LEGENDA COLORI CONDUTTORI
BK - NERO
BLACK
OG ARANCIO
ORANGE
RD ROSSO
RED
VI VIOLA
VIOLET
BU BLU
BLUE
GY GRIGIO
GRAY
BN MARRONE
BROWN
CI CIANO
CYAN
GN VERDE
GREEN
WH BIANCO
WHITE
WIRING COLOR CABLE NOTE COSTRUTTIVE
AD ECCEZIONE DEI CASI IN CUI E' ESPRESSAMENTE INDICATO
LE APPARECCHIATURE DELLO SCHEMA SONO SEMPRE RAPPRESENTATE
IN ASSENZA DI TENSIONE, DI PRESSIONE E MANCANZA DI FLUIDO
CONSTRUCTION NOTE
EXCEPT WHERE INDICATED ALL EQUIPMENTS IN THE WIRING DIAGRAMS ARE
SHOWN WITHOUT VOLTAGE, PRESSURE AND FLOW
1- SE NON DIVERSAMENTE INDICATO IL CABLAGGIO DOVRA' ESSERE
ESEGUITO NEL SEGUENTE MODO: 1- UNLESS OTHERWISE INDICATED THE WIRING SHALL BE AS FOLLOWS
:
A) I COLLEGAMENTI RELATIVI AI CAVI DI POTENZA DOVRANNO ESSERE
REALIZZATI CON CONDUTTORE DI SEZ. MINIMA 2,5 mmq DI COLORE NERO
A NORME CEI 20-22
A) POWER CABLE CONNECTIONS SHALL BE WIRED WITH BLACK
CONDUCTOR SIZE 2,5 mmq TYPE CEI 20-22
B) I COLLEGAMENTI RELATIVI ALLE SCHEDE DEGLI INGRESSI E DELLE
USCITE DEL PLC DOVRANNO ESSERE CABLATI CON CONDUTTORE
DI SEZ. MINIMA 0,5 mmq CIANO TRANNE COMUNI (+ e -) DI SEZ. MINIMA 1
mmq BLU E GRIGIO
B) PROGRAMMABLE CONTROLLER INPUTS/OUTPUTS
SHALL BE WIRED WITH CYAN CONDUCTOR WITH SIZE MIN 0,5 mmq
EXCEPT COMMON (+ e -) SIZE MIN. 1 mmq BLUE AND GREY
C) I CIRCUITI AUSILIARI 110Vac DOVRANNO ESSERE REALIZZATI CON
CONDUTTORE DI SEZIONE MINIMA 1,5 mmq ROSSO (FASE) / ROSSO (FASE
A TERRA)
C) AUXILIARY CIRCUITS 110Vac SHALL BE WIRED WITH RED CONDUCTOR
(PHASE) / RED CONDUCTOR (PHASE TO GROUND) WITH SIZE MIN 1,5 mmq
D) I CIRCUITI AUSILIARI 220Vac DOVRANNO ESSERE REALIZZATI CON
CONDUTTORE DI SEZIONE MINIMA 1,5 mmq VIOLA (FASE) / VIOLA (FASE A
TERRA)
D) AUXILIARY CIRCUITS 220Vac SHALL BE WIRED WITH VIOLET
CONDUCTOR (PHASE) / VIOLET CONDUCTOR (PHASE TO GROUND) WITH
SIZE MIN 1,5 mmq
E) I CIRCUITI AUSILIARI 24Vac DOVRANNO ESSERE REALIZZATI CON
CONDUTTORE DI SEZIONE MINIMA 1,5 mmq ROSSO (FASE) / ROSSO (FASE
A TERRA)
E) AUXILIARY CIRCUITS 24Vac SHALL BE WIRED WITH RED CONDUCTOR
(PHASE) / RED CONDUCTOR (PHASE TO GROUND) WITH SIZE MIN 1,5 mmq
F) I CIRCUITI AUSILIARI 24Vdc DOVRANNO ESSERE REALIZZATI CON
CONDUTTORE DI SEZIONE MINIMA 1,5 mmq BLU (+) / GRIGIO (- A TERRA) F) AUXILIARY CIRCUITS 24Vdc SHALL BE WIRED WITH BLUE CONDUCTOR
(+) / GRAY CONDUCTOR (- TO GROUND) WITH SIZE MIN 1,5 mmq
G) I COLLEGAMENTI RELATIVI ALLE SCHEDE DEGLI INGRESSI E USCITE
ANALOGICI DEL PLC E LE MORSETTIERE DOVRANNO ESSERE REALIZZATI
CON CAVETTO SCHERMATO MIN 0,5 mmq A NORME CEI 20-22 (BIANCO - /
MARRONE +)
G) PROGRAMMABLE CONTROLLER ANALOG INPUT AND OUTPUT AND
TERMINAL STRIPS SHALL BE WIRED WITH CONDUCTOR SHIELDED SIZE
MIN 0,5 mmq TYPE CEI 20-22 (WHITE - / BROWN +)
MARSINA