motor type ............................................................................ 14
N
Name plate ............................................................................. 8
Nozzle .................................................................................... 50
Nozzle distance ........................................................... 22, 24
Nozzle selection .................................................................. 20
Nozzle selection table ........................................................ 20
O
OFF function ........................................................................ 32
Oil circulation device.......................................................... 64
Oil circulation unit ............................................................... 64
Oil filter .................................................................................. 63
Oil hose ................................................................................. 28
Oil meter ............................................................................... 64
Oil nozzle .............................................................................. 50
Oil pressure measuring device ........................................ 34
Oil pump ......................................................... 10, 11, 28, 34
Oil quantity regulator.......................................................... 10
Oil supply...................................................................... 28, 63
Oil temperature.................................................................... 63
Oil throughput...................................................................... 38
Operating problems ........................................................... 60
Operating unit...................................................................... 32
Service interval .................................................................... 46
Service plan.......................................................................... 47
Setting diagram ................................................................... 21
Shutdown ............................................................................. 45
Shutdown time .................................................................... 45
Sleeve bearing..................................................................... 53
Solenoid valve...................................................................... 10
Sound .................................................................................... 15
Sound power level.............................................................. 15
Sound power levels............................................................ 15
Sound pressure level ......................................................... 15
Spares ................................................................................... 67
Spring bar coupling............................................................ 54
Stability problems ............................................................... 60
Standards ............................................................................. 13
Start problems ..................................................................... 60
Storage.................................................................................. 15
Suction resistance ...................................................... 28, 63
Supply.................................................................................... 28
Supply pressure .......................................................... 28, 34
Supply temperature ............................................................ 28
T
Temperature ......................................................................... 15
Throughput ........................................................................... 38
Transport............................................................................... 15
Type key .................................................................................. 8
U
P
Pa............................................................................................ 62
Partial load............................................................................ 40
Pascal .................................................................................... 62
Password .............................................................................. 36
Power consumption ........................................................... 14
Pre-filter................................................................................. 63
Pressure gauge ................................................................... 34
Pressure hose...................................................................... 27
Pressure measuring device .............................................. 34
Pressure regulating screw ................................................ 37
Pressure switch........................................................... 10, 41
Pulsating ............................................................................... 60
Pump....................................................................... 10, 28, 34
Pump coupling..................................................................... 55
Pump pressure ..................................................... 20, 34, 37
Unit ......................................................................................... 62
Unit fuse ................................................................................ 14
Unit of pressure................................................................... 62
V
Vacuum ................................................................................. 63
Vacuum gauge..................................................................... 34
Variable speed drive........................................................... 12
Voltage supply ..................................................................... 14
W
Weight................................................................................... 18
R
Refractory ............................................................................. 19
Reset...................................................................................... 59
Return .................................................................................... 28
Return pressure........................................................... 35, 37
Ring main operation ........................................................... 64
Ring main pump .................................................................. 64
S
Safety measures.................................................................... 6
Sequence of operation ...................................................... 11
Serial number......................................................................... 8
Service................................................................................... 46
Service contract .................................................................. 46
83252902 1/2019-09 La
82-84
83252902 1/2019-09 La
Max Weishaupt GmbH · 88475 Schwendi
Weishaupt close by? Addresses, telephone numbers etc. can be found
at www.weishaupt.de
We reserve the right to make changes. All rights reserved.
The complete program:
Reliable technology and prompt, professional service
W Burners
up to 570 kW
The compact burners, proven millions of times
over, are economical and reliable. Available as
gas, oil and dual fuel burners for domestic and
commercial applications.
The purflam® burner version with special
mixing head gives almost soot-free combustion
of oil with greatly reduced NOx emissions.
The wall-hung condensing boilers WTC-GW
have been developed to meet the highest
demands in ease of operation and efficiency.
Modulating operation means these units
operate quietly and economically.
monarch® WM Burners
and Industrial Burners
Floor-standing condensing boilers
for oil and gas
up to 1,200 kW
up to 11,700 kW
These legendary industrial burners are durable
and versatile.
Numerous variations of oil, gas and dual fuel
burners meet a wide range of applications and
capacity requirements.
The floor-standing condensing boilers
WTC-GB (up to 300 kW) and WTC-OB
(up to 45 kW) are efficient, low in pollutants
and versatile in use.
Even the largest capacities can be covered by
cascading up to four gas condensing boilers.
WKmono 80 Burners
Solar systems
up to 17,000 kW
The WKmono 80 burners are the most
powerful monoblock burners from Weishaupt.
They are available as oil, gas or dual fuel
burners and are designed for tough industrial
application.
The stylish flat-plate collectors are the ideal
complement for any Weishaupt heating
system. They are suitable for solar water
heating and for combined heating support.
With versions for on-roof, in-roof and flat roof
installations, solar energy can be utilised on
almost any roof.
WK Burners
Water heaters/Energy storage
up to 32,000 kW
These industrial burners of modular
construction are adaptable, robust and
powerful.
Even on the toughest industrial applications
these oil, gas and dual fuel burners operate
reliably.
The diverse program of potable water and
energy storage for various heat sources
includes storage volumes of 70 to 3,000 litres.
In order to minimize storage losses, potable
water cylinders from 140 to 500 litres are
available with highly efficient insulation using
vacuum insulation panels.
MCR Technology / Building Automation
from Neuberger
Heat pumps
From control panels to complete building management systems - at Weishaupt you can find
the entire spectrum of modern control
technology. Future orientated, economical and
flexible.
83252902 1/2019-09 La
Wall-hung condensing boilers
for gas
up to 240 kW
up to 180 kW
The heat pump range offers solutions for the
utilisation of heat from the air, the soil or
ground water.
Some systems are also suitable for cooling
buildings.
Service
Geothermal probe drilling
Weishaupt customers can be assured that
specialist knowledge and tools are available
whenever they are needed. Our service
engineers are fully qualified and have
extensive product knowledge, be it for burners,
heat pumps, condensing boilers or solar
collectors.
With its daughter company, BauGrund Süd,
Weishaupt also offers geothermal probe and
well drilling. With the experience of more than
10,000 systems and more than 2 million meters
of drilling, BauGrund Süd offers a
comprehensive service program.
Téléchargement