Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 83252902 1/2019-09 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 1 User instructions .............................................................................................................. 4 1.1 Target group .................................................................................................................. 4 1.2 Symbols .......................................................................................................................... 4 1.3 Guarantee and Liability ............................................................................................... 5 2 Safety ..................................................................................................................................... 6 2.1 Designated application ............................................................................................... 2.2 Safety measures ........................................................................................................... 2.2.1 Normal operation ................................................................................................... 2.2.2 Electrical connection ............................................................................................ 2.3 Alterations to the construction of the equipment ................................................. 2.4 Noise emission ............................................................................................................. 2.5 Disposal ......................................................................................................................... 3 6 6 6 6 7 7 7 Product description ........................................................................................................ 8 3.1 Type key ......................................................................................................................... 8 3.2 Serial number ................................................................................................................ 8 3.3 Function .......................................................................................................................... 9 3.3.1 Air supply ................................................................................................................ 9 3.3.2 Oil supply ............................................................................................................. 10 3.3.3 Electrical components ....................................................................................... 12 3.4 Technical data ............................................................................................................. 13 3.4.1 Approval data ...................................................................................................... 13 3.4.2 Electrical data ..................................................................................................... 14 3.4.3 Ambient conditions ............................................................................................ 15 3.4.4 Fuels ...................................................................................................................... 15 3.4.5 Emissions ............................................................................................................. 15 3.4.6 Rating .................................................................................................................... 16 3.4.7 Dimensions .......................................................................................................... 17 3.4.8 Weight .................................................................................................................. 18 4 Installation ........................................................................................................................ 19 4.1 Installation conditions ................................................................................................ 4.2 Check rating ................................................................................................................ 4.3 Set mixing head .......................................................................................................... 4.3.1 Setting diagram .................................................................................................. 4.3.2 Set mixing head without combustion head extension ............................... 4.3.3 Set mixing head with combustion head extension ..................................... 4.4 Burner installation ...................................................................................................... 5 19 20 21 21 22 24 26 Installation ........................................................................................................................ 28 5.1 Oil supply ..................................................................................................................... 28 5.2 Electrical connection ................................................................................................. 30 6 83252902 1/2019-09 La Operation .......................................................................................................................... 32 2-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning .............................................................................................................. 33 7.1 Prerequisite ................................................................................................................. 7.1.1 Connect measuring devices ............................................................................ 7.2 Adjusting the burner .................................................................................................. 7.3 Set oil pressure switch ............................................................................................. 7.4 Concluding work ........................................................................................................ 7.5 Check combustion ..................................................................................................... 7.6 Ratings apportionment ............................................................................................. 33 34 36 41 42 43 44 8 Shutdown .......................................................................................................................... 45 9 Servicing ............................................................................................................................ 46 9.1 Notes on servicing ..................................................................................................... 9.2 Service plan ................................................................................................................. 9.3 Hinge open the burner .............................................................................................. 9.4 Set ignition electrodes .............................................................................................. 9.5 Replace nozzle ............................................................................................................ 9.6 Removing and refitting air damper actuator ......................................................... 9.7 Removing air regulator .............................................................................................. 9.8 Set air regulator .......................................................................................................... 9.9 Removing and refitting oil quantity regulator actuator ....................................... 9.10 Set pump coupling .................................................................................................. 9.11 Removing fan wheel ................................................................................................ 10 Troubleshooting ............................................................................................................ 57 10.1 Procedures for fault conditions ............................................................................ 10.1.1 Fault .................................................................................................................... 10.1.2 Lockout .............................................................................................................. 10.2 Rectifying faults ........................................................................................................ 11 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 Technical documentation ......................................................................................... 62 11.1 Conversion table unit of pressure ........................................................................ 62 12 Project planning ............................................................................................................. 63 12.1 Oil supply .................................................................................................................. 12.1.1 Ring main operation ........................................................................................ 12.1.2 Oil circulation unit ............................................................................................ 12.2 Flue gas system ....................................................................................................... 12.3 Additional requirements ......................................................................................... 83252902 1/2019-09 La 63 64 64 64 65 13 Spares ................................................................................................................................. 66 14 Notes ................................................................................................................................... 80 15 Key word index .............................................................................................................. 81 3-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 1 User instructions 1 User instructions Translation of original operating instructions This manual forms part of the equipment and must be kept on site. Carefully read the manual prior to working on the unit. It is supplemented by the installation and operating instructions for the Combustion Manager. 1.1 Target group The manual is intended for the operator and qualified personnel. It should be observed by all personnel working with the unit. Work on the unit must only be carried out by personnel who have the relevant training and instruction. Persons with limited physical, sensory or mental capabilities may only work on the unit if they are supervised or have been trained by an authorised person. Children must not play with the unit. 1.2 Symbols Immediate danger with high risk. Non observance can lead to serious injury or death. DANGER Danger with medium risk. Non observance can lead to environmental damage, serious injury or death. WARNING Danger with low risk. Non observance can cause damage to the equipment and injury to personnel. CAUTION Important information Requires direct action Result after an action Itemisation Range of values … 83252902 1/2019-09 La 4-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 1 User instructions 1.3 Guarantee and Liability Guarantee and liability claims for personal and equipment damage are excluded, if they can be attributed to one or more of the following causes: non approved application, non-observance of the manual, operation with faulty safety equipment, continual operation despite a fault, improper installation, commissioning, operation and service, repairs, which have been carried out incorrectly, the use of non original Weishaupt parts, force majeure, unauthorised modifications made to the unit, the installation of additional components, which have not been tested with the unit, the installation of combustion chamber inserts, which impede full flame formation, unsuitable fuels, defects in the inlet lines. 83252902 1/2019-09 La 5-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 2 Safety 2 Safety 2.1 Designated application The burner is suitable for continuous operation (only in conjunction with QRI flame sensor) on heat exchangers to EN 303 and EN 267. If the burner is not used on combustion chambers to EN 303 and EN 267, a safety assessment of combustion and flame stability during individual process conditions and of the shutdown limits of the combustion plant has to be carried out and documented. The combustion air must be free from aggressive compounds (e.g. Halogens). If the combustion air in the boiler room is contaminated, increased cleaning and servicing will be required. In this case ducted air intake is recommended. The burner should only be used in enclosed rooms. Improper use could: endanger the health and safety of the user or third parties, cause damage to the unit or other material assets. 2.2 Safety measures Safety relevant fault conditions must be eliminated immediately. Components, which show increased wear and tear or whose design lifespan is or will be exceeded prior to the next service should be replaced as a precaution. 2.2.1 Normal operation All labels on the unit must be kept in a legible condition. Stipulated settings, service and inspection work should be carried out at regular intervals. Only operate the unit with its cover closed. Do not touch moving parts during operation. 2.2.2 Electrical connection For work carried out on live components: Observe the accident prevention instructions DGUV Regulation 3 and adhere to local directives, tools in accordance with EN 60900 should be used. 83252902 1/2019-09 La 6-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 2 Safety 2.3 Alterations to the construction of the equipment All conversions require written approval from Max Weishaupt GmbH. No additional components may be fitted, which have not been tested for use with the equipment. Use only original Weishaupt replacement parts. 2.4 Noise emission The noise emissions are determined by the acoustic behaviour of all components fitted to the combustion system. Prolonged exposure to high noise levels can lead to loss of hearing. Provide operating personnel with protective equipment. Noise emissions can further be reduced with a sound attenuator. 2.5 Disposal Dispose of all materials and components in a safe and environmentally friendly way at an authorised location. Observe local regulations. 83252902 1/2019-09 La 7-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3 Product description 3.1 Type key WM-L20/2-A R Type WM L 20 2 A Series: Monoblock monarch® Fuel: Oil EL Size Ratings size Construction Version R Type of control: modulating 3.2 Serial number The serial number on the name plate identifies the product. This is required by Weishaupt's customer service department. 1 1 Name plate Ser.No. 83252902 1/2019-09 La 8-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.3 Function 3.3.1 Air supply Air dampers The air dampers regulate the air quantity required for combustion. The combustion manager controls the air dampers via actuator. At burner shutdown the air dampers close automatically. At burner shutdown the air dampers close automatically. Fan wheel The fan wheel supplies the air from the air intake housing to the combustion head. Flame tube The air gap between flame tube and diffuser is adjusted by positioning the flame tube. This adjusts the mixing pressure and the air quantity required for combustion. 83252902 1/2019-09 La 9-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.3.2 Oil supply Oil pump The pump draws the oil through the supply line and carries it under pressure to the oil nozzle. The pressure regulating valve keeps the oil pressure constant. Solenoid valves The solenoid valves open and close the oil supply. Oil quantity regulator The oil quantity regulator is driven by the combustion manager via actuator. An oil metering vee slot in the oil quantity regulator changes the spill back quantity of the fuel and thus the atomised quantity of the oil at the oil nozzle. The oil quantity regulator has two metering slots. Each metering slot is matched with a specific oil throughput. The identity code numbers on the shaft of the oil quantity regulator denote the oil throughput range. 1 2 Identity code 1 2 Factory setting see burner data sheet. Oil throughput up to 280 kg/h greater than 280 kg/h Maximum oil pressure switch The maximum oil pressure switch monitors the pressure in the return. If the value set is exceeded, the burner switches off. Minimum oil pressure switch (optional) Depending on the burner application, optional equipment may be required for optimum operation [ch. 12.3]. The minimum oil pressure switch monitors the pump pressure in the supply. If the preset pressure is not achieved, the combustion manager initiates a lockout. 83252902 1/2019-09 La 10-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description Sequence of operation During the pre-purge time all solenoid valves are closed. For burner ignition, the combustion manager opens the solenoid valves. The oil quantity regulator is in the open position (ignition position). Due to the low resistance of the oil quantity regulator in the return only a small quantity of oil is atomised at the nozzle, the larger quantity flows to the pump return. If the load increases, the metering slot in the oil quantity regulator is reduces, this reduces the oil flow in the return and thus increases the oil quantity at the nozzle outlet. 1 3 2 4 P P 5 1 2 3 4 5 6 7 7 M 6 5 Oil pump Minimum oil pressure switch (optional) Solenoid valve supply (fitted in flow direction) Nozzle head with nozzle Solenoid valve return (fitted against flow direction) Oil quantity regulator Max. oil pressure switch One solenoid valve in the supply is always switched electrically in series with one solenoid valve in the return. The voltage of the solenoid coil is therefore 115 V at 230 V / 50 Hz mains voltage. 83252902 1/2019-09 La 11-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.3.3 Electrical components Combustion Manager The combustion manager W-FM is the control unit of the burner. It controls the sequence of operation, monitors the flame and communicates with all components. Display and operating unit (ABE) The ABE is used to display and alter the operational values and parameters of the combustion manager. It is connected by connection line and can be remove from the burner. Burner motor The burner motor drives the fan wheel and the oil pump. Without variable speed drive the combustion manager controls a contactor or star delta switching. With variable speed drive, a frequency converter is connected upstream. Ignition unit The electronic ignition unit creates a spark at the electrode, which ignites the fuel/ air mixture. Flame sensor The combustion manager monitors the flame signal via the flame sensor. If the flame signal becomes too weak, the combustion manager carries out a controlled shutdown. See installation and operating manual of the Combustion Manager W-FM for flame signal required. Limit switch The limit switch in the housing prevents burner start in the open position. 83252902 1/2019-09 La 12-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.4 Technical data 3.4.1 Approval data DIN CERTCO 5G1031 Basic standards EN 267:2011 Additional standards, see EU conformity certification. 83252902 1/2019-09 La 13-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.4.2 Electrical data Burner control Mains voltage / mains frequency Consumption at start Consumption during operation Power consumption Internal unit fuse External fuse 230 V/50 Hz max 295 W max 185 W max 1.6 A T6.3H, IEC 127-2/5 max 16 AB Burner motor WM-D112/140-2/3K5 Efficiency [η] 87.7 % (at 100 % load) 88.8% (at 75 % load) Type Poles Nominal load Mains frequency Mains voltage Speed Disposal Design height Ambient temperature Coolant temperature Operating temperature Explosion protection Consumption Power consumption External fuse direct start 87.4 % (at 50 % load) IE3 see name plate Max Weishaupt GmbH Max-Weishaupt-Straße 14 88475 Schwendi District Court Ulm HRB 640125 WM-D112/140-2/3K5 2 3.5 kW 50 Hz 380 … 415 V 2940 min-1 (rpm) see Ch. 2.3 Disposal 1000 m -15 … +40°C – max 40°C – max 4.1 kW max 7.2 A 25 A External fuse YΔ start 16 A External fuse frequency converter mounted 20 A External fuse frequency converter separate 16 A Efficiency class Year of manufacture Manufacturer 83252902 1/2019-09 La 14-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.4.3 Ambient conditions Temperature in operation –10(1 … +40 °C Temperature during transport / storage –20 … +70 °C relative humidity max 80 %, no dew point Installation elevation max 2000 m(2 (1 With the relevant suitable fuel oil and layout of oil supply. (2 Consultation with Weishaupt is required for higher installation elevation. 3.4.4 Fuels Fuel oil EL to DIN 51603-1 Fuel oil EL A Bio 10 to DIN 51603-6 Fuel oil EL to ÖNORM-C1109 (Austria) Fuel oil EL to SN 181 160-2 (Switzerland) 3.4.5 Emissions Flue gas To EN 267 the burner complies with emission class 2. The NOx values are influenced by: combustion chamber dimensions flue gas system fuel combustion air (temperature and humidity) medium temperature Combustion chamber dimensions, see Weishaupt Partner Portal / Documents and Applications / Online Applications / NOX calculation for burners. Sound levels Dual number noise emission values Measured sound power level LWA (re 1 pW) 87 dB(A)(1 Uncertainty value KWA Measured sound pressure level LpA (re 20 μPa) 4 dB(A) 80 dB(A)(2 Uncertainty value KpA 4 dB(A) (1 Determined to ISO 9614-2. (2 Determined at 1 metre distance from the front of the burner. The measured noise levels plus uncertainty values form the upper limit value, which could occur when measuring. 83252902 1/2019-09 La 15-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.4.6 Rating Combustion heat rating Combustion heat rating 600 … 2100 kW 50 … 176 kg/h(1 (1 The oil throughput data relates to a calorific value of 11.9 kWh/kg for fuel oil EL. Capacity graph Capacity graph to EN 267. The capacity data given relates to an installation elevation of 500 m above sea level. For installation elevations above 500 m a capacity reduction of approx. 1 % per 100 m applies. A limited capacity graph is valid for ducted air intake. 13 12 11 10 9 8 7 6 5 4 3 2 1 0 -1 2 -2 -3 500 700 50 900 70 1100 90 1300 110 1500 130 1 1 Combustion heat rating [kW] or [kg/h] 2 Combustion chamber pressure [mbar] 83252902 1/2019-09 La 16-84 1700 1900 150 2100 170 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 3.4.7 Dimensions 86 m 9m 8 mm 424 mm 198 mm 340 mm 84 0 209 mm mm 409 mm 225 mm 408 mm 573 mm 220 mm Burner 254 mm 1 810 mm 1 227 … 247 mm without combustion head extension 327 ± 3 mm with combustion head extension (100 mm) 427 ± 3 mm with combustion head extension (200 mm) 527 ± 3 mm with combustion head extension (300 mm) 83252902 1/2019-09 La 17-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 3 Product description 50 mm 165 mm 200 mm Mixing head 3.4.8 Weight approx. 96 kg 83252902 1/2019-09 La 18-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 4 Installation 4.1 Installation conditions Burner type and capacity graph Burner and heat exchanger must be matched. Check burner type and burner capacity. Installation location Prior to installation ensure that: the space for the burner hinging range is sufficient [ch. 3.4.7], sufficient combustion air is available, if necessary install ducted air intake, Prepare heat exchanger The refractory 3 must not protrude beyond the front edge of the combustion head. The refractory can take a conical shape (min 60°). Refractory may not be required on boilers with water-cooled front, unless the manufacturer gives other instructions. Following installation, the aperture 4 between flame tube and refractory should be filled with flame-proof, resilient insulating material. Do not make solid. Heat exchangers with deep refractories or thick doors, or heat exchangers with reverse flame combustion chambers may require a combustion head extension. Head extensions of 100, 200 and 300 mm are available. Dimension 2 then changes according to the head extension used. M12 1 45° 260 mm 220 mm 60° 4 260 mm 3 298 mm 2 The burner has to be hinged open by approx. 70 … 80° to allow removal of the mixing head. 1 Flange gasket 2 min 227 mm (combustion head OPEN) max 247 mm (combustion head CLOSED) 3 Refractory 4 Aperture 83252902 1/2019-09 La 19-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 4.2 Check rating The burner as delivered has been: pre-sized for a specific oil throughput, equipped with an oil nozzle type -w- K3 S1 50°. The exact details are documented on the burner data sheet. Pump pressure setting 30 bar Determine exact oil throughput at oil meter or by weighing. Nozzle selection table -w- K3 S1 50° The following minimum capacity values are achieved with an oil quantity regulator setting of 90°. Nozzle size [kg/h] 90 100 110 120 130 140 150 160 170 180 83252902 1/2019-09 La Burner capacity [kW] at pump pressure 20 bar 22 bar 24 bar 26 bar 851 893 934 976 898 941 984 1027 987 1035 1083 1130 1095 1147 1200 1252 1214 1272 1330 1389 1297 1359 1421 1483 1416 1483 1549 1616 1505 1576 1648 1719 1624 1700 1776 1853 1708 1788 1867 1947 20-84 28 bar 1017 1070 1178 2305 1447 1545 1682 1791 1929 2026 30 bar 1059 1113 1226 1357 1505 1607 1749 1862 2005 2106 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 4.3 Set mixing head 4.3.1 Setting diagram Set mixing head relative to the combustion heat rating required. Therefore the flame tube setting and air damper setting are matched. Do not operate the burner outside of the capacity graph. Determine the required flame tube setting (dimension S1) and air damper setting from diagram and note down. Example Burner rating required Combustion chamber pressure Flame tube setting dimension S1 (auxiliary dimension E) Air damper setting 13 12 60° 11 Example 1 1300 kW 1.5 mbar 123 mm (10 mm) 55° Example 2 1750 kW 2.5 mbar 114 mm (19 mm) > 90° 70° 80° 5 6 50° 10 9 40° 8 3 7 30° 6 20° 5 4 3 2 1 0 -1 2 -2 103 (30) 123 118 113 108 (10) (15) (20) (25) -3 -4 4 -5 500 700 900 1100 1300 1500 1700 1900 2100 1 1 2 3 4 Combustion heat rating [kW] Combustion chamber pressure [mbar] Air damper setting in degree of angle(1 Flame tube setting dimension S1 [mm](1 (auxiliary dimension E [mm])(1 5 Setting range of air dampers with flame tube setting CLOSED (123 mm) 6 Setting range for flame tube with air damper setting > 90° (1 Different settings may be required depending on site conditions. 83252902 1/2019-09 La 21-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 4.3.2 Set mixing head without combustion head extension Hinge open the burner [ch. 9.3]. 1. Set distance nozzle support to nozzle body The distance between nozzle support and nozzle body 2 must be 90 mm. If necessary adjust nozzle body: Undo screws 1 on nozzle support. set distance nozzle support to nozzle body to 90 mm, Re-tighten screws. 90 1 mm 2 2. Set nozzle distance Check nozzle distance (dimension A) using auxiliary dimension 2 between diffuser sleeve and burner flange. Nozzle distance (dimension A) 7 mm 10 mm 13 mm Auxiliary dimension 2 25 mm 28 mm 31 mm Factory setting The diffuser could become soiled if incorrectly positioned. Determine auxiliary dimension 2 at a minimum of 3 points (each offset by 120°). Check alignment of nozzle assembly to diffuser (even aperture). If necessary set nozzle distance: Undo screws 1. Rotate diffuser sleeve 3, until auxiliary dimension 2 has been reached. Re-tighten screws. 1 3 2 1 A 83252902 1/2019-09 La 22-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 3. Set distance flame tube to diffuser The distance of flame tube to diffuser (dimension S1) determined from the setting diagram is set between the flame tube and diffuser sleeve using auxiliary dimension E. Measure auxiliary dimension E and compare to the table below. Distance determined Flame tube to diffuser (dimension S1) 123 mm 118 mm 113 mm 108 mm 103 mm Auxiliary dimension E 10 mm (combustion head CLOSED) 15 mm 20 mm 25 mm 30 mm (combustion head OPEN) If the distance varies from the measured value by more than 5 mm, set flame tube: Undo screws 1. Adjust flame tube 2 until auxiliary dimension E has been reached, ensuring not to alter the setting of the diffuser sleeve 3. Centralise flame tube whilst checking the distance at a minimum of 3 positions (each offset by 120°). Re-tighten screws. 2 1 3 E 1 S1 Set ignition electrodes [ch. 9.4] 83252902 1/2019-09 La 23-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 4.3.3 Set mixing head with combustion head extension Hinge open the burner [ch. 9.3]. Remove nozzle assembly. 1. Check flame tube length Check total length of flame tube, see table. Extension Total length 100 mm 349 mm ±1 200 mm 449 mm ±1 300 mm 549 mm ±1 2. Nozzle distance and flame tube setting The nozzle distance and the flame tube setting must be matched to one another. Check nozzle distance, see table. Nozzle distance (dimension A) 7 mm 10 mm 13 mm Flame tube setting 4 11 mm 14 mm 17 mm Factory setting If necessary set nozzle distance: Undo locking screws 3. Adjust diffuser and set nozzle distance (dimension A). Re-tighten locking screws.Re-tighten locking screws. Match flame tube setting to nozzle distance: Undo screws 1. Adjust flame tube 2, until flame tube setting 4 has been reached. Centralise flame tube whilst checking the distance at a minimum of 3 positions (each offset by 120°). Re-tighten screws. After every alteration to the nozzle distance or to the flame tube setting: Check distance flame tube to diffuser. Set ignition electrodes [ch. 9.4] 2 1 4 1 3 A 83252902 1/2019-09 La 24-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 3. Set distance flame tube to diffuser The distance flame tube to diffuser (dimension S1) determined from the setting diagram is set at setting bolt 1 using auxiliary dimension EV. Measure auxiliary dimension EV and compare to the table below. Distance determined Flame tube to diffuser (dimension S1) 123 mm 118 mm 113 mm 108 mm 103 mm Auxiliary dimension Ev 30 mm (combustion head CLOSED) 25 mm 20 mm 15 mm 10 mm (combustion head OPEN) If auxiliary dimensions EV varies from the measured value by more than 5 mm: Undo locknut on setting bolt 1. Turn setting bolt until auxiliary dimension EV has been reached. Re-tighten locknut. 1 Ev S1 83252902 1/2019-09 La 25-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation 4.4 Burner installation Fit flange gasket 3 and hinged flange 2 to the boiler plate using screws 1. The aperture between combustion head and refractory should be filled with flame-proof, resilient insulating material. Do not make solid. 1 3 2 Using suitable lifting equipment lift burner and, using hinge pins 1 fit into hinged flange, observe pivoting direction. Without combustion head extension Close burner and secure with dome nut 2. 1 2 83252902 1/2019-09 La 26-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 4 Installation With combustion head extension Connect pressure hoses ensuring correct allocation. Place ignition lines from the hinged flange into the burner housing. R V Close burner and secure with dome nut 2. Remove view port cover. Plug in ignition lines 1. Refit view port cover. 2 1 83252902 1/2019-09 La 27-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 5 Installation 5 Installation 5.1 Oil supply Observe EN 12514-2, DIN 4755, TRÖI and local regulations. Check conditions for oil pump Suction resistance Supply pressure Supply temperature (1 Measured at the pump. max 0.4 bar(1 max 5 bar(1 max 140 °C(1 Check conditions for oil hoses Length Oil hose connection Threaded socket connection Nominal pressure Thermal load 1000 / 1300 mm M30 x 1.5 M30 x 1.5 x G1 10 bar max 100 °C Connect oil supply Damage to the oil pump caused by incorrect connection Mixing up supply and return can damage the oil pump. Ensure correct connection of oil hoses to the supply and return of the pump. CAUTION 1 2 1 Supply 2 Return 83252902 1/2019-09 La 28-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 5 Installation Connect oil supply and observe: do not twist oil hoses avoid mechanical tension consider length of hose required for the hinge range, do not kink oil hoses (curve radius 1 of 145 mm must be maintained). If these conditions for connection can not be met: Adapt oil supply on site. 1 Purge oil supply and ensure it is tight CAUTION Damage to oil meter in oil circulating device resulting from purging If an oil circulating device is fitted, the purging process could damage the integrated oil meter. Replace oil meter with adapter during purging. Oil pump seized due to running dry Pump could be damaged. Fill oil supply with oil and purge. CAUTION Ensure oil supply is tight. 83252902 1/2019-09 La 29-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 5 Installation 5.2 Electrical connection DANGER WARNING Risk of electric shock Working on the device when voltage is applied can lead to electric shock. Isolate the device from the power supply prior to starting any work. Safeguard against accidental restart. Electric shock caused by frequency converter It is possible that electrical components continue to carry voltage and cause electric shock even after the voltage supply has been disconnected. Wait approx. 5 minutes before commencing work. Electric voltage has dissipated. The electrical connection must only be carried out by qualified electricians. Observe local regulations. Connect combustion manager Use cable entry grommets on the housing. Connect wiring to wiring diagram enclosed. Control circuits, which are taken directly via a 16 AB fuse from a 3 phase or single phase alternating current supply, must only be connected between a phase conductor and earth potential neutral conductor. On mains supply, which does not have a neutral, the control voltage must be supplied via an isolating transformer. The pole of the transformer, which is to be used as the neutral conductor, must be earthed. Phase L must not be mixed up with the neutral conductor N. Contact protection will otherwise no longer be given. Malfunctions, which endanger operational safety could occur. The cable cross section of the voltage supply must be suitable for the nominal current of the external fuse (maximum 16 AB). All other cable connections must be suitable for the relevant internal unit fuse (T6.3H). Earthing and neutral conductor must conform to local regulations. The following applies for cable length: all cable lengths maximum 100 m, use only original Weishaupt parts as Bus line, install Bus line as line configuration. 83252902 1/2019-09 La 30-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 5 Installation Connecting the burner motor The motor must be protected against thermal overload and short circuit. Weishaupt recommend the use of a motor protection switch. Open terminal box on motor. Connect voltage supply to wiring diagram enclosed, observe motor rotation. Variable speed drive (optional) If the frequency converter is located on the motor, the cable to the frequency converter is not screened. If the frequency converter is separate the control line and the motor connection must be screened. Apply screen to the screen clamp on frequency converter. Use screen cable glands (metal) on the burner. 83252902 1/2019-09 La 31-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 6 Operation 6 Operation For further details see installation and operating instructions Combustion Manager. Display and operating unit (ABE) 4 1 3 2 1 Dial knob navigation through parameter structure; changing values select return/cancel return to operating display 2 [Enter] 3 [esc] 4 [info] OFF function Press [ENTER] and [esc] simultaneously. Immediate lockout. The lockout is stored in the fault history. 83252902 1/2019-09 La 32-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7 Commissioning 7.1 Prerequisite Commissioning must only be carried out by qualified personnel. Only correctly carried out commissioning ensures the operational safety. Prior to commissioning ensure that: all assembly and installation work has been carried out correctly, sufficient combustion air is available, if necessary install ducted air intake the annulus between flame tube and heat exchanger is filled the heat exchanger is filled with medium the regulating, control and safety devices are functioning and set correctly the flue gas ducts are unimpeded a measuring point conforming to standards is available to measure the flue gas the heat exchanger and flue gas ducting up to the test point are sound (extraneous air influences the test results) the operating instructions of the heat exchanger are complied with a heat demand is available Additional system-related tests could be necessary. Please observe the operating guidelines for the individual components. On installations with process equipment, the conditions for safe operation and commissioning must be met, see worksheet 8-1 (Print No. 831880xx). 83252902 1/2019-09 La 33-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7.1.1 Connect measuring devices Pressure measuring device for mixing pressure Open pressure test point for mixing pressure 1 and connect pressure measuring device. 1 Oil pressure measuring devices on oil pump WARNING Oil leakage from oil pressure measuring devices due to constant load Oil pressure measuring devices could be damaged and cause environmental pollution through leakage. Close or remove oil pressure measuring devices once commissioning is complete. Vacuum gauge for suction resistance/supply pressure. Pressure gauge for pump pressure. Close fuel shut off devices. Remove closing plug on the pump. Connect vacuum gauge 1 and pressure gauge 2. 1 83252902 1/2019-09 La 2 34-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning Oil pressure measuring device connected to the return line WARNING Oil leakage from oil pressure measuring devices due to constant load Oil pressure measuring devices could be damaged and cause environmental pollution through leakage. Close or remove oil pressure measuring devices once commissioning is complete. Pressure gauge for return pressure. Remove bypass plug from the return line for pressure gauge 1. Connect pressure gauge. 1 83252902 1/2019-09 La 35-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7.2 Adjusting the burner In addition to this chapter, the installation and operating manual of the Combustion Manager should be observed. This manual contains detailed information about: menu structure and navigation, parameter settings, editing of points, function, etc. Prerequisite Open oil shut off devices. Switch on voltage supply. 1. Switch off burner The ABE is in OperationalStat in the sub menu NormalOperation and displays current values. Exit level using the [esc] key. Select ManualOperation. Select Autom/Manual/Off. Set Burner Off. The burner switches off. Exit level using the [esc] key. 2. Enter password Select Param & Display. Select Access with HE (password for heating engineer). Enter HE password using dial knob and confirm with [ENTER]. 3. Check load limits Select RatioControl. Select OilSettings. Select LoadLimits. Select MinLoadOil and set 0.0%. Select MaxLoadOil and set 100%. Use [esc] key to return to the display LoadLimits. 4. Check ignition position The setting of the oil quantity regulator in ignition position is pre-set when supplied (see burner data sheet). Select SpecialPositions. Select IgnitionPos. Select IgnPosOil (setting oil quantity regulator in ignition position). Check IgnPosOil. Use [esc] key to return to the display IgnitionPos. 83252902 1/2019-09 La 36-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 5. Check mixing pressure in ignition position Select ProgramStop. Select 36 IgnPos. Use [esc] key to return to the display with OilSettings. Select Autom/Manual/Off. Select Manual (Burner On). The burner starts and stops in ignition position without flame formation Check rotation direction of burner motor The mixing pressure in ignition position must be 2 … 4 mbar above the combustion chamber pressure. If necessary, adjust mixing pressure via air damper setting: Select OilSettings Select SpecialPositions. Select IgnitionPos. Select IgnitionPosAir and adjust. Use [esc] key to return to the display IgnitionPos. Only in conjunction with frequency converter In oil operation, the ignition speed should be 100 %. 6. Ignition Set Program stop to 44 Interv 1. The burner ignites and the actuators stop in the ignition position. The pump pressure in ignition position must be26 … 29 bar, see burner data sheet. Check pump pressure at pressure gauge. Remove end cap 1. Undo lock nut 2. Set pump pressure using pressure regulating screw. increase pressure: clockwise rotation, decrease pressure: anticlockwise rotation. 2 1 Check combustion values in ignition position. Set O2 content of approx. 5 % by positioning oil quantity regulator (IgnPosOil), whilst observing return pressure and maintaining 12 bar. 83252902 1/2019-09 La 37-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7. Set intermediate load points Set ProgramStop to deactivated. Use [esc] key to return to the display SpecialPositions. Select CurveParams. Press [ENTER]. Point 1 is displayed. Point 1 has been factory preset to a specific oil throughput, see burner data sheet. Check combustion values Adjust air damper setting (Air): Press [ENTER] key. Select Change point?. Select Actuator positions with start. Call up and change values with dial knob and [ENTER]. Exit point 1 using [esc] key and save with [ENTER] key. Press [esc] key. The menu displays Point, Manual and the current actuator positions. In menu Point all load points can be adjusted. In menu point Manual the current burner capacity can be adjusted manually. Select Manual and confirm with [ENTER]. Increase burner rating using dial knob whilst observing combustion values (excess air) and flame stability. Set load point using [ENTER] key if either: the O2 content in the flue gas increases to above 7 %, the soot limit is reached, the CO content increases, the flame reaches the limit of stability. The new load point is displayed in menu Point and can be adjusted. Correct combustion values via oil quantity regulator position (Burn). Exit setting using [esc] and save with [ENTER]. Exit load point using [esc]. Repeat steps until full load (Load: 100) has been reached. 8. Adjust full load When adjusting, the ratings data given by the boiler manufacturer and the capacity graph of the burner should be observed [ch. 3.4.6]. The burner has been factory pre-sized for a specific oil throughput, see burner data sheet. Only in conjunction with frequency converter Select speed at full load as low as possible, but not less than 90 %. Observe flame stability. Set pump pressure and oil quantity regulator position to the data given on the burner data sheet. Determine oil throughput, if necessary adjust position of oil quantity regulator (Burn) until the oil throughput required is achieved. Check combustion values Determine combustion limit and set excess air [ch. 7.5]. The pump pressure must not be altered once this work has been completed. 83252902 1/2019-09 La 38-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 9. Re-define point 1 Drive to point 1 in menu Point, whilst observing the combustion values. Check combustion values and correct if necessary. Carry out load apportionment [ch. 7.6]. Only in conjunction with frequency converter In oil operation, the speed should only be reduced so far, that the pump pressure set at full load does not fall by more than 15 %. To allow a reduction of MinLoad after commissioning, point 1 should be set below the required partial load. However, it must lie within the capacity graph of the burner. 10. Delete intermediate load points Delete all load points except for point 1 and full load (Load: 100). When an intermediate load point is deleted, all points above this intermediate load point are reduced by one number. 11. Set new intermediate load points Starting at point 1, new load points must be set until full load is reached. A maximum of 15 load points can be programmed. A minimum of 5 load points are required for modulating operation. Increase burner rating in menu Manual, whilst observing combustion values. Set new intermediate load point using [ENTER] key. Optimise combustion at intermediate load point. Carry out load apportionment [ch. 7.6]. Repeat steps until full load (Load: 100) has been reached. Exit level using the [esc] key. 83252902 1/2019-09 La 39-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 12. Check start behaviour Restart burner in Manual operation. Check start behaviour and if necessary correct ignition position. If the ignition position has been altered: Re-check start behaviour. If the oil temperature has been altered: Re-check start behaviour. Restart each point and check combustion values. 13. Define partial load Select LoadLimits. Select MinLoad. Define and set partial load whilst: Maintain return pressure of 8 bar. observing data provided by boiler manufacturer, observing the burner capacity graph [ch. 3.4.6]. 14. Set burner to automatic operation Exit level using the [esc] key. Select Autom/Manual/Off. Set Automatic. Exit level using the [esc] key. If necessary adjust load controller. 15. Carry out data backup Exit level using the [esc] key. Select Updating. Select Param backup. Select LMV → AZL . Start data backup by pressing [ENTER] key. The values have been backed up from the combustion manager to the ABE. Exit level using the [esc] key. 83252902 1/2019-09 La 40-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7.3 Set oil pressure switch Minimum oil pressure switch in the flow (optional) Depending on the burner application, optional equipment may be required for optimum operation [ch. 12.3]. Remove end cap. Set minimum oil pressure switch in the supply to 5 bar below the minimum pump pressure. Refit end cap. Maximum oil pressure switch in the return Remove end cap. Set maximum oil pressure switch in the return to 5 bar, for ring main operation set to 5 bar above the ring main pressure.. Refit end cap. 83252902 1/2019-09 La 41-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7.4 Concluding work WARNING Oil leakage from oil pressure measuring devices due to constant load Oil pressure measuring devices could be damaged and cause environmental pollution through leakage. Close or remove oil pressure measuring devices once commissioning is complete. Check control and safety devices. Check tightness of oil carrying components. Enter combustion values and settings in the commissioning record and/or test sheet. Inform the operator about the use of the equipment. Hand the installation and operating manual to the operator and inform him that this should be kept with the appliance. Point out to operator that the installation should be serviced annually. 83252902 1/2019-09 La 42-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7.5 Check combustion Determine excess air Slowly close air damper(s) in the relevant operating point, until the combustion limit is reached (soot number approx. 1). Measure and document O2 content. Read air number (λ). Increase air number to ensure sufficient excess air: by 0.15 … 0.2 (equates to 15 … 20 % excess air), by more than 0.2 for more difficult conditions, such as: dirty combustion air, fluctuating intake temperature, fluctuating chimney draught. Example λ + 0.15 = λ* Set air number (λ*), do not exceed CO content of 50 ppm. Measure and document O2 content. Check flue gas temperature Check flue gas temperature. Ensure that the flue gas temperature complies with the data provided by the boiler manufacturer. If necessary adjust flue gas temperature, e g.: Increase burner capacity in partial load to avoid condensation in the flue gas ducts, except on condensing units. Reduce burner capacity in full load to improve efficiency. Adjust heat exchanger to the data provided by the manufacturer. Determine flue gas losses Drive to full load. Measure combustion air temperature (tL) near the air damper(s). Measure oxygen content (O2) and flue gas temperature (tA) at the same time at one point. Determine flue gas losses using the following formula: qA = qA tA tL O2 (tA - tL ) ( A2 )+B 21- O2 Flue gas losses [%] Flue gas temperature [°C] Combustion air temperature [°C] Volumetric content of oxygen in dry flue gas [%] Fuel factors A2 B 83252902 1/2019-09 La Fuel oil 0.68 0.007 43-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 7 Commissioning 7.6 Ratings apportionment The load points are automatically assigned relative to the capacity. Incorrect load distribution can cause operating problems during the load control. Assign capacity in % for load point using the following formula. Enter the calculated capacity for load point in Load. Load [%] = 83252902 1/2019-09 La 44-84 Throughput load point Throughput full load 100 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 8 Shutdown 8 Shutdown For breaks in operation: Switch off burner. Close fuel shut off devices. 83252902 1/2019-09 La 45-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9 Servicing 9.1 Notes on servicing DANGER WARNING Risk of electric shock Working on the device when voltage is applied can lead to electric shock. Isolate the device from the power supply prior to starting any work. Safeguard against accidental restart. Electric shock caused by frequency converter It is possible that electrical components continue to carry voltage and cause electric shock even after the voltage supply has been disconnected. Wait approx. 5 minutes before commencing work. Electric voltage has dissipated. Danger of getting burned on hot components Hot components can lead to burns. Allow components to cool. WARNING Servicing must only be carried out by qualified personnel. The combustion plant should be serviced annually. Depending on site conditions more frequent checks may be required. Components, which show increased wear and tear or whose design lifespan is or will be exceeded prior to the next service should be replaced as a precaution. Weishaupt recommends a service contract is entered into to ensure regular inspections. The following components must only be replaced and must not be repaired: combustion manager flame sensor actuator oil solenoid valve nozzle head, pressure switch, oil nozzle. Prior to every servicing Inform the operator about the extent of service work to be carried out. Switch off mains switch of installation and safeguard against accidental reactivation. Close fuel shut off devices. Following servicing Check tightness of oil carrying components. Check function of: ignition, flame monitoring, oil pump (pump pressure and suction resistance), Pressure switch control and safety devices. Check combustion values, if necessary re-adjust the burner. Enter combustion values and settings in the commissioning record and/or test sheet. 83252902 1/2019-09 La 46-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.2 Service plan Components Fan wheel Coupling cross on coupling centre piece Criteria / design lifespan(1 Soiling Damage Wear Service procedure Clean Replace Replace Air duct Air damper Soiling Soiling Distance to housing < 0.3 mm Sleeve bearing air damper shaft Has play Air regulator cladding Damage/brittleness/soiling View port cover Air escaping Ignition cable Damage Ignition electrode Soiling Damage/wear Combustion Manager 250 000 burner starts or 10 years(2 Flame sensor Soiling Damage Flame tube/diffuser Oil nozzle Oil hose 250 000 burner starts or 10 years(2 Soiling Damage Soiling/wear Recommendation: at least every 2 years Clean Clean Adjust [ch. 9.8] Replace [ch. 9.8] Replace Replace Replace Clean Replace Replace Clean Replace Clean Replace Replace Recommendation: at least every 2 years Replace Damage/oil escaping Recommendation: every 5 years Replace Pressure hose nozzle assembly Damage/oil escaping (with combustion head exten5 years sion) Oil solenoid valve Soundness Replace oil pump or solenoid valve (2 Oil quantity regulator 250 000 burner starts or 10 years Excess air due to wear Replace Hysteresis behaviour/damage/oil escaping 250 000 burner starts or 10 years(2 Oil pressure switch Switch point Check (2 250 000 burner starts or 10 years Replace (1 The specified design lifespan applies for typical use in heating, hot water and steam systems as well as for thermal process systems to EN 746. (2 If a criterion is reached, carry out maintenance measures. 83252902 1/2019-09 La 47-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.3 Hinge open the burner Observe notes on servicing [ch. 9.1]. Damage to oil hoses due to mechanical strain If oil hoses are leaking, oil can escape and lead to environmental damage. Avoid mechanical strain on the oil hoses when hinging open the burner. WARNING Check hinge pin 1 on burner flange is fitted correctly. Remove dome nut 2. Carefully hinge open the burner. 1 83252902 1/2019-09 La 48-84 2 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.4 Set ignition electrodes Observe notes on servicing [ch. 9.1]. The distance between the ignition electrodes and other components must be greater than the spark gap between the electrodes. The ignition electrodes must not touch the nozzle's atomising cone. Hinge open the burner [ch. 9.3]. Remove nozzle assembly (only with combustion head extension). Undo screw 1 on the ignition electrode holder. Set ignition electrodes. Tighten screw. 1 4. 83252902 1/2019-09 La 49-84 .. 6 mm 3 ... 4 mm Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.5 Replace nozzle Observe notes on servicing [ch. 9.1]. Do not clean nozzles, always fit new nozzles. Hinge open the burner. Remove ignition electrodes. Counter-hold on the nozzle assembly using a spanner and remove nozzle. Fit new nozzle ensuring it is seated tightly. Fit and adjust ignition electrodes [ch. 9.4]. With combustion head extension Hinge open the burner. Remove pressure hoses. Remove fixing screws from nozzle assembly bracket. Remove nozzle assembly. Measure distance to diffuser and record. Remove diffuser and nozzle support complete with ignition electrodes. Counter-hold on the nozzle assembly using a spanner and remove nozzle. Fit new nozzle ensuring it is seated tightly. Refit diffuser and nozzle support with ignition electrodes. Check, and if necessary adjust, nozzle distance to diffuser. Refit in reverse order, ensuring correct allocation of pressure hoses. 1 2 1 Nozzle 2 Nozzle assembly 83252902 1/2019-09 La 50-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.6 Removing and refitting air damper actuator Observe notes on servicing [ch. 9.1]. Removing Remove actuator cover. Unplug plug and remove cable entry gland 1. Undo locknut 2 on the coupling. Remove screws 3. Remove actuator from the coupling. 2 3 1 Refitting Refit actuator in reverse order, ensuring correct alignment of shaft key. Check address and Bus termination, see installation and operating manual Combustion Manager. 83252902 1/2019-09 La 51-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.7 Removing air regulator Observe notes on servicing [ch. 9.1]. Remove air damper actuator [ch. 9.6]. Remove inlet mesh 2. Remove air regulator 1. 1 2 83252902 1/2019-09 La 52-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.8 Set air regulator Observe notes on servicing [ch. 9.1]. Remove air inlet mesh [ch. 9.7]. If necessary remove air regulator [ch. 9.7]. Set air dampers Only tamper proof screws should be used in the air regulator section. If the distance of the air dampers to the housing on the actuator side is less than the dimension of 0.3 mm: Undo screws 1. Align air dampers. Re-tighten screws. Ensure air dampers have freedom of movement. Check sleeve bearing It must not be possible to axially move the air dampers without using force (0 mm play). If axial play 2 is present at the air dampers: Replace sleeve bearing. 83252902 1/2019-09 La 53-84 1 0.4 mm ±0.1 1 2 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.9 Removing and refitting oil quantity regulator actuator Observe notes on servicing [ch. 9.1]. Removing Remove actuator cover. Unplug plug and remove cable entry gland 3. Remove view port 1 – or – if the actuator is not at 0°, remove plug 2. Undo locknut 5. Remove screws 4. Remove actuator from the coupling. 1 2 5 4 3 If the intermediate housing or the coupling need to be replaced: Undo second locknut 2 of coupling. Carefully pull coupling from drive shaft. Remove shaft keys 1. Undo fixing screws and remove intermediate housing 3. 1 1 3 2 Refitting Refit actuator in reverse order. Ensure correct alignment of shaft keys. Push coupling carefully and without pressure onto shaft. Check address and Bus termination, see installation and operating manual Combustion Manager. 83252902 1/2019-09 La 54-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.10 Set pump coupling Observe notes on servicing [ch. 9.1]. A flexible pump coupling is fitted between fan wheel and oil pump. Remove air regulator cover. Undo Allen screw 2 on the pump coupling. Align pump coupling in such a way that no axial loading force is applied to the drive shaft and the coupling centre piece 1 is provided with an axial play of 1.5 mm. Tighten Allen screw. 2 1 83252902 1/2019-09 La 55-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 9 Servicing 9.11 Removing fan wheel Observe notes on servicing [ch. 9.1]. A tamper proof screw must be used when installing the fan wheel. Remove screw 1. Remove fan wheel with fan wheel puller from motor shaft. 1 83252902 1/2019-09 La 56-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 10 Troubleshooting 10 Troubleshooting 10.1 Procedures for fault conditions Check prerequisites for operation: Voltage supply available. Heating switch is set to On. Temperature regulator or pressure regulator on heat exchanger has been set correctly. Boiler or heating circuit control is functioning and set correctly. The combustion manager recognises irregularities of the burner and displays these on the display and operating unit (ABE). The following conditions can occur: Fault [ch. 10.1.1] Lockout [ch. 10.1.2] 83252902 1/2019-09 La 57-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 10 Troubleshooting 10.1.1 Fault If a fault occurs, the combustion manager initiates a controlled shutdown. The display and operating unit alternately shows the shutdown behaviour and the fault diagnosed as a plain text display. Example Safety shutdown Safety loop is open The burner restarts automatically as soon as the fault condition has been rectified. The following faults may be corrected by the operator: Fault Cause Safety circuit open Temperature limiter or pressure limiter on heat exchanger has triggered(1 Low water safety interlock on heat exchanger has triggered(1 Rectification Reset temperature limiter or pressure limiter on heat exchanger. Top up water. Reset low water safety interlock on heat exchanger. (1 Notify your heating contractor or Weishaupt Customer Service if the problem occurs repeatedly. All other faults must only be rectified by qualified personnel. Read the error code and proceed according to the error message, see installation and operating manual combustion manager. 83252902 1/2019-09 La 58-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 10 Troubleshooting 10.1.2 Lockout If a lockout condition occurs, the combustion manager initiates a fault shutdown and burner lockout. The display and operating unit alternately shows the shutdown behaviour and the fault diagnosed as a plain text display. Example Lockout Air pressure is off Once the fault has been rectified, the combustion manager has to be reset for restart. Lockouts must only be rectified by qualified personnel. Read the error code and proceed according to the error message, see installation and operating manual combustion manager. Resetting WARNING Damage resulting from incorrect fault repair Incorrect fault repair can cause damage to the equipment and injure personnel. Do not carry out more than 2 lockout resets successively. Faults must be rectified by qualified personnel. If the ABE displays a fault: Exit display using the [esc] key. Reset burner using the [ENTER] key. If the [esc] key has been pressed twice, reset can only be carried out via the menu. Select Operating display. Select Status/Reset. Current lockout is displayed. Exit display using the [esc] key. Reset burner using the [ENTER] key. Exchanging the unit If the combustion manager or the ABE are replaced: Select and check fault history and lockout history and include a copy when returning the unit for exchange. 83252902 1/2019-09 La 59-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 10 Troubleshooting 10.2 Rectifying faults The following faults must only be rectified by qualified personnel: Fault Cause Rectification Burner motor does not run No voltage Check voltage supply Overload relay or motor protection Check setting switch has tripped Motor contactor / frequency converter Replace motor contactor / frequency defective converter Motor defective Replace motor No ignition Ignition electrodes too far apart or short Set ignition electrode [ch. 9.4] circuit Ignition electrode dirty or wet Clean and adjust ignition electrode [ch. 9.4] Ceramic insulator defective Replace ignition electrode. Ignition cable defective Replace ignition cable Ignition unit defective Replace ignition unit Fuel valve does not open No voltage Check voltage supply Coil defective Replace coil Oil pump supplies no oil Shut off device closed Open shut off device Oil supply leaking Check oil supply [ch. 12.1] Anti siphon valve does not open Check valve and replace if necessary Oil filter of oil supply soiled Clean filter insert or replace Oil pump defective Replace oil pump No oil throughput at the nozzle Nozzle blocked Replace nozzle No flame formation despite igni- Ignition electrode set incorrectly Set ignition electrode [ch. 9.4] tion and fuel Mixing pressure too high Correct mixing pressure in ignition load setting, if necessary adjust mixing head [ch. 4.3] Poor start behaviour of burner Mixing pressure too high Correct mixing pressure in ignition load setting, if necessary adjust mixing head [ch. 4.3] Ignition electrode set incorrectly Set ignition electrode [ch. 9.4] Too much or too little fuel Correct fuel quantity in ignition position via fuel actuator Combustion manager does not Flame sensor soiled Clean flame sensor detect a flame signal Flame signal insufficient Check flame signal Check flame sensor Check burner setting Flame sensor defective Replace flame sensor Combustion pulsating or burner Incorrect combustion air quantity Check combustion values booming Mixing head set incorrectly Set mixing head [ch. 4.3] Back pressure from the system Check flue gas system [ch. 12.2] Flame failure during operation Oil supply leaking / suction resistance Check oil supply [ch. 12.1] too high Oil nozzle soiled/worn Replace nozzle Flame signal insufficient Check flame signal Check flame sensor Check burner setting 83252902 1/2019-09 La 60-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 10 Troubleshooting The following faults must only be rectified by qualified personnel: Fault Cause Oil pump makes severe mech- Oil pump sucks air anical noise Suction resistance in oil line too high Oil nozzle atomisation uneven Combustion head is contaminated with oil or has heavy carbon deposits Fuel valve does not close tight Heavy material erosion on the flame tube 83252902 1/2019-09 La Rectification Ensure oil supply is tight Clean filter Check oil supply [ch. 12.1] Nozzle soiled/worn Replace nozzle Oil nozzle defective Replace nozzle Mixing head set incorrectly Set mixing head [ch. 4.3] Incorrect combustion air quantity Adjust burner Boiler room ventilated insufficient Ensure sufficient boiler room ventilation Nozzle assembly and diffuser not Check centralisation of nozzle ascentred sembly to diffuser Dirt particles in the fuel valve Replace fuel valve High boiler room temperatures or acidic Use H1 flame tube with higher temcombustion air due to ambient condiperature resistance tions 61-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 11 Technical documentation 11 Technical documentation 11.1 Conversion table unit of pressure Bar 0.1 mbar 1 mbar 10 mbar 100 mbar 1 bar 10 bar 83252902 1/2019-09 La Pa 10 100 1 000 10 000 100 000 1 000 000 62-84 hPa 0.1 1 10 100 1 000 10 000 Pascal kPa 0.01 0.1 1 10 100 1 000 MPa 0.00001 0.0001 0.001 0.01 0.1 1 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 12 Project planning 12 Project planning 12.1 Oil supply Observe EN 12514-2, DIN 4755, TRÖI and local regulations. General information relating to the oil supply Do not use cathode protection system with steel tanks. With oil temperatures < 5 °C, the separation of paraffin can cause oil lines, oil filters and nozzles to become blocked. Avoid placing oil tanks and pipelines in areas subject to frost. The oil supply should be installed in such a way that it is possible to hinge open the burner. Fit oil filter in front of pump, maximum mesh aperture 100 μm. Suction resistance and supply pressure CAUTION Pump damage due to excessive suction resistance A suction resistance greater than 0.4 bar can damage the pump. Reduce suction resistance – or – install oil supply pump or suction unit, whilst observing the maximum supply pressure at the oil filter. The suction resistance depends on: suction line length and diameter, pressure loss of oil filter and other components, lowest oil level in the oil storage tank (max 3.5 m below the oil pump). Shut off devices at the burner CAUTION Damage caused by the shut off device closing too fast Pressure surges and cavitation can damage the components of the oil supply. When testing the operation of the limit switches the shut off device must only be closed until the safety shut off responds. The shut off device can only be closed completely when the oil pump has shut off. The isolating valves operate mechanically in compound and are fitted with a limit switch, which inhibits burner operation when the isolating valves are closed. Protect shut off devices in the return line from accidental closure. The installation of non return valves is not permitted. 83252902 1/2019-09 La 63-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 12 Project planning 12.1.1 Ring main operation Oil supply via ring main system is recommended for: large industrial and district heating installations, which are run almost continually, larger distances, several burners. For installation and function drawing for ring main operation, see Technical worksheets. The installation of a duplex oil pump station as ring main pump is recommended. Cleaning and service work on the pump or oil filter is then possible during burner operation. The supply quantity must be a minimum of one and a half to twice the total firing rates of all burners supplied by the ring main. The burners are connected to the ring main via a two pipe system. Set ring main pressure for fuel oil EL via pressure regulating valve to 1 … 1.5 bar. The oil filter must be suitable for the ring main pressure. An oil circulation device or Weishaupt gas/air separator should be fitted at each oil outlet point. Observe information label on separator. 12.1.2 Oil circulation unit The ring main supply can be fitted with an oil circulation unit. The unit contains: oil meter, oil filter, circulation tank, safety valve. Recommendation Weishaupt oil circulation unit W-OC-… 12.2 Flue gas system When designing the flue gas system observe BDH Info sheet No. 32 "Requirements on flue gas systems, see www.bdh-koeln.de. 83252902 1/2019-09 La 64-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 12 Project planning 12.3 Additional requirements Additional requirements for burners for liquid and gaseous fuels to EN 267: the pressure equipment operates in accordance with the Pressure Equipment Directive 2014/68/EU, as components of industrial thermal process plants in accordance with EN 746-2, on steam and hot water water-tube boilers in accordance with EN 12952-8. PED 2014/68/EU X EN 746-2 EN 12952-8 X X X X X X X X X X X X X X Components Requirement Burner control, combustion manager Flame monitor, flame sensor Control device air/fuel ratio Air monitoring device, air pressure switch Minimum fuel pressure monitoring device Maximum fuel pressure monitoring device Oil solenoid valve Manual shut off device for all fuels Safety devices for save operation Designed for continuous operation greater than 1200 kW self-checking X Electrical equipment Only for burners with return flow nozzle. (2 Only for continuous operation without monitoring. (1 83252902 1/2019-09 La 65-84 ISO 23552-1 Min. pressure switch to EN 1854 Min. oil pressure switch(2 Max. oil pressure switch(1 2 x flow, 2 x return, EN 23553-1 Isolating valve Connected to the input of the combustion manager in the closed circuit current principle EN 50156 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares 13 Spares 1.01 1.07 (1 1.06 (1 1.03 (1 1.05 1.10 1.04 (1 1.02 1.09 1.08 1.20 1.11 1.12 1.14 1.16 1.14 1.15 1.21 1.18 1.15 1.13 83252902 1/2019-09 La 1.19 66-84 1.17 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares Pos. 1.01 1.02 1.03 1.04 1.05 1.06 1.07 1.08 1.09 1.10 1.11 1.12 1.13 1.14 1.15 1.16 1.17 1.18 1.19 1.20 1.21 83252902 1/2019-09 La Description View port cover complete View port set View port closing cover – Spring nut 4 x 9 Hinge pin 14 x 277 Circlip 10 Hinged flange – Screw M12 x 35 – Washer B13 DIN 125 St Screw M12 x 70 DIN 931 8.8 Dome nut M12 DIN 1587 Washer B13 DIN 125 St Flange gasket 330/340 x 202 - TK298 Cable entry W-FM complete Air regulator housing Air regulator cladding Screw M6 x 185 DIN 912 Screw M6 x 35 / 250 Washer 5.1 x 11 x 0.6 Air regulator cover Lining air regulator cover Spring nut 6 x 20 Name plate Cable gland set 67-84 Order No. 211 204 01 022 211 104 01 192 211 104 01 132 412 509 211 304 01 077 431 604 211 204 01 027 402 705 430 801 401 701 412 401 430 801 211 204 01 057 211 104 01 052 211 204 02 157 211 204 02 167 402 408 211 204 02 137 430 015 211 204 02 197 211 204 02 187 412 506 211 204 01 067 211 204 00 512 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares 2.05 2.04 2.01 2.02 2.06 2.06 2.03 2.07 2.08 2.09 2.10 2.16 2.15 2.17 (1 2.18 (1 (1 (1 (1 (1 2.20 2.26 (1 2.22 2.21 (1 2.25 2.19 2.23 2.24 2.24 2.12 2.27 2.13 2.21 2.14 2.14 2.22 2.11 83252902 1/2019-09 La 68-84 (1 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares Pos. 2.01 2.02 2.03 2.04 2.05 2.06 2.07 2.08 2.09 2.10 2.11 2.12 2.13 2.14 2.15 2.16 2.17 2.18 2.19 2.20 2.21 2.22 2.23 2.24 2.25 2.26 2.27 83252902 1/2019-09 La Description Motor WM-D112/140-2/3K5 with motor contactor Motor contactor B7, 230V 50Hz Cable gland set Motor WM-D112/140-2/3K5 for frequency converter mounted Frequency converter configured WM-D112/140-2/3K5 for W-FM 200 Shaft key 6 x 6 x 45 Fan wheel TS-S 268 x 104 S1 (50Hz) – fan wheel puller (tool) Washer 8.5 x 22 Screw M8 x 20 DIN 7991 with Precote Inlet nozzle 285 x 209 x 43 (50Hz) Air inlet mesh – Screw M5 x 16 Duo Taptite Air regulator complete Air regulator Air damper – Screw M4 x 10 DIN 912 with TufLok Actuator SQM45.291 B9 3Nm – Cable entry cpl. with 2 W-FM plugs Shaft key 3 x 3.7 DIN 6888 Air damper shaft with coupling Air damper shaft with spring pin Sleeve bearing set air regulator Air regulator scale Adjusting lever Screw M5 x 12 with Precote Ball joint rod Screw M6 x 16 with TufLok Screw M6 x 110 DIN 7500 Washer A6.4 DIN 125 Washer 5.1 x 11 x 0.6 69-84 Order No. 215 204 07 010 702 818 211 204 00 512 215 204 07 020 211 204 07 077 490 316 211 204 08 011 111 111 00 012 111 612 08 097 404 414 211 204 02 017 211 204 02 222 409 312 211 204 02 142 211 204 02 147 211 204 02 077 402 264 651 501 217 605 12 052 490 157 211 204 02 202 211 204 02 212 211 104 02 502 211 314 02 177 211 104 02 047 211 104 02 187 211 104 02 192 402 268 409 364 430 400 430 015 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares 3.50* 3.50* 3.04 3.51* 3.01 3.51* 3.03 3.02 3.01 3.02 3. 3.08 3.02 3.05 3. 3.07 3.03 3.02 3.06 3.05 3.10 3.11 3.12 3.13 3.21 3.09 3.22 3.24 3.20 3.12 3.14 3.19 3.25 3.22 3.23 3.28 3.27 3.02 3.05 3.26 3.15 3.18 3.17 3.02 3.16 3.29 3.45 3.49 3.47 3.46 3.48 3.30 3.31 3.32 3.35 3.44 3.34 3.38 3.39 3.41 3.40 3.42 83252902 1/2019-09 La 70-84 3.02 3.02 3.05 3.29 3.33 3.37 3.40 3.05 3.03 3.48 3.43 3.02 3.03 3.35 3.36 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares Pos. 3.01 3.02 3.03 3.04 3.05 3.06 3.07 3.08 3.09 3.10 3.11 3.12 3.13 3.14 3.15 3.16 3.17 3.18 3.19 3.20 3.21 3.22 3.23 3.24 3.25 3.26 3.27 3.28 3.29 3.30 3.31 3.32 3.33 3.34 3.35 3.36 83252902 1/2019-09 La Description Threaded socket 6LL M10X1 X G 1/4 Sealing ring A13.5 x 17 x 1.5 DIN 7603 Cu Solenoid valve 6027 NC DN3.5 110-120V 50Hz Solenoid coil 110-120V 50Hz 20W Screwed union 24-SDSX-L10-G¼A-ST-CH60 Screwed union 24-SWT-L10-ST Bypass plug BUZ 10-L with nut Pressure gauge 0 to 40 bar with ball valve Oil line 10 x 1.0 return solenoid valve Screwed union 24-BDE-L10-G¼B-ST-C21 Threaded socket G⅜ x G¼I x 20 Sealing ring A 17 x 21 x 1.5 DIN 7603 Cu Oil quantity regulator W-ÖMR 1 f. W-FM Screwed union 24-SDSX-L10-G⅜A-ST-CH60 Oil line 10 x 1.0 suppl. oil regulator Screwed union 24-SWL-L10-ST Screwed union 24-SWE-L10-ST Oil line 10 x 1.0 x 68 distributor piece Threaded socket G¼I x G½I x 40 Sealing ring C6.2 x 17.5 x 2 DIN 16258 Cu Pressure switch type DSB 146 F931 1-10bar Shaft key 3 x 3.7 DIN 6888 Interm. housing for oil regulator series B View port 33 x 33 x 6 Oblong plug GPN 270 R 3015 Spring coupling bar series 2 Actuator SQM45.291 B9 3Nm – Cable entry cpl. with 1 W-FM plugs Oil line 10 x 1.0 flow S-SV Threaded socket 10 x G¼ x 50 Threaded socket 10L M16 x 1.5 x G½ x 34 Sealing ring A21 x 26 x 1.5 DIN 7603 Cu Pump TA2C 4010-7W Edge sealing ring GP-SR-G½B-H4.5-ST Screwed union 24-BDEX-L18-G½B-ST-C21 Screwed union 24-SWS-L18-L10-ST-CP1L Union nut 24-N-L18-ST 71-84 Order No. 140 223 85 067 440 010 604 872 604 692 452 253 452 501 211 304 13 012 110 011 50 012 215 204 06 028 452 603 211 373 15 127 440 003 211 704 15 202 452 277 215 204 06 038 452 551 452 451 212 374 06 038 290 504 13 037 440 007 640 102 490 157 211 704 15 272 211 404 17 027 446 115 217 704 15 107 651 501 217 605 12 042 215 204 06 018 151 101 26 012 111 574 06 017 440 020 601 050 450 652 450 650 452 151 452 803 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares 3.50* 3.50* 3.04 3.51* 3.01 3.51* 3.03 3.02 3.01 3.02 3. 3.08 3.02 3.05 3. 3.07 3.03 3.02 3.06 3.05 3.10 3.11 3.12 3.13 3.21 3.09 3.22 3.24 3.20 3.12 3.14 3.19 3.25 3.22 3.23 3.28 3.27 3.02 3.05 3.26 3.15 3.18 3.17 3.02 3.16 3.29 3.45 3.49 3.47 3.46 3.48 3.30 3.31 3.32 3.35 3.44 3.34 3.38 3.39 3.41 3.40 3.42 83252902 1/2019-09 La 72-84 3.02 3.02 3.05 3.29 3.33 3.37 3.40 3.05 3.03 3.48 3.43 3.02 3.03 3.35 3.36 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares Pos. Description 3.37 Collar screw GP-BDBS-L15-G½-ST 3.38 Sealing ring A27 x 32 x 2 DIN 7603 Cu 3.39 Threaded socket DN 20 M30 x 1.5 x M26 x1.5 3.40 Oil hose DN20 1000 lg identification black 3.41 Threaded socket DN 20 M30 x 1.5 x G1 3.42 Sealing ring A33 x 39 x 2 DIN 7603 Cu 3.43 Pipe elbow DN 20 M30x1.5xM30x1.5 x G⅛ 3.44 Threaded socket DN 20 M30 x 1.5 x G½ 3.45 Vacuum gauge -1+9 bar for TA pump 3.46 Pressure gauge 0 to 40 bar for TA pump 3.47 Pump coupling 54.3 x D 35 3.48 Universal joint 3.49 Coupling centre piece 235 mm 3.50 Pressure hose DN 6 650 mm* 3.51 Nut M16 x 1.5 * * Only in conjunction with combustion head extension. 83252902 1/2019-09 La 73-84 Order No. 450 651 440 039 111 782 06 027 491 034 112 151 00 057 440 032 453 251 112 654 00 017 210 204 06 192 210 204 06 182 218 324 09 012 111 151 09 017 211 402 09 012 210 201 10 012 210 104 10 087 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares 4.01 4.03 4.04 4.05 4.06 4.05 4.12 4.09 4.08 4.07 4.01 4.02* 4.04 4.05 4.06* 4.05 4.10* 4.09* 4.12 4.11* 83252902 1/2019-09 La 74-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares Pos. 4.01 Description Flame tube – WM-L20/2 – H1 WM-L20/2 4.02 Extension pipe – extended by 100 mm* – extended by 200 mm* – extended by 300 mm* 4.03 Diffuser 165 x 50 4.04 Ignition electrode holder 4.05 Ignition electrode 4.06 Ignition cable 11 /4.1 – 400 mm (Standard) – 500mm (for 100 mm extension)* – 500mm (for 200 mm extension)* – 700mm (for 300 mm extension)* 4.07 Fixing plate for nozzle assembly 4.08 Nozzle support 4.09 Nozzle head – Standard – extended by 100 mm* – extended by 200 mm* – extended by 300 mm* 4.10 Nozzle support for extension* 4.11 Diffuser for extension* 4.12 Spill type nozzle – K3S1 70 kg 50° – K3S1 80 kg 50° – K3S1 90 kg 50° – K3S1 100 kg 50° – K3S1 110 kg 50° – K3S1 120 kg 50° – K3S1 130 kg 50° – K3S1 140 kg 50° – K3S1 150 kg 50° – K3S1 160 kg 50° – K3S1 170 kg 50° – K3S1 180 kg 50° – K3S1 190 kg 50° – K3S1 200 kg 50° – K3S1 210 kg 50° * Only in conjunction with combustion head extension. 83252902 1/2019-09 La 75-84 Order No. 111 762 14 047 111 762 14 067 150 518 14 057 150 518 14 067 150 518 14 077 211 204 14 012 211 104 10 107 211 104 10 047 211 104 11 032 211 104 11 042 211 104 11 052 218 204 11 072 211 104 10 097 211 204 10 017 215 204 10 012 210 205 10 012 210 205 10 022 210 205 10 032 210 104 10 067 210 204 14 022 602 557 602 558 602 559 602 560 602 561 602 562 602 563 602 564 602 565 602 566 602 567 602 568 602 583 602 569 602 584 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares 5.10 5.08 5.09 5.07 5.06 5.05 5.11 5.21 5.04 5.12 5.03 5.13 5.05 5.01 5.14 5.15 5.02 5.16 5.20 5.17 5.19 5.18 83252902 1/2019-09 La 76-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares Pos. 5.01 5.02 5.03 5.04 5.05 5.06 5.07 5.08 5.09 5.10 5.11 5.12 5.13 5.14 5.15 5.16 5.17 5.18 5.19 5.20 83252902 1/2019-09 La Description ABE for W-FM 100/200 – Western Europe 1 (GB, D, F, I, E, P) – Western Europe 2 (GB, NL, DK, S, N, FIN) – Eastern Europe 1 (GB, PL, H, CZ, KRO, SLO) – Eastern Europe 2 (GB, D, RUS, TR, RO, BG) Plug cable W-FM…ABE – ABE fitted to housing – ABE fitted external 4000 mm – ABE fitted external 2500 mm – ABE fitted external 1500 mm Cover – ABE inbuilt – ABE external Combustion manager 230 V 50/60 Hz – W-FM 100 without load controller – W-FM 100 with load controller – W-FM 200 Stay bolt cover W-FM Mounting plate for W-FM Flame sensor QRI 2B2.B180B Flange for flame sensor QRI Seal for flame sensor flange Limit switch Transf. for W-FM 100/200 AGG 5.220 230 V Seal for ignition unit 2 pole Ignition unit type W-ZG02 230V with W-FM plug Plug cable W-FM transf. 12-0-12V Plug cable W-FM transf. 230V/12V Plug cable for pressure switch DSB158 Plug cable W-FM - air actuator Plug cable SQM to SQM 500mm with angle Plug cable with plug X8-02 solenoid valve Plug cable with plug X8-03 solenoid valve 77-84 Order No. 600 439 600 440 600 441 600 442 217 706 12 102 217 706 12 192 217 706 12 432 217 706 12 422 211 204 12 012 211 204 12 022 217 706 12 862 217 706 12 872 600 463 211 104 12 037 218 204 12 017 600 652 217 706 12 097 217 104 12 017 211 104 01 062 600 331 217 204 11 017 217 704 11 052 217 104 12 012 217 706 12 012 211 104 12 412 217 605 12 212 215 104 12 032 212 324 12 032 218 324 12 012 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares 5.10 5.08 5.09 5.07 5.06 5.05 5.11 5.21 5.04 5.12 5.03 5.13 5.05 5.01 5.14 5.15 5.02 5.16 5.20 5.17 5.19 5.18 83252902 1/2019-09 La 78-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 13 Spares Pos. 5.21 83252902 1/2019-09 La Description W-FM plug – X3-01 Motor On – X3-02 Air pressure switch – X3-03 Limit switch burner flange – X3-04 Mains and safety circuit – X4-01 Oil/Gas change-over – X4-02 Ignition unit – X4-03 Solenoid valve venting APS – X5-01 Min. oil press. DSA58 – X5-02 Max. oil press. DSA46 – X5-03 Control circuit – X6-01 Start release – X6-02 Magnetic coupling - oil pump – X6-03 Oil safety valve – X7-01 Oil valve stage 2 – X7-02 Oil valve stage 3 – X7-03 Start release Gas – X8-01 Oil - Gas- display – X8-02 Oil valve additional – X8-03 Oil valve 1; 2 x 110V – X9-01 Gas, PV, V1, V2, SV – X9-02 N, PE – X9-03 Gas max./min. – X10-01 Transformer 230/12V – X10.02.1 Flame sensor QRB – X10-02.2 Flame sensor QRI – X50 CAN-Bus ABE – X51 CAN-Bus actuator – X52 Transformer 2 x 12V – X60 Temperature sensor – X61 Actual value U/I – X62 Set value U/I – X63 Output 4-20mA – X70 Proximity switch motor – X71 Gas meter – X72 Oil meter – X73 Frequency converter 79-84 Order No. 716 300 716 301 716 302 716 303 716 304 716 305 716 306 716 307 716 308 716 309 716 310 716 311 716 312 716 313 716 314 716 315 716 316 716 317 716 318 716 319 716 320 716 321 716 322 716 323 716 332 716 325 716 326 716 327 716 328 716 329 716 330 716 331 716 333 716 334 716 335 716 336 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 14 Notes 14 Notes 83252902 1/2019-09 La 80-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 15 Key word index 15 Key word index A ABE ........................................................................................ 12 Actuator......................................................................... 51, 54 Adjustment ........................................................................... 36 Air damper ................................................................ 9, 21, 53 Air damper setting .............................................................. 21 Air inlet mesh ....................................................................... 53 Air number ............................................................................ 43 Air regulator.................................................................. 52, 53 Ambient conditions............................................................. 15 Aperture ........................................................................ 19, 26 Approval data....................................................................... 13 Atomising pressure..................................................... 20, 37 B Backup .................................................................................. 40 Bar .......................................................................................... 62 Boiler room ............................................................................. 6 Breaks in operation............................................................. 45 Burner control...................................................................... 14 Burner motor ................................................................ 12, 14 C Capacity ................................................................................ 16 Capacity graph .................................................................... 16 CO content .......................................................................... 43 Combustion air ...................................................................... 6 Combustion chamber pressure ....................................... 16 Combustion control............................................................ 43 Combustion head ............................................................... 26 Combustion head extension.............................. 17, 19, 24 Combustion heat rating ............................................. 16, 21 Combustion limit ................................................................. 43 Combustion Manager ........................................................ 12 Commissioning.................................................................... 33 Consumption........................................................................ 14 Continuous operation .......................................................... 6 Conversion table ................................................................. 62 Coupling................................................................................ 54 D Data backup ......................................................................... 40 Design lifespan ............................................................... 6, 46 Dimension E ......................................................................... 21 Dimension S1 ...................................................................... 21 Dimensions........................................................................... 17 Display ................................................................................... 32 Display and operating unit ................................. 12, 32, 57 Disposal .................................................................................. 7 Drilling diagram.................................................................... 19 Ducted air intake ............................................................ 6, 16 E Electrical connection.......................................................... 30 Electrical data ...................................................................... 14 Electrodes............................................................................. 49 Emission................................................................................ 15 Emission class ..................................................................... 15 Excess air.............................................................................. 43 83252902 1/2019-09 La Exchanging the unit ............................................................ 59 Extension............................................................................... 24 F Fabrication number............................................................... 8 Fan pressure ........................................................................ 34 Fan wheel......................................................................... 9, 56 Fault ............................................................................... 58, 60 Filter ....................................................................................... 63 Flame sensor........................................................................ 12 Flame signal ......................................................................... 12 Flame tube....................................................................... 9, 19 Flame tube length ............................................................... 24 Flame tube setting ...................................................... 21, 24 Flow pressure ...................................................................... 28 Flow temperature ................................................................ 28 Flue gas losses.................................................................... 43 Flue gas measurement....................................................... 43 Flue gas system................................................................... 64 Flue gas temperature ......................................................... 43 Frequency converter .......................................................... 12 Fuel......................................................................................... 15 Fuel oil ................................................................................... 15 Full load ................................................................................. 38 Fusing .................................................................................... 14 G Gas/air separator ................................................................ 64 Guarantee............................................................................... 5 H Heat exchanger ................................................................... 19 Humidity ................................................................................ 15 I Ignition electrode ................................................................ 49 Ignition electrodes .............................................................. 49 Ignition position ................................................................... 36 Ignition unit ........................................................................... 12 Installation............................................................................. 19 Installation elevation ................................................... 15, 16 Installation location ............................................................. 19 L Liability..................................................................................... 5 Lifespan............................................................................ 6, 46 Limit switch........................................................................... 12 Load distribution ................................................................. 44 Lockout................................................................... 57, 58, 60 M Mains voltage ....................................................................... 14 Max. oil pressure switch ............................................ 10, 41 mbar ....................................................................................... 62 Measuring device................................................................ 34 Metering slot ........................................................................ 10 Min. oil pressure switch............................................. 10, 41 Mixing head ..................................................................... 9, 21 81-84 Installation and operating instruction Oil burner WM-L20/2-A R (W-FM100/200) 15 Key word index Mixing pressure ................................................................... 34 Motor.............................................................................. 12, 31 Motor type ............................................................................ 14 N Name plate ............................................................................. 8 Nozzle .................................................................................... 50 Nozzle distance ........................................................... 22, 24 Nozzle selection .................................................................. 20 Nozzle selection table ........................................................ 20 O OFF function ........................................................................ 32 Oil circulation device.......................................................... 64 Oil circulation unit ............................................................... 64 Oil filter .................................................................................. 63 Oil hose ................................................................................. 28 Oil meter ............................................................................... 64 Oil nozzle .............................................................................. 50 Oil pressure measuring device ........................................ 34 Oil pump ......................................................... 10, 11, 28, 34 Oil quantity regulator.......................................................... 10 Oil supply...................................................................... 28, 63 Oil temperature.................................................................... 63 Oil throughput...................................................................... 38 Operating problems ........................................................... 60 Operating unit...................................................................... 32 Service interval .................................................................... 46 Service plan.......................................................................... 47 Setting diagram ................................................................... 21 Shutdown ............................................................................. 45 Shutdown time .................................................................... 45 Sleeve bearing..................................................................... 53 Solenoid valve...................................................................... 10 Sound .................................................................................... 15 Sound power level.............................................................. 15 Sound power levels............................................................ 15 Sound pressure level ......................................................... 15 Spares ................................................................................... 67 Spring bar coupling............................................................ 54 Stability problems ............................................................... 60 Standards ............................................................................. 13 Start problems ..................................................................... 60 Storage.................................................................................. 15 Suction resistance ...................................................... 28, 63 Supply.................................................................................... 28 Supply pressure .......................................................... 28, 34 Supply temperature ............................................................ 28 T Temperature ......................................................................... 15 Throughput ........................................................................... 38 Transport............................................................................... 15 Type key .................................................................................. 8 U P Pa............................................................................................ 62 Partial load............................................................................ 40 Pascal .................................................................................... 62 Password .............................................................................. 36 Power consumption ........................................................... 14 Pre-filter................................................................................. 63 Pressure gauge ................................................................... 34 Pressure hose...................................................................... 27 Pressure measuring device .............................................. 34 Pressure regulating screw ................................................ 37 Pressure switch........................................................... 10, 41 Pulsating ............................................................................... 60 Pump....................................................................... 10, 28, 34 Pump coupling..................................................................... 55 Pump pressure ..................................................... 20, 34, 37 Unit ......................................................................................... 62 Unit fuse ................................................................................ 14 Unit of pressure................................................................... 62 V Vacuum ................................................................................. 63 Vacuum gauge..................................................................... 34 Variable speed drive........................................................... 12 Voltage supply ..................................................................... 14 W Weight................................................................................... 18 R Refractory ............................................................................. 19 Reset...................................................................................... 59 Return .................................................................................... 28 Return pressure........................................................... 35, 37 Ring main operation ........................................................... 64 Ring main pump .................................................................. 64 S Safety measures.................................................................... 6 Sequence of operation ...................................................... 11 Serial number......................................................................... 8 Service................................................................................... 46 Service contract .................................................................. 46 83252902 1/2019-09 La 82-84 83252902 1/2019-09 La Max Weishaupt GmbH · 88475 Schwendi Weishaupt close by? Addresses, telephone numbers etc. can be found at www.weishaupt.de We reserve the right to make changes. All rights reserved. The complete program: Reliable technology and prompt, professional service W Burners up to 570 kW The compact burners, proven millions of times over, are economical and reliable. Available as gas, oil and dual fuel burners for domestic and commercial applications. The purflam® burner version with special mixing head gives almost soot-free combustion of oil with greatly reduced NOx emissions. The wall-hung condensing boilers WTC-GW have been developed to meet the highest demands in ease of operation and efficiency. Modulating operation means these units operate quietly and economically. monarch® WM Burners and Industrial Burners Floor-standing condensing boilers for oil and gas up to 1,200 kW up to 11,700 kW These legendary industrial burners are durable and versatile. Numerous variations of oil, gas and dual fuel burners meet a wide range of applications and capacity requirements. The floor-standing condensing boilers WTC-GB (up to 300 kW) and WTC-OB (up to 45 kW) are efficient, low in pollutants and versatile in use. Even the largest capacities can be covered by cascading up to four gas condensing boilers. WKmono 80 Burners Solar systems up to 17,000 kW The WKmono 80 burners are the most powerful monoblock burners from Weishaupt. They are available as oil, gas or dual fuel burners and are designed for tough industrial application. The stylish flat-plate collectors are the ideal complement for any Weishaupt heating system. They are suitable for solar water heating and for combined heating support. With versions for on-roof, in-roof and flat roof installations, solar energy can be utilised on almost any roof. WK Burners Water heaters/Energy storage up to 32,000 kW These industrial burners of modular construction are adaptable, robust and powerful. Even on the toughest industrial applications these oil, gas and dual fuel burners operate reliably. The diverse program of potable water and energy storage for various heat sources includes storage volumes of 70 to 3,000 litres. In order to minimize storage losses, potable water cylinders from 140 to 500 litres are available with highly efficient insulation using vacuum insulation panels. MCR Technology / Building Automation from Neuberger Heat pumps From control panels to complete building management systems - at Weishaupt you can find the entire spectrum of modern control technology. Future orientated, economical and flexible. 83252902 1/2019-09 La Wall-hung condensing boilers for gas up to 240 kW up to 180 kW The heat pump range offers solutions for the utilisation of heat from the air, the soil or ground water. Some systems are also suitable for cooling buildings. Service Geothermal probe drilling Weishaupt customers can be assured that specialist knowledge and tools are available whenever they are needed. Our service engineers are fully qualified and have extensive product knowledge, be it for burners, heat pumps, condensing boilers or solar collectors. With its daughter company, BauGrund Süd, Weishaupt also offers geothermal probe and well drilling. With the experience of more than 10,000 systems and more than 2 million meters of drilling, BauGrund Süd offers a comprehensive service program.