16
2.1.5 Automatic Load Control
2.1.5.1 Mechanical Governors
Automatic turbine regulation is achieved by governor speed droop settings. This involves a response of the
fly balls (mechanical governor) to changes in the rotational speed. Because of the inertia of mechanical
system and fly-balls, the governor does not respond immediately when the generator load is varied
suddenly. There is a certain time lag (or delay) between the actual load change and the governor response.
The turbine governors were able to maintain a uniform rotational speed of the generating set at all operating
conditions. However, the actual speed of the turbine deviates from the rated speed within certain limits.
Speed droop usually varied between zero and six percent.
2.1.5.2 Analogue Electronic Governors
Electronic governors later introduced respond not only to changes in the rotational speed, but also to
accelerations during load variations. The governor responds to the maximum acceleration and start
opening/closing the turbine gates to a significant extend before the change in the rotational speed of the
generator. The principal advantage of such a governor is that an abrupt variation of the load causes a far
smaller temporary change (temporary speed droop) in the rotational speed of the generating set than the
speed sensitive regulation alone. Feed back of the actual change in servomotor function provides an
integral function for limiting temporary speed droop and thus providing PID control.
In both cases frequency control is provided by speed level setting (speed at no load) manually by the
operator at regular intervals, generally half an hour.
2.1.5.3 Reactive Power Control
Reactive power control is also provided by providing parallel running compensation (droop setting) in the
generating sets.
2.1.6 Machine Running Supervision
Once the unit is started and synchronized with the system, the operating personnel in the control room have
to perform or supervise the following three important functions of the unit.
(i) Load-frequency control
(ii) Reactive power and voltage control
(iii) Supervision of alarm and protective equipment
Functions of the above are discussed below:
2.1.6.1 Load Frequency Control
In an isolated system consisting of a generator and load, the varying demand of the load can be satisfied
entirely by the governor action. The governor of the unit is set to maintain the frequency at 50 Hz by
setting the speed droop indicator to zero. The machine speed will be maintained exactly at 50 Hz with
varying load demands provided the amount of load is not greater than the unit’s ability to carry it.
When a unit is operating in an interconnected system it is not possible, and is indeed virtually, impossible
to set all governors to respond isochronously to maintain constant frequency. In such cases unit speed
droop is set at 3 to 8 percent depending on the system’s load sharing requirement. A governor set on 5
percent speed droop will cause its generator to accept 100 percent of its capacity when there is frequency
droop of five percent. Depending on its regulating ability, unit can be adjusted to help maintain system
frequency, which is the exact indication of the balance between supply and demand. The operator in the
control room, on receipt of orders from the central load dispatch office, adjusts the speed level of the unit to
assist the system to maintain frequency at 50 Hz. In the case of units fitted with automatic load-frequency
control device, the speed level is adjusted from the load dispatch office itself. Automatic load frequency
control is rarely employed being costly.